![BRK electronic C0250B Quick Manual Download Page 4](http://html1.mh-extra.com/html/brk-electronic/c0250b/c0250b_quick-manual_2815209004.webp)
CAT.
CO250B/CO250LB
ARCHITECTURAL AND ENGINEERING SPEC
TECHNICAL SPECS
SHIPPING SPECS
INSTALLATION OF ALARM
The carbon monoxide alarm shall be a BRK Model CO250 and shall provide at a
minimum the following features and functions:
1. An electrochemical CO sensor.
2. The unit shall be capable of self restoring.
3. The unit shall have an “End of Life” signal after 10 years (120 months) of operation.
This signal should be capable of temporarily being silenced for up to 2 days. After
about 2 days, the signal will resume. After about 2-3 weeks the signal cannot be
silenced.
4. Powered by a supervised 9V battery and a solid state piezo horn rated at 85dB at
10 ft.
5. A visual LED power-on indicator to confirm unit is receiving power or is in alarm.
6. A test/silence button to check all alarm functions and to silence any nuisance
alarms. In addition, the unit shall have a low battery silence feature to quiet
the low battery chirp for up to eight hours.
7. A tamper resistant locking pin should be provided that locks alarm cover to prevent
removal of battery.
8. The CO sensor is adjusted not to detect CO levels below 30 PPM and will not
alarm when exposed to constant levels of 30 PPM for 30 days. It will alarm at the
following levels: 400 PPM CO between 4 and 15 minutes, 150 PPM CO between 10
and 50 minutes and 70 PPM CO between 60 and 240 minutes.
9. The unit shall be capable of operating between 40°F (4°C) and 100°F (38°C) and
relative humidity between 10% and 95%.
10. The unit shall contain mounting hardware and shall be listed for wall or ceiling
mounting.
11. The unit shall at a minimum meet the requirements of UL2034, NFPA 720, NFPA
101, ICC.
Alarm Dimensions: 1.6”H x 4.25”Dia
Weight:
5.1 oz
Operating Voltage:
9V Battery Powered
Temperature Range: 40°F (4°C) to 100°F (38°C)
Humidity Range:
10% to 95% relative humidity (RH)
Audio Alarm:
85dB at 10 feet
Test/Silence:
Electronically simulates carbon monoxide condition,
causing the unit to alarm. Press and hold test/silence
button
Alarm Reset:
Automatic when CO clears
CO Sensor:
Electrochemical
Indicator Lights/Sounds:
DC Power:
Intermittent Red LED
Local Alarm:
Audio alarm and rapidly flashing Red LED
End of Life:
Replace alarm 120 months after installation
Listing:
Listed to UL2034 Standard
Individual Carton Dimensions
4.38 ”L x 1.75”W x 4.38”H
Weight
0.39 lbs.
Cube
0.02 ft3
UPC
0 29054 00392 8: CO250B
0 29054 00725 4: CO250LB
Master Carton Dimensions
12.63”L x 6.13”W x 5.19”H
Master Pack
6
Weight
3.2 lbs.
Cube:
0.15 ft3
I2of5:
600 29054 00392 0: CO250B
600 29054 00725 6: CO250LB
Pallet Information
Cases per Layer
36
Number of Layers:
9
Cases per Pallet:
324
Units per Pallet:
1,944
Cube:
55.0 ft3
Weight:
1,107 lbs.
©2015 BRK Brands, Inc. a Jarden Corporation
Company (NYSE: JAH)
3901 Liberty Street Road
Aurora, IL 60504-8122
All rights reserved
First Alert is a registered trademark of the First Alert Trust
BRK is a registered trademark of BRK Brands, Inc.
CM3171
brkelectronics.com
Installation of this CO alarm must conform to NFPA 720. Always check your local building
codes. Follow all instructions for placement as outlined in the user’s manual in sections
titled “Recommended Locations for CO Alarms” and “Locations to Avoid for CO Alarms”.
THE PARTS OF THIS CO ALARM
1. “Open Here”
2. “No Battery” tab
3. Test/Silence button tab
4. CO alarm base
5. Standard screw mounting slots
6. Install 9V battery here
7. Locking pin slot
8. Locking pin: Remove and
insert in 7
MOUNTING
BRACKET
TOP VIEW
SIDE VIEW
CO
1
2
3
4
5
7
6
8
7