2 Installation
2.1 Mounting of the product
The installation of this product is reserved exclusively to qualified personnel. Make sure that the power system in
the installation room is disconnected before the electrical assembling operations.
The product must not be installed close to curtains or cloths, because these could affect its functioning. Before
the mounting operations of the product, read carefully and strictly follow the instruction manual and make sure
to have all the necessary equipment for the installation.
For the proper functioning of the system, it is important that the ISSO guidelines regarding to air overflow must
be considered. These are as follows:
▪
The net cross-section of the fresh air supply must be at least 0.0012 m² per dm³/s of the required air volume
flow, based on an average air speed of 0.83 m / s in the opening.
▪
The air overflow is often done by a gap under a door. Also special airflow control devices are used, for example
in the door or wall. These facilities should never be blocked.
Pre-disposition
Room
Corridor/
Central hall
Note the gap height used under the door.
1 Grill
2 Fan unit
F = W - 25mm
W= Thickness of the wall
Room
Corridor
Indoor Mixfan 616190-C