BRK electronic First Alert SC9120BA User Manual Download Page 2

7

8

Printed in Mexico   M08-0121-014   

K1   10/15

BRK Electronics

®

is a registered trademark of BRK Brands, Inc.

First Alert

®

is a registered trademark of the First Alert Trust.

9

10

11

12

WEEKLY TESTING

•   NEVER use an open flame of any kind to test this unit. You

might accidentally damage or set fire to the unit or to your

home. The built-in test switch accurately tests the unit’s

operation as required by Underwriters Laboratories of

Canada

(ULC).

NEVER use vehicle exhaust! Exhaust may

cause permanent damage and voids your warranty.

      •   DO NOT stand close to the Alarm when the horn is sounding.

Exposure at close range may be harmful to your hearing.

When testing, step away when horn starts sounding.

It is important to test this unit every week to make sure it is working

properly. Using the test button is the recommended way to test this

Smoke/CO Alarm.

1.   Push and hold the Test/Silence button on the cover until you hear a

“chirp.” The “chirp” marks the start of the self-test sequence.

2.   During testing, you will hear a loud, repeating horn pattern: 

3 beeps, pause, 3 beeps while the red smoke LED flashes. Then

you will hear a loud, repeating horn pattern: 4 beeps, pause, 4

beeps, pause, while the red CO LED flashes.

3.   When testing a series of interconnected units you must test each

unit individually. Make sure all units alarm when each one is tested.

If the Smoke/CO Alarm does not test properly:

1.   Make sure the AC power is applied and battery is fresh and installed

correctly.

2.   Be sure the alarm is clean and dust-free.

3.   Test the unit again.

4.   If a Latch is set, the first TEST switch activation may be interpreted

as a "Clear Latch" signal.

If the Smoke/CO Alarm is still not working properly, replace it immediately.

Refer to the “Limited Warranty” at the end of this manual.

If there is still a problem, do not try to fix the Alarm yourself. 

This will void your warranty!

REGULAR MAINTENANCE

Use only the replacement batteries listed below. The unit may not

operate properly with other batteries. Never use rechargeable 

batteries since they may not provide a constant charge.

This unit has been designed to be as maintenance-free as possible, but

there are a few simple things you must do to keep it working properly:

•     Test it at least once a week.

•     Clean the Smoke/CO Alarm at least once a month; gently vacuum

the outside of the Smoke/CO Alarm using your household vacuum’s

soft brush attachment. Test the Smoke/CO Alarm. Never use water,

cleaners or solvents since they may damage the unit.

•     If the Smoke/CO Alarm becomes contaminated by excessive dirt,

dust and/or grime, and cannot be cleaned to avoid unwanted

alarms, replace the unit immediately.

•     Relocate the unit if it sounds frequent unwanted alarms. See “Where

This Alarm Should Not Be Installed” for details.

•     When the battery back-up becomes weak, the Alarm will “chirp”

about once a minute (the low battery warning). This warning should

last 7 days, but you should replace the battery immediately to 

continue your protection. 

This Alarm must have AC or battery

power to operate. If AC power fails, and the battery is dead 

or missing, the Alarm cannot operate.

DO NOT spray cleaning chemicals or insect sprays directly on or near

the Alarm. DO NOT paint over the Alarm. Doing so may permanently

damage the Alarm.
CHOOSING A REPLACEMENT BATTERY:

This Smoke/CO Alarm requires one standard 9V alkaline battery. The

following alkaline batteries are acceptable as replacements: Duracell

#MN1604 or MX1604; Eveready “Energizer” 522. You can also use an

Ultralife 9V lithium battery #U9VL for longer service life between battery

changes. 

These batteries are available at many local retail stores.

All the batteries specified above are acceptable replacement batteries

for this unit. Regardless of the manufacturer’s suggested battery life,

you MUST replace the battery immediately once the unit starts “chirp-

ing” (the “low battery warning”). For any device employing a battery,

constant exposure to high or low humidity may reduce battery life.

Actual battery service life depends on the Alarm and the environment in

which it is installed. All the batteries specified above are acceptable

replacement batteries for this unit. Regardless of the manufacturer’s

suggested battery life, you MUST replace the battery immediately once

the unit starts “chirping” (the “low battery warning”).

Always use the exact batteries specified by this User’s Manual.  DO

NOT use rechargeable batteries. Clean the battery contacts and also

those of the device prior to battery installation. Install batteries correctly

with regard to polarity (+ and -).

Please dispose of or recycle used batteries properly, following any local

regulations.  Consult your local waste management authority or recy-

cling organization to find an electronics recycling facility in your area.

DO NOT DISPOSE OF BATTERIES IN FIRE.  BATTERIES MAY

EXPLODE OR LEAK.

Keep battery out of reach of children.  In the event a battery is swal-

lowed, immediately contact your poison control center, your physician,

or the Canadian Battery Ingestion hotline at 1-416-813-5900 as serious

injury may occur.

POTENTIAL

SOURCES OF CO

IN THE HOME

Fuel-burning appli-

ances like:

portable

heater, gas or wood burn-

ing fireplace, gas kitchen

range or cooktop, gas

clothes dryer.

Damaged or insufficient

venting:

corroded or 

disconnected water

heater vent pipe, leaking

chimney pipe or flue, or

cracked heat exchanger, blocked or clogged chimney opening.

Improper use of appliance/device:

operating a barbecue grill or 

vehicle in an enclosed area (like a garage or screened porch).

Transient CO Problems:

“transient” or on-again-off-again CO problems

can be caused by outdoor conditions and other special circumstances.

The following conditions can result in transient CO situations:

1.   Excessive spillage or reverse venting of fuel appliances caused by

outdoor conditions such as:

      •  Wind direction and/or velocity, including high, gusty winds. Heavy

air in the vent pipes (cold/humid air with extended periods

between cycles).

      •  Negative pressure differential resulting from the use of exhaust

fans.

      •  Several appliances running at the same time competing for limited

fresh air.

      •  Vent pipe connections vibrating loose from clothes dryers, 

furnaces, or water heaters.

      •  Obstructions in or unconventional vent pipe designs which can

amplify the above situations.

2.   Extended operation of unvented fuel burning devices (range, oven, 

fireplace).

3.   Temperature inversions, which can trap exhaust close to the ground.

4.   Car idling in an open or closed attached garage, or near a home.

These conditions are dangerous because they can trap exhaust in your

home. Since these conditions can come and go, they are also hard to

recreate during a CO investigation.

HOW CAN I PROTECT MY FAMILY FROM CO 

POISONING?

A CO Alarm is an excellent means of protection. It monitors the air 

and sounds a loud alarm before Carbon Monoxide levels become

threatening for average, healthy adults.

A CO Alarm is not a substitute for proper maintenance of home 

appliances.

To help prevent CO problems and reduce the risk of CO poisoning:

      •  Clean chimneys and flues yearly. Keep them free of debris, leaves,

and nests for proper air flow. Also, have a professional check for

rust and corrosion, cracks, or separations. These conditions can

prevent proper air movement and cause backdrafting. Never “cap”

or cover a chimney in any way that would block air flow.

      •  Test and maintain all fuel-burning equipment annually. Many local

gas or oil companies and HVAC companies offer appliance

inspections for a nominal fee.

      •  Make regular visual inspections of all fuel-burning appliances.

Check appliances for excessive rust and scaling. Also check the

flame on the burner and pilot lights. The flame should be blue. 

A yellow flame means fuel is not being burned completely and 

CO may be present. Keep the blower door on the furnace closed.

Use vents or fans when they are available on all fuel-burning

appliances. Make sure appliances are vented to the outside. Do

not grill or barbecue indoors, or in garages or on screen porches.

      •  Check for exhaust backflow from CO sources. Check the draft

hood on an operating furnace for a backdraft. Look for cracks on

furnace heat exchangers.

      •  Check the house or garage on the other side of shared wall.

      •  Keep windows and doors open slightly. If you suspect that CO 

is escaping into your home, open a window or a door. Opening

windows and doors can significantly decrease CO levels.

In addition, familiarize yourself with all enclosed materials. Read

this manual in its entirety, and make sure you understand what to

do if your CO Alarm sounds.

ABOUT SMOKE ALARMS

Battery (DC) operated Smoke Alarms:

Provide protection even when

electricity fails, provided the batteries are fresh and correctly installed.

Units are easy to install, and do not require professional installation.

However, they do not provide interconnected functionality.

AC powered Smoke Alarms: 

Can be interconnected so if one unit

senses smoke, all units alarm. They do not operate if electricity fails.

AC with battery (DC) back-up: 

will operate if electricity fails, provided

the batteries are fresh and correctly installed. AC and AC/DC units

must be installed by a qualified electrician.

Wireless Interconnected Alarms:

Offer the same interconnected 

functionality as with hardwired alarms, without wires. Units are easy 

to install and do not require professional installation. They provide 

protection even when electricity fails, provided the batteries are fresh

and correctly installed.

Smoke Alarms for Solar or Wind Energy users and battery backup

power systems:

AC powered Smoke Alarms should only be operated

with true or pure sine wave inverters. Operating this Smoke Alarm with

most battery-powered UPS (uninterruptible power supply) products or

square wave or “quasi sine wave” inverters 

will damage the Alarm

If you are not sure about your inverter or UPS type, please consult with

the manufacturer to verify.

Smoke Alarms for the hearing impaired: 

Special purpose Smoke

Alarms should be installed for the hearing impaired. They include a 

visual alarm and an audible alarm horn, and meet the requirements of

the Americans With Disabilities Act. These units can be interconnected

so if one unit senses smoke, all units alarm.

Smoke alarms are not to be used with detector guards

unless the

combination has been evaluated and found suitable for that purpose.
All these Smoke Alarms are designed to provide early warning of fires if

located, installed and cared for as described in the user’s manual, and if

smoke reaches the Alarm. If you are unsure which type of unit to install,

refer to NFPA (National Fire Protection Association) 72 (National Fire

Alarm Code) and NFPA 101 (Life Safety Code). National Fire Protection

Association, One Batterymarch Park, Quincy, MA 02269-9101 U.S.A.

Local building codes may also require specific units in new construction

or in different areas of the home.

SPECIAL COMPLIANCE CONSIDERATIONS

This unit alone is not a suitable substitute for complete fire 

detection systems in places housing many people—like apartment

buildings, condominiums, hotels, motels, dormitories, hospitals,

long-term health care facilities, nursing homes, day care facilities, 

or group homes of any kind—even if they were once single-family

homes. It is not a suitable substitute for complete fire detection 

systems in warehouses, industrial facilities, commercial buildings,

and special-purpose non-residential buildings which require special

fire detection and alarm systems. Depending on the building codes

in your area, this unit may be used to provide additional protection

in these facilities.
The following information applies to all four types of buildings listed

below:

In new construction, most building codes require the use of AC or

AC/DC powered Smoke Alarms only. AC, AC/DC, or DC powered 

Smoke Alarms can be used in existing construction as specified by local

building codes. Refer to NFPA 72 (National Fire Alarm Code) and NFPA

101 (Life Safety Code), local building codes, or consult your Fire

Department for detailed fire protection requirements in buildings not

defined as “households.”

1. Single-Family Residence:

Single family home, townhouse. It is recommended this unit be installed

on every level of the home, in every bedroom, and in each bedroom

hallway.

2. Multi-Family or Mixed Occupant Residence:

Apartment building, condominium. This unit is suitable for use in individual

apartments or condos, provided a primary fire detection system already

exists to meet fire detection requirements in common areas like lobbies,

hallways, or porches. Using this unit in common areas may not provide

sufficient warning to all residents or meet local fire protection ordinances/ 

regulations.

3. Institutions: 

Hospitals, day care facilities, long-term health care facilities. This unit is

suitable for use in individual patient sleeping/resident rooms, provided a

primary fire detection system already exists to meet fire detection

requirements in common areas like lobbies, hallways, or porches. 

Using this unit in common areas may not provide sufficient warning 

to all residents or meet local fire protection ordinances/regulations.

4. Hotels and Motels:

Also boarding houses and dormitories. This unit is suitable for use inside

individual sleeping/resident rooms, provided a primary fire detection sys-

tem already exists to meet fire detection requirements in common areas

like lobbies, hallways, or porches. Using this unit in common areas may

not provide sufficient warning to all residents or meet local fire protec-

tion ordinances/regulations.

GENERAL LIMITATIONS OF SMOKE/CO ALARMS

LIMITED WARRANTY

BRK Brands, Inc., ("BRK") the maker of BRK

®

brand and First Alert

®

brand products, warrants that for a period of ten years from the date of purchase, 

this product will be free from defects in material and workmanship. BRK, at its option, will repair or replace this product or any component of the product

found to be defective during the warranty period. Replacement will be made with a new or remanufactured product or component. If the product is no

longer available, replacement may be made with a similar product of equal or greater value. This is your exclusive warranty.
This warranty is valid for the original retail purchaser from the date of initial retail purchase and is not transferable. Keep the original sales receipt. 

Proof of purchase is required to obtain warranty performance. BRK dealers, service centers, or retail stores selling BRK products do not have the right to

alter, modify or any way change the terms and conditions of this warranty.
This warranty does not cover normal wear of parts or damage resulting from any of the following: negligent use or misuse of the product, use on improper

voltage or current, use contrary to the operating instructions, disassembly, repair or alteration by anyone other than BRK or an authorized service center.

Further, the warranty does not cover Acts of God, such as fire, flood, hurricanes and tornadoes or any batteries that are included with this unit.
BRK shall not be liable for any incidental or consequential damages caused by the breach of any express or implied warranty. Except to the extent 

prohibited by applicable law, any implied warranty of merchantability or fitness for a particular purpose is limited in duration to the duration of the above

warranty. Some states, provinces or jurisdictions do not allow the exclusion or limitation of incidental or consequential damages or limitations on how long an

implied warranty lasts, so the above limitations or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other

rights that vary from state to state or province to province.

How to Obtain Warranty Service
Service: 

If service is required, do not return the product to your retailer. In order to obtain warranty service, contact the Consumer Affairs Division at 

1-800-323-9005, 7:30 AM - 5:00 PM Central Standard Time, Monday through Friday. To assist us in serving you, please have the model number and 

date of purchase available when calling. 

For Warranty Service return to:

BRK Brands, Inc., 1301 Joe Battle, El Paso, TX 79936 U.S.A.

Battery:

BRK Brands, Inc. make no warranty, express or implied, written or oral, including that of merchantability or fitness for any particular purpose 

with respect to battery.

Once a minute, the alarm sounds 3 “chirps”, and

the green light flashes quickly three times.

MALFUNCTION SIGNAL.

Unit needs to be

replaced. Based on self-diagnostic tests, the unit

has detected a fault.

Units under warranty should be returned to 

manufacturer for replacement. See “Limited

Warranty” for details.

The light flashes (GREEN) and the horn sounds 

3 “chirps” every minute.

END OF LIFE SIGNAL.

CO Alarm needs to be replaced.

Immediately replace the CO Alarm.

Horn "chirps" about once per minute; 

Green 

"Power/Smoke"

LED flashes Green On

for 2 seconds/Off for 2 seconds. (Low Battery

Latch is engaged.)

Low battery warning. Battery is low or missing.

Replace the battery, avoid interrupting AC 

power.

If your Alarm does this...

It means...

You should...

Green Power/Smoke LED is OFF. Unit will not

alarm when you press the Test/Silence button.

Unit may not be receiving any power.

Check the AC power supply. Make sure the

power connector is securely attached to the

alarm. Make sure a fresh 9V battery is installed 

to power the battery back-up

*

.

Green light flashes ON, once a minute (horn is

silent).

Alarm is not receiving AC power.

Unit is operating on battery back-up.

Check the AC power supply.

TROUBLESHOOTING GUIDE

Alarm goes back into alarm after you pressed

the Test/Silence button to silence an alarm.

Smoke and/or CO levels are still potentially 

dangerous.

Refer to “If Your Smoke/CO Alarm Sounds” for

details on how to respond to an alarm. If anyone

is feeling ill, EVACUATE your home immediately

and call 911.

If you have any questions that cannot be answered by reading this manual, call Consumer Affairs: 1-800-323-9005.

*

For a list of acceptable replacement batteries, see “Regular Maintenance.”

Alarm sounds frequently even though no high 

levels of smoke or CO are revealed in an 

investigation.

The Alarm may be improperly located. Refer to

“Where to Install This Alarm.”

Relocate your alarm. If frequent alarms continue,

have home rechecked for potential problems.

You may be experiencing an intermittent smoke

or CO problem.

ELECTRICAL SHOCK HAZARD. Turn off the power to the area where the Alarm is installed BEFORE removing it from the mounting bracket or

checking any electrical connections! Failure to turn off the power first may result in serious electrical shock, injury or death.

For your records, please record:

Date Purchased: _______________________________

Where Purchased:

__________________________________________

Date Installed: ____________/____________Month/Year
Replace alarm 10 years after installation since the alarm may no

longer accurately detect carbon monoxide. Please write the date

in the space provided:

_____________/____________Month/Year

The alarm will also provide an audible End-of-Life Signal 

approximately 10 years after installation to remind you to 

replace the unit.
The End-of-Life Signal can be silenced for up to 2 days. 

Do not unplug the alarm or remove the batteries until you get

replacement.

This Smoke/CO Alarm is intended for residential use. It is not intended

for use in industrial applications where Occupational Safety and Health

Administration (OSHA) requirements for Carbon Monoxide Alarms must

be met. The Smoke Alarm portion of this device is not intended to alert

hearing impaired residents. Special purpose Smoke Alarms should be

installed for hearing impaired residents (CO Alarms are not yet available

for the hearing impaired).

Smoke/CO Alarms may not waken all individuals.

Practice the

escape plan at least twice a year, making sure that everyone is involved

– from kids to grandparents. Allow children to master fire escape 

planning and practice before holding a fire drill at night when they are

sleeping. If children or others do not readily waken to the sound of the

Smoke/CO Alarm, or if there are infants or family members with mobility

limitations, make sure that someone is assigned to assist them in fire

drill and in the event of an emergency. It is recommended that you hold

a fire drill while family members are sleeping in order to determine their

response to the sound of the Smoke/CO Alarm while sleeping and 

to determine whether they may need assistance in the event of an 

emergency.

Smoke/CO Alarms cannot work without power.

Battery operated units

cannot work if the batteries are missing, disconnected or dead, if the wrong

type of batteries are used, or if the batteries are not installed correctly. 

AC units cannot work if the AC power is cut off for any reason (open fuse

or circuit breaker, failure along a power line or at a power station, electrical

fire that burns the electrical wires, etc.). If you are concerned about the 

limitations of battery or AC power, install both types of units.

This Smoke/CO Alarm will not sense smoke or CO that does not

reach the sensors.

It will only sense smoke or CO at the sensor. Smoke

or CO may be present in other areas. Doors or other obstructions may

affect the rate at which CO or smoke reaches the sensors. If bedroom

doors are usually closed at night, we recommend you install an alarm

device (Combination CO and Smoke Alarm, or separate CO Alarms and

Smoke Alarms) in each bedroom and in the hallway between them.

This Smoke/CO Alarm may not sense smoke or CO on another 

level of the home. 

Example: This alarm device, installed on the second

floor, may not sense smoke or CO in the basement. For this reason, 

one alarm device may not give adequate early warning. Recommended

minimum protection is one alarm device in every sleeping area, every

bedroom, and on every level of your home. Some experts recommend

battery powered Smoke and CO Alarms be used in conjunction with

interconnected AC powered Smoke Alarms. For details, see “About

Smoke Alarms” for details.

This carbon monoxide alarming device is designed to detect car-

bon monoxide gas

from ANY source of combustion. It is NOT designed

to detect smoke, fire, or any other gases.

Smoke/CO Alarms may not be heard.

The alarm horn loudness 

meets or exceeds current standards of 85 dB at 3 meters (10 feet). 

However, if the Smoke/CO Alarm is installed outside the bedroom, it

may not wake up a sound sleeper or one who has recently used drugs

or has been drinking alcoholic beverages. This is especially true if the

door is closed or only partly open. Even persons who are awake may

not hear the alarm horn if the sound is blocked by distance or closed

doors. Noise from traffic, stereo, radio, television, air conditioner, or

other appliances may also prevent alert persons from hearing the alarm

horn. This Smoke/CO Alarm is not intended for people who are hearing

impaired.

The Alarm may not have time to alarm before the fire itself causes

damage, injury, or death, since smoke from some fires may not

reach the unit immediately. Examples of this include persons

smoking in bed, children playing with matches, or fires caused 

by violent explosions resulting from escaping gas.
This Smoke/CO Alarm is not a substitute for life insurance.

Though this Smoke/CO Alarm warns against increasing CO levels or the

presence of smoke, BRK Brands, Inc. does not warrant or imply in any

way that they will protect lives. Homeowners and renters must still

insure their lives.

This Smoke/CO Alarm has a limited life.

Although this Smoke/CO

Alarm and all of its parts have passed many stringent tests and are

designed to be as reliable as possible, any of these parts could fail at

any time. Therefore, you must test this device weekly. The unit should 

be replaced immediately if it is not operating properly.

This Smoke/CO Alarm is not foolproof.

Like all other electronic

devices, this Smoke/CO Alarm has limitations. It can only detect smoke

or CO that reaches the sensors. It may not give early warning of the

source of smoke or CO is in a remote part of the home, away from the

alarm device.

LATCHING FEATURES

Alarm Latch

is activated after an Alarm is exposed to alarm levels of

smoke or carbon monoxide. After smoke or CO levels drop below alarm

levels, the 

“Smoke/Power”

or 

“CO”

Red LED will begin to flash On 2

seconds/Off 2 seconds. It will continue to flash or “latch” until you clear 

it by testing the alarm.

This feature helps emergency responders, investigators, or service 

technicians identify which unit(s) in your home were exposed to alarm

levels of smoke or carbon monoxide. This can help investigators 

pinpoint the source of smoke or CO.

Interconnected Alarms.

Latching Alarm Indicator shows which Alarm(s)

in the series were exposed to alarm levels of smoke or carbon monoxide.

The Latching Alarm Indicator stays ON until you clear it, so it can alert

you to an alarm that occurred while you were away from home, even

though smoke or CO present in the air has dropped below alarm levels.

Low Battery Latch

is activated when the Alarm is in the "low battery

condition". When this occurs, the 

Smoke/Power

LED flashes Green On

for 2 seconds/Off for 2 seconds. This feature is designed to help you

identify which Alarm needs to have the battery replaced. Although, the

Alarm will sound the low battery chirp approximately once every minute,

sometimes during the initial stages of "low battery", the Alarm will chirp

in greater intervals than one minute, sometimes up to several hours, until

the battery reaches a steady low battery level. This innovative feature

eliminates the frustration of waiting for and/or identifying which unit is

chirping.

Latching Features Note: Without AC Power and running on battery

only, Low Battery Latch or Alarm Latch are only engaged for about

15 minutes to conserve power. Low Battery Latch and Alarm Latch

do not operate with a missing battery and no AC Power.

IF YOUR SMOKE/CO ALARM SOUNDS, Continued

WHAT YOU NEED TO KNOW ABOUT CO

WHAT IS CO?

CO is an invisible, odorless, tasteless gas produced when fossil fuels 

do not burn completely, or are exposed to heat (usually fire). Electrical

appliances typically do not produce CO.

These fuels include:

Wood, coal, charcoal, oil, natural gas, gasoline,

kerosene, and propane.

Common appliances are often sources of CO. If they are not properly

maintained, are improperly ventilated, or malfunction, CO levels can rise

quickly. CO is a real danger now that homes are more energy efficient.

“Air-tight” homes with added insulation, sealed windows, and other

weatherproofing can “trap” CO inside.

SYMPTOMS OF CO POISONING

The following symptoms may be related to CARBON MONOXIDE 

POISONING and should be discussed with ALL members of the 

household:

Mild Exposure:

Headaches, running nose, sore eyes, often described as

“flu”-like symptoms.

Medium Exposure:

Dizziness, drowsiness, vomiting.

Extreme Exposure:

Unconsciousness, brain damage, death.

Many cases of reported CARBON MONOXIDE POISONING indicate that

while victims are aware they are not well, they become so disoriented

they are unable to save themselves by either exiting the building or 

calling for assistance. 

This CO Alarm measures exposure to CO over time. It alarms if CO 

levels are extremely high in a short period of time, or if CO levels reach

a certain minimum over a long period of time. The CO Alarm generally

sounds an alarm before the onset of symptoms in average, healthy

adults.

Why is this important? Because you need to be warned of a potential 

CO problem while you can still react in time. In many reported cases of

CO exposure, victims may be aware that they are not feeling well, but

become disoriented and can no longer react well enough to exit the

building or get help. Also, young children and pets may be the first 

affected. The average healthy adult might not feel any symptoms when

the CO Alarm sounds. However, people with cardiac or respiratory 

problems, infants, unborn babies, pregnant mothers, or elderly people

can be more quickly and severely affected by CO. If you experience 

even mild symptoms of CO poisoning, consult your doctor immediately!
This device is designed to protect individuals from the acute effects of

carbon monoxide exposure. It will not fully safeguard individuals with

specific medical conditions. If in doubt consult a medical practitioner.

FINDING THE SOURCE OF CO AFTER AN ALARM

Carbon monoxide is an odorless, invisible gas, which often makes it 

difficult to locate the source of CO after an alarm. These are a few of

the factors that can make it difficult to locate sources of CO:

      •   House well ventilated before the investigator arrives.

      •   Problem caused by “backdrafting.”

      •   Transient CO problem caused by special circumstances.

Because CO may dissipate by the time an investigator arrives, it may 

be difficult to locate the source of CO.

BRK Brands, Inc. shall not be

obligated to pay for any carbon monoxide investigation or service

call.

REGULATORY INFORMATION FOR SMOKE/CO

ALARMS

REGULATORY INFORMATION FOR CO ALARMS
CANADIAN STANDARDS ASSOCIATION

What Levels of CO Cause an Alarm?

CSA 6.19 requires residential CO Alarms to sound when exposed to 

levels of CO and exposure times as described below. They are measured

in parts per million (ppm) of CO over time (in minutes).

CSA 6.19 Required Alarm Points*:

      •   If the alarm is exposed to 400 ppm of CO, IT MUST ALARM

BETWEEN 4 and 15 MINUTES.

      •   If the alarm is exposed to 150 ppm of CO, IT MUST ALARM

BETWEEN 10 and 50 MINUTES.

      •   If the alarm is exposed to 70 ppm if CO, IT MUST ALARM

BETWEEN 60 and 240 MINUTES.

*

Approximately 10% COHb exposure at levels of 10% to 95% Relative

Humidity (RH).

The unit is designed not to alarm when exposed to a constant level 

of 30 ppm for 30 days.

CO Alarms are designed to alarm before there is an immediate life threat.

Since you cannot see or smell CO, never assume it’s not present.

•     An exposure to 100 ppm of CO for 20 minutes may not affect 

average, healthy adults, but after 4 hours the same level may 

cause headaches. 

•     An exposure to 400 ppm of CO may cause headaches in average,

healthy adults after 35 minutes, but can cause death after 2 hours.

Standards:

CSA 6.19

Audible Alarm:

85 dB minimum at 3 meters (10 feet).

RECOMMENDED LOCATIONS FOR SMOKE ALARMS
Installing Smoke Alarms in Single-Family Residences

The National Fire Protection Association (NFPA), recommends one

Smoke Alarm on every floor, in every sleeping area, and in every bed-

room. In new construction, the Smoke Alarms must be AC powered and

interconnected. See “Agency Placement Recommendations” for details.

For additional coverage, it is recommended that you install a Smoke

Alarm in all rooms, halls, storage areas, finished attics, and basements,

where temperatures normally remain between 4

o

C (40

o

F) and 38

o

(100

o

F). Make sure no door or other obstruction could keep smoke from

reaching the Smoke Alarms.

More specifically, install Smoke Alarms:

•     On every level of your home, including finished attics and basements.

•     Inside every bedroom, especially if people sleep with the door partly

or completely closed.

•     In the hall near every sleeping area. If your home has multiple 

sleeping areas, install a unit in each. If a hall is more than 12 meters

(40 feet long), install a unit at each end.

•     At the top of the first-to-second floor stairway, and at the bottom of

the basement stairway.

Specific requirements for Smoke Alarm installation vary from state to

state and from region to region. Check with your local Fire Department

for current requirements in your area. 

It is recommended AC or AC/DC

units be interconnected for added protection.

AGENCY PLACEMENT RECOMMENDATIONS

NFPA 72 (National Fire Code) Chapter 11

“For your information, the National Fire Protection Association's

Standard 72, reads as follows:”

“11.5.1 One- and Two-Family Dwelling Units.”

“11.5.1.1 Smoke Detection.

Where required by applicable laws, codes, 

or standards for the specified occupancy, approved single- and multiple-

station Smoke Alarms shall be installed as follows: (1) In all sleeping

rooms. Exception: Smoke Alarms shall not be required in sleeping rooms

in existing one- and two-family dwelling units. (2) Outside of each 

separate sleeping area, in immediate vicinity of the sleeping rooms. 

(3) On each level of the dwelling unit, including basements. Exception:

In existing one- and two family dwelling units, approved Smoke Alarms

powered by batteries are permitted.”

“A.11.8.3 Are More Smoke Alarms Desirable? 

The required number of Smoke Alarms might not provide reliable early

warning protection for those areas separated by a door from the areas

protected by the required Smoke Alarms. For this reason, it is recom-

mended that the householder consider the use of additional Smoke

Alarms for those areas for increased protection. The additional areas

include the basement, bedrooms, dining room, furnace room, utility

room, and hallways not protected by the required Smoke Alarms. The

installation of Smoke Alarms in kitchens, attics (finished or unfinished), or

garages is not normally recommended, as these locations occasionally

experience conditions that can result in improper operation.”

M08-0121-014_M08-0121-006.E_SC9120A_BA_V5.0  15-10-16  11:24 AM  Page 2

Reviews: