CAT.
7010BSL
ARCHITECTURAL AND ENGINEERING SPEC
TECHNICAL SPECS
SHIPPING SPECS
INSTALLATION OF ALARM
UL1971 Signaling Devices Light Dispersion Chart
TOP VIEW
MOUNTING
BRACKET
SIDE VIEW
The integrated strobe light & smoke alarm shall be a BRK Model 7010BSL and shall
provide at a minimum the following features and functions:
1. A photoelectric smoke sensing chamber.
2. A 177 candela Xenon strobe light. The Smart Strobe shall have separate fl ash
patterns to distinguish between smoke/heat and carbon monoxide dangers.
3. Fully screened sensing chamber to resist entry of small insects thereby reducing
the probability of unwanted alarms.
4. Powered by 120V AC, 60Hz and have a monitored two AAA battery backup for alarm
and a solid state piezo horn rated at 85dB at 10 ft and be capable of self restoring.
5. A visual green LED power-on indicator to confi rm unit is receiving power or is in
alarm.
6. A full function test button should check all alarm functions by simulating a smoke
condition, causing the unit to alarm.
7. Two Latching features: Alarm Latch to easily identify initiating alarm after alarm
condition has subsided. Low battery latch: to visually identify which unit is in
low battery condition. Two Silence Features: Alarm Silence to temporarily silence
nuisance alarms. Low Battery Silence to silence low battery chirp for up to 8 hours.
8. Two Locking features - tamper resistant locking pins that lock battery drawer and/
or alarm to mounting bracket.
9. The unit shall be capable of operating between 40°F (4°C) and 100°F (38°C) and
relative humidity between 10% and 90%.
10. The unit shall have a plug in connector and be capable of interconnection of up to
18 alarms, 12 of which can be smoke alarms.
11. The unit shall at a minimum meet the requirements of UL217, UL1971, ADA, ANSI
117.1, CSFM, NFPA 72, NFPA 101 and the ICC.
Alarm Dimensions:
5.1” dia x 4.0”H
Weight:
10.9 oz
Operating Voltage:
120V AC 60Hz w/ two AAA battery backup for alarm
Voltage Range: 108V AC to 132V AC
Operating Current:
0.05/0.60 amps (standby/alarm)
Temperature Range: 40°F (4°C) to 100°F (38°C)
Humidity Range:
10% to 90% relative humidity (RH)
Audio Alarm:
85dB at 10 feet
Test/Silence:
Electronically simulates smoke condition, causing the unit
to alarm. Press and hold test/silence button
Alarm Reset:
Automatic when smoke clears
Interconnections:
Up to 18 units of First Alert or BRK Smoke, CO and Heat
Alarms. Maximum of 12 smoke alarms. See user’s manual
for
details.
Smoke Sensor:
Photoelectric
Strobe Light:
177 candela Xenon strobe
Flash Rate:
1 Hz.
Smoke Alarm:
Constant approx. 1 fl ash per second.
CO Alarm:
Intermittent approx. 1 fl ash per second for four
fl ashes, then 5 seconds off. Pattern is repeated.
Indicator Lights/Sounds:
AC Power:
Constant Green LED
DC Power:
Intermittent Red LED
Local Alarm:
Red LED fl ashes rapidly, steady fl ashing strobe
Remote Alarm:
Red LED out.
Listing:
Listed to UL217 & UL1971 Standards
90 90
Angle
(In Degrees)
Percent
Light Intensity
0
5-25
30-45
50
55
60
65
70
75
80
85
90
100
90
75
55
45
40
35
35
30
30
25
25
45 45
0
90
90
45
45
0
WALL
LIGHT
LIGHT
CEILING
FIGURE 1: Light Output
for Ceiling Mount
FIGURE 2: Light Output
for Wall Mount
Individual Carton Dimensions
5.25”L x 4.13”W x 5.44”H
Weight
0.97 lbs.
Cube
0.07 ft3
UPC
0 29054 12104 2
Master Carton Dimensions
12.63”L x 5.81”W x 5.94”H
Master Pack
3
Weight
3.24 lbs.
Cube:
0.25 ft3
I2of5:
300 29054 12104 3
Pallet Information
Cases per Layer
24
Number of Layers:
7
Cases per Pallet:
168
Units per Pallet:
504
Cube:
47.5 ft3
Weight:
609 lbs.
©2011 BRK Brands, Inc. a Jarden Corporation
Company (NYSE: JAH)
3901 Liberty Street Road
Aurora, IL 60504-8122
All rights reserved
First Alert is a registered trademark of the First Alert Trust
BRK is a registered trademark of BRK Brands, Inc.
CM3032
brkelectronics.com
Installation of this smoke alarm must conform to all local electrical
codes and Article 760 of the National Electrical Code (NFPA 70)
and NFPA 72. Interconnected units must meet the following
requirements: Total length of wire interconnecting units should
be less than 1000 feet, be #18 gauge or larger and be rated at
least 300V. It is recommended that all units be on the same fuse
or circuit breaker. If local codes do not permit, be sure the neutral
wire is common to both phases.
THE PARTS OF THIS SMOKE ALARM
1. Mounting bracket
2. Mounting Slots
3. Locking Pins
4. Hot (Black) AC Wire
5. Neutral (White) AC Wire
6. Interconnect (Orange) Wire
7. Pull-out Battery Drawer
8. Quick-Connect Plug
A. Unswitched 120VAC 60 Hz source
B. To additional units; Maximum = 18 total
(Maximum 12 Smoke Alarms)
1a. Smoke Alarm
5. Electrical Box
1b. Smoke/Strobe Combo 6. Neutral Wire (White)
2. Ceiling or Wall
7. Interconnect Wire (Orange)
3. Power Connector
8. Hot Wire (Black)
4. Wire Nut
678
4 3
1b
5
2
A
B
}
}
4 3
1a
5
2
8
1
7
6
5
4
3
2
5.0"
4.0"