Other General Location Guidelines

  •  Place the standby generator in a prepared location that 

is flat and has provisions for water drainage.

  •  Install the standby generator in a location where sump 

pump discharge, rain gutter down spouts, roof run-off, 

landscape irrigation, or water sprinklers will not flood 

the unit or spray the enclosure and enter any air inlet or 

outlet openings.

  •  Install the standby generator where it will not affect or 

obstruct any services (including covered, concealed 

and underground), such as telephone, electric, fuel 

(natural gas / LPG vapor), irrigation, air conditioning, 

cable, septic, sewer, well and so forth.

  •  Install the standby generator where leaves, grass, 

snow, etc., will not obstruct air inlet and outlet 

openings. If prevailing winds will cause blowing or 

drifting, you may need to construct a windbreak to 

protect the unit.

Concrete Slab

At the appropriate location, construct a concrete slab:
  •  28 day compression strength of 3000 psi (200 MPa)
  •  Minimum 5” (13 cm) thick
  •  Minimum 6” (15 cm) wider than enclosure on all sides 

(shown as D in figure)

  •  Strengthen slab with No. 6 reinforcing bars  

(on 12” (30.5 cm) centers) or 8 ga. steel wire fabric  

(6” (15 cm) centers).

Attach unit to slab at four corner locations (

A

) with minimum 

5/16”(8 mm) diameter masonry anchor bolts long enough to 

secure the unit.
The fuel inlet location (

B

), the wire entry location (

C

), the 

concrete slab (

D

), and the exhaust outlet (

E

) are shown for 

reference.

E

A

C

B

D

42” (106.68 cm) 

Concrete Slab (Ref)

30” (76.20 cm) 

Base

27.73” (70.43 cm) 

Anchor Hole

6” (15.24 cm) 

Min. Overhang All 

Sides

7.4”  

(18.80 cm)

2X 73.43” (186.51 cm)

32.3” (82.04 cm) 

Roof Overhang

18.9”  

(48.00 cm)

70”  

(177.80 cm) 

Base

68”  

(172.72 cm) 

Anchor Hole

71”  

(180.34 cm)  

Roof  

Overhang

82”  

(208.28 cm)  

Concrete  

Slab (Ref)

Summary of Contents for Standby Generator Systems

Page 1: ...ual Liquid Cooled Generator System This generator is rated in accordance with UL Underwriters Laboratories 2200 stationary engine generator assemblies and CSA Canadian Standards Association standard C...

Page 2: ...ce This generator system requires professional installation before use The installer should follow the instructions completely Where to Find Us You never have to look far to find support and service f...

Page 3: ...andby Generator to REDUCE THE RISK OF FIRE 14 Other General Location Guidelines 16 Concrete Slab 16 Access Ports 18 The Gaseous Fuel System 20 Fuel Consumption 21 Fuel Pressure 21 Power Loss 21 Fuel P...

Page 4: ...ing Parts Electrical Shock Explosion WARNING The engine exhaust from this product contains chemicals known to the State of California to cause cancer birth defects or other reproductive harm WARNING C...

Page 5: ...ce the fuel system lines must be properly purged and leak tested After the generator is installed you should inspect the fuel system periodically NO leakage is permitted DO NOT operate engine if smell...

Page 6: ...running at governed speed DO NOT modify generator in any way NOTICE Improper treatment of generator could damage it and shorten its life Use generator only for intended uses If you have questions abo...

Page 7: ...ons must strictly comply with all applicable codes industry standards and regulations Owner Responsibilities Read and follow the instructions given in the operator s manual Follow a regular schedule i...

Page 8: ...ge If loss or damage is noted after delivery separate the damaged materials and contact the carrier for claim procedures Missing or damaged parts are not warranted Shipment Contents The standby genera...

Page 9: ...control panel to the transfer switch is installed in a separate conduit from high voltage wires unless the insulation rating on all wiring is rated for 600V See Transfer Switch Communication Dipswitch...

Page 10: ...N o t f o r R e p r o d u c t i o n 10 BRIGGSandSTRATTON COM Page Intentionally Left Blank...

Page 11: ...ld result in death serious injury headache fatigue dizziness vomiting confusion seizures nausea or fainting Operate this product ONLY outdoors in an area that will not accumulate deadly exhaust gas Ke...

Page 12: ...to a potentially occupied building or structure By law it is required in many states to have a Carbon Monoxide CO detector in operating condition in homes and other structures occupied by people Carbo...

Page 13: ...oors ventilation intakes soffit vents crawl spaces open garage doors or other openings where exhaust gas could accumulate and enter inside or be drawn into a potentially occupied building or structure...

Page 14: ...ad clearance from any structure overhang or trees DO NOT place weatherproof enclosure under a deck or other type of structure that may confine airflow USE ONLY flexible fuel line provided Connect prov...

Page 15: ...tallations with Structure Without a Fire Rating NOTICE The figures below show the minimum installation distances allowed to structures and items listed in legend Standby weatherproof enclosure must ha...

Page 16: ...enings If prevailing winds will cause blowing or drifting you may need to construct a windbreak to protect the unit Concrete Slab At the appropriate location construct a concrete slab 28 day compressi...

Page 17: ...Use a spreader bar to ensure that the chains straps or cables DO NOT touch the generator s roof Hooks may be used in the lifting holes in place of the pipe in accordance with OSHA or local lifting re...

Page 18: ...fuel selector and engine starter E Control Panel Cover field wiring and control wires Each generator is shipped with a set of identical keys These keys fit in the lock on the front and rear removable...

Page 19: ...2 Secure the panel with two bolts To remove front panel 1 Remove the two bolts H that secure the panel to the unit 2 Lift panel to remove from unit To secure front panel 1 Place panel in unit 2 Secur...

Page 20: ...s known to occur piping should be protected against freezing The termination of hard piping should include a sediment trap E where condensate is not likely to freeze A minimum of one accessible approv...

Page 21: ...ing Maximum pressure with engine OFF at No Load is 13 85 in W C Power Loss Air density is less at high altitudes resulting in less available engine power Specifically engine power will decrease 3 for...

Page 22: ...the open position 3 Press the control board OFF button 4 Remove 15 Amp fuse from control panel 5 Remove the rear panel 6 Locate the fuel selector collar on bottom of fuel regulator A 7 Carefully push...

Page 23: ...and Line 2 Power connection to transfer switch G Neutral and Ground Connection Connect to transfer switch neutral and ground System Connectors Compare this illustration with your generator to familia...

Page 24: ...wn schematically and as wiring diagram A complete schematic and wiring diagram can be found later in this manual Neutral is not bonded to ground at generator NOTICE Prior to making connections verify...

Page 25: ...d terminals installed per terminal supplier s instructions and comply with national electrical codes and local requirements Utility Circuit Connection 240V Utility leads must be routed in conduit The...

Page 26: ...ity outage OFF Turns off running generator prevents unit from starting and resets any detected faults OFF must be pressed and held for more than 5 seconds in order to reset service codes MANUAL Used t...

Page 27: ...THE GENERATOR OFF TURNS OFF RUNNING GENERATOR PREVENTS UNIT FROM STARTING AND RESETS ANY DETECTED FAULTS AUTOMATIC MODE NORMAL OPERATING POSITION PRESS AND HOLD BUTTON TO PLACE UNIT INTO AUTOMATIC MO...

Page 28: ...ate or change these settings follow the steps below IF DURING PROGRAMMING NO BUTTONS ARE PRESSED FOR 30 SECONDS THE CONTROL PANEL WILL AUTOMATICALLY EXIT THE PROGRAM MODE SET DATE SET DATE If set to O...

Page 29: ...button The following will scroll across the digital display and then move to the next item Run time Date Time Exercise Cycle date and start time The user can press the LEFT ARROW or RIGHT ARROW at an...

Page 30: ...d region where the generator is being operated Confirm all settings before operating the generator for the first time For advanced menu items press and hold the left arrow right arrow and escape key f...

Page 31: ...e specifications shown in this chart Battery Specifications BCI Model 26R Volts 12 Volt DC Amps MIN 525 CCA cold cranking amps Type VRLA Valve Regulated Lead Acid Terminal Hardware Post Dimensions MAX...

Page 32: ...rged This may cause the engine to run roughly for a few minutes 6 Listen for unusual noises vibration or other indications of abnormal operation Check for oil leaks while engine runs 7 Let engine warm...

Page 33: ...generator will only enter the exercise cycle if the unit is in the AUTO mode and this exact procedure is followed To set the exercise timer NOTICE The generator is set with a default exercise cycle se...

Page 34: ...N o t f o r R e p r o d u c t i o n 34 BRIGGSandSTRATTON COM Schematic Diagram...

Page 35: ...N o t f o r R e p r o d u c t i o n 35...

Page 36: ...N o t f o r R e p r o d u c t i o n 36 BRIGGSandSTRATTON COM Wiring Diagram...

Page 37: ...N o t f o r R e p r o d u c t i o n 37...

Page 38: ...N o t f o r R e p r o d u c t i o n 38 BRIGGSandSTRATTON COM NOTES...

Page 39: ...N o t f o r R e p r o d u c t i o n 39 NOTES...

Page 40: ...N o t f o r R e p r o d u c t i o n Page Intentionally left Blank...

Reviews: