background image

 

SPBP   

 

 

 

 

  

 

 

 

 

SERVICING PROCEDURES FOR BLAZEX RANGE 

STORED PRESSURE POWDER MODELS 

 
 

MODEL NO'S: XAS6, XAS9 

 
 
1.  Remove extinguisher from hanging bracket and check security of the bracket, 

rectify if necessary.  Check exterior of extinguisher for corrosion or damage, if 
found

, mark the maintenance label as “CONDEMNED” and withdraw from 

service. 

 
2.  Ensure safety pin is in position and the extinguisher has not been completely 

or partially discharged.  If the extinguisher has been completely or partially 
discharged, discontinue servicing procedure and commence recharge 
procedure (Ref. RPBP). 

 
3.  Ensure instruction label is legible, rectify as necessary. Check for 

damage/corrosion to extinguisher body.  If significant damage/corrosion is 
found, mark the extinguisher as condemned and/or remove from service. 

 
4.  Checkweigh the extinguisher against the gross weight recorded on service 

label. If underweight by more than 10% of contents, the extinguisher should 
be removed from service and recharged. Invert extinguisher to loosen 
powder. 

 
5.  Check safety pin for free removal.  Replace pin and fit new seal (in 

accordance with service colour code). 

 
6.  Check pressure gauge is reading 12 bar (@+20ºc) in the green zone. Check 

that gauge is operational by using magnetic gauge test kit; ensure that after 
testing the needle returns to the original mark. Fit new gauge sticker.  If a 
deviation of more than 10% is recorded, remove extinguisher from service 
and recharge. 

 
7.  Remove discharge hose and blow through.  Check discharge hose, nozzle 

and clips for wear, cuts or abrasion. Replace as necessary. 

Fit new „O‟ring to 

hose assembly and refit hose.                                       

 
8.  Fill in details of service, including extinguisher weight, on service label using 

indelible pen.  Clean extinguisher and return to service. 

Reviews: