Page | 15
transferred to the genset. If the Mains voltage returns to normal, the controller will sense this and return
the load back to the Mains, further it will stop the genset after a cool down period.
Figure 6: SMD for AMF mode
Engine
Cooling
Down in LIM
Mains ON = 1
or Electric trip
Mains = 0 and
No Warning/No Electric Trip/No Shutdown
Engine Off
Engine On
Engine Start
Emergency shutdown input = 1
Or Genset shutdown action = 1
Time >= [Time of warm up + Time of load
transfer] and Mains ON = 0 and Remote
start = 1