background image

Page 

3

 of 

5

 

 

SPCOL   

 

 

 

 

 

REV 3: September 2010 

 

SERVICING PROCEDURE FOR BRITANNIA FIRE EXTINGUISHERS 

CARTRIDGE OPERATED LIQUID MODELS 

 

MODEL NO'S: BW6, BW9, BT6, BT9, BAF9, BAQ6, BAQ9, BTU3, BTU6

 

 
1.

 

Remove extinguisher from hanging bracket and check security of the bracket, rectify if 
necessary.  Check exterior of extinguisher for corrosion or damage, if found withdraw from 
service. 

 
2.

 

Ensure safety pin is in position and the extinguisher has not been completely or partially 
discharged. If the extinguisher has been completely or partially discharged, discontinue 
servicing procedure and commence recharge procedure (ref. RPCOL). 

 
3.

 

Ensure instruction label is legible, rectify as necessary.  Check for damage/corrosion to 
extinguisher body.   If damage/corrosion is found, mark the extinguisher as condemned 
and/or remove from service. 

 

4.

 

Weigh extinguisher and compare mass to that recorded when the extinguisher was 
commissioned or last discharge tested. Recharge the extinguisher if there is a difference of 
more than 10% of the content weight. 

 
5.

 

Ensure your body/head is not directly over extinguisher. Remove the headcap using the 
nutring spanner [Part Ref: HCS] (warning: should pressure issue from vents, allow pressure 
to escape before complete removal of headcap).   Do not use blunt instrument, i.e. screw 
driver etc. 

 
6.

 

Check liquid level ensuring level is below the hanging bracket.  Add or remove liquid to 
correct level if necessary. 

 
7.

 

Inspect the interior of the extinguisher for evidence of lifting or cracking of the polythene 
lining, or corrosion.  If found, mark as condemned and remove from service. 

 
8.

 

Unscrew CO

2

 Cartridge from headcap, clean and check for damage lifting of plastic coating, 

corrosion and age of cartridge (must be changed if older than 10 years from date of 
manufacture), replace if necessary with new cartridge from manufacturer. 

 
9.

 

Checkweigh cartridge against marked weight.  Replace if loss of contents is in excess of 10%. 

 
10.

 

Wipe headcap valve clean, check for damage.  Remove safety pin and squeeze levers 
ensuring free movement of the firing pin/spindle. Check for blockages and valve shut off by 
blowing through hose whilst opening and closing valve.  Ensure nutring vents are clear. 

 
 
 
 
 

Summary of Contents for BW6

Page 1: ...Page 1 of 5 BRITANNIA RANGE EXTINGUISHER SERVICING MAINTENANCE INSTRUCTIONS Cartridge Operated Water Based extinguishers ...

Page 2: ...e security and suitability of the hanging bracket and that the extinguisher is of the right type for the prevalent risk If the extinguisher is to be sited in a hazardous corrosive environment i e marine use the inspection periods should be more frequent The effects of the environment should be considered with particular reference to corrosion and legibility of marking instructions If there is corr...

Page 3: ...ore than 10 of the content weight 5 Ensure your body head is not directly over extinguisher Remove the headcap using the nutring spanner Part Ref HCS warning should pressure issue from vents allow pressure to escape before complete removal of headcap Do not use blunt instrument i e screw driver etc 6 Check liquid level ensuring level is below the hanging bracket Add or remove liquid to correct lev...

Page 4: ...and hose clips for wear cuts or abrasions Replace if necessary 13 Refit safety pin service indicator and seal in accordance with service colour code Refit original or new CO2 cartridge 14 Clean extinguisher neck threads and refit headcap using nutring spanner Part Ref HCS do not use blunt instrument 15 Fill in details of service on service label including extinguisher weight using indelible pen Cl...

Page 5: ...t holes 4 Empty residual liquid from extinguisher and rinse with clean water 5 Inspect the internal lining for signs of detachment cracks or corrosion If found remove from service and replace 6 Refill the cylinder to the correct level making allowance for any additives if applicable Then add foam concentrate additives ensuring manufacturers specifications are met 7 Remove CO2 cartridge and discard...