RPSPP   

 

 

 

 

 

REV 2:  September 2010 

 

RECHARGING PROCEDURE FOR BRITANNIA RANGE STORED PRESSURE DRY POWDER MODELS 

 

MODEL NO'S:  BAS2, BAS4, BAS6, BAS9, BMS9 

 

THESE RECHARGE PROCEDURES SHOULD BE USED IF COMPLETE OR PARTIAL USE OF THE 

EXTINGUISHER IS SUSPECTED

 

 
1.

 

Check for signs of damage or corrosion to extinguisher.  If found, do not continue recharge 
procedure, mark extinguisher 'condemned' and inform user. Ensure instruction label is 
legible, rectify if necessary. 

 
2.

 

Ensure pressure is relieved by inverting extinguisher and squeezing the levers together 
slowly (whilst pointing nozzle down and away). 

 
3.

 

Loosen headcap, using nutring spanner [Part Ref: HCS].  (Do not use hammer or other blunt 
implement).  Remove headcap slowly, allowing residual pressure to escape through vent 
holes. 

 
4.

 

Empty residual powder from extinguisher body. 

 
5.

 

Inspect the extinguisher inside, checking for caked powder or corrosion, indicating moisture 
inside the cylinder, rectify or replace extinguisher if found. 

 
6.

 

Recharge the extinguisher body with new dry powder, ensuring correct quantity and type. 

Never mix different types of powder as pressure and moisture may develop as a result of 
a chemical reaction.

 

 
7.

 

Remove syphon tube, spindle holder/plug, spring and spindle. Thoroughly clean any residual 
powder from both chambers using a soft brush or valve tool.  Remove 'O' rings from spindle, 
clean 'O' ring grooves and lubricate lightly using silicon gel.  Fit new 'O' rings ensuring they 
are centralised. 

 
8.

 

Refit spindle, spring and spindle housing to headcap.  Refit syphon tube.  Fit new headcap 
'O' ring. 

 
9.

 

Clean cylinder neck threads and 'O' ring seat.  Refit headcap, tighten using headcap spanner.   
Refit safety pin, seal and service indicator (in accordance with service colour code).         

 
10.

 

Pressurise through schrader valve connection to 12 bar (@+20ºc) using compressed dry air 
or Nitrogen. 

 
11.

 

Check for leakage.  Record recharging details, including new weight on service label. 