21

4. Replace spark plug if electrodes are pitted, burned or

porcelain is cracked. Use the recommended
replacement spark plug. See 

Specifications

.

5. Install spark plug and tighten firmly.

Service Spark Arrester

The engine exhaust muffler has a spark arrester screen.
Inspect and clean the screen every 100 hours of operation or
once each year, whichever comes first.

If you use your generator on any forest-covered, brush-
covered, or grass-covered unimproved land, it must have a
spark arrester. The spark arrester must be maintained in
good condition by the owner/operator.

1. To remove muffler heat shield (

A

) from muffler (

B

),

remove four screws that connect guard to muffler
bracket.

2. Remove four screws that attach spark arrester screen

(

C

).

3. Inspect screen and obtain a replacement if torn,

perforated or otherwise damaged. DO NOT use a
defective screen. If screen is not damaged, clean it with
commercial solvent.

4. Reattach screen and muffler guard.

Air Cooling System

Over time debris may accumulate in cylinder cooling fins and
cannot be observed without partial engine disassembly. For
this reason, we recommend you have an authorized service
dealer clean the cooling system per recommended intervals
(see 

Maintenance Schedule

in beginning of 

Maintenance

section). Equally important is to keep top of engine free from
debris. See 

Clean Debris

.

Check Valve Clearance

Regular valve clearance check and adjustment will improve
performance and extend engine life. This procedure cannot
be done without partial engine disassembly and the use of
special tools. For this reason we recommend that you have
an authorized service dealer check and adjust valve clearance
at recommended intervals (see 

Maintenance Schedule

in the

Maintenance

section).

Carburetor Adjustment

The carburetor on this engine is low emission. It is equipped
with a non-adjustable idle mixture valve. Top speed has been
set at the factory. If adjustment is required, see an
authorized service dealer.

WARNING

Contact with muffler area can result in serious
burns.

Exhaust heat / gases can ignite combustibles,
structures or damage fuel tank causing a fire.

• DO NOT touch hot parts and AVOID hot exhaust gases.

• Allow equipment to cool before touching.

• Keep at least 5 feet (1.5 m) of clearance on all sides of

generator including overhead.

• Code of Federal Regulation (CFR) Title 36 Parks, Forests, and

Public Property require equipment powered by an internal
combustion engine to have a spark arrester, maintained in
effective working order, complying to USDA Forest service
standard 5100-1C or later revision. In the State of California a
spark arrester is required under section 4442 of the California
Public resources code. Other states may have similar laws.

A

B

C

A

CAUTION

Excessively high operating speeds increase risk of injury
and damage to generator.

Excessively low speeds impose a heavy load.

• DO NOT tamper with governed speed. Generator supplies

correct rated frequency and voltage when running at governed
speed.

• DO NOT modify generator in any way.

Summary of Contents for 8000 Watt Portable Generator

Page 1: ...Printed in U S A Manual No 195693GS Revision E 05 29 2007 8000 Watt Portable Generator Operator s Manual BRIGGS STRATTON POWER PRODUCTS GROUP LLC JEFFERSON WISCONSIN U S A...

Page 2: ...or is designed and intended only for supplying electrical power for operating compatible electrical lighting appliances tools and motor loads and is not intended for any other purpose It is important...

Page 3: ...d Receptacles 12 Battery Float Charger 13 Operation 14 Starting the Engine 14 Connecting Electrical Loads 15 Oil Pressure Shutdown 15 Stopping the Engine 15 Cold Weather Operation 15 Don t Overload Ge...

Page 4: ...moderate injury NOTICE indicates a situation that could result in equipment damage Follow safety messages to avoid or reduce the risk of injury or death The manufacturer cannot possibly anticipate eve...

Page 5: ...stop engine with electrical devices plugged in and turned on WARNING Fuel and its vapors are extremely flammable and explosive Fire or explosion can cause severe burns or death WHEN ADDING OR DRAINING...

Page 6: ...ire where it cannot contact spark plug WHEN TESTING FOR ENGINE SPARK Use approved spark plug tester DO NOT check for spark with spark plug removed CAUTION Excessively high operating speeds increase ri...

Page 7: ...nch 7 16 and 13mm open end wrench Pliers Safety glasses Install the wheel kit as follows 1 Tip generator so that generator rests on frame with engine end up 2 Slide axle A through both mounting bracke...

Page 8: ...before starting engine High Altitude At altitudes over 5 000 feet 1524 meters a minimum 85 octane 85 AKI 89 RON gasoline is acceptable To remain emissions compliant high altitude adjustment is requir...

Page 9: ...se consult a qualified electrician electrical inspector or the local agency having jurisdiction In some areas generators are required to be registered with local utility companies If the generator is...

Page 10: ...g Ensure exhaust gas is kept away from any windows doors ventilation intakes or other openings that can allow exhaust gas to collect in a confined area Prevailing winds and air currents should be take...

Page 11: ...r loads E Grounding Fastener Consult your local agency having jurisdiction for grounding requirements in your area F Data Tag Provides model revision and serial number of generator Please have these r...

Page 12: ...0 watts of power 7 2 kW at 30 Amps for 240 Volts or two independent 120 Volt loads at 30 Amps each The outlet is protected by a double pole rocker switch circuit breaker 120 Volt AC 20 Amp Duplex Rece...

Page 13: ...xt to the start switch Plug battery charger into a 120 Volt AC wall receptacle 2 Unplug charger from unit and wall outlet when generator is being started and while it is in operation 3 Keep this charg...

Page 14: ...ters move choke lever to Half choke position until engine runs smoothly and then to Run position IMPORTANT If engine floods place choke lever in Run position and crank until engine starts NOTE If engi...

Page 15: ...stop engine with electrical devices plugged in and turned ON 2 Let engine run at no load for several minutes to stabilize internal temperatures of engine and generator 3 Push engine rocker switch to...

Page 16: ...aking sure muffler side of generator is exposed NOTE Structure should hold enough heat created by the generator to prevent icing problem 2 DO NOT enclose generator any more than shown NOTE If a wheel...

Page 17: ...to stabilize engine runs smoothly and attached device operates properly 4 Plug in and turn on the next load 5 Again permit the generator to stabilize 6 Repeat steps 4 and 5 for each additional load NE...

Page 18: ...ance Generator maintenance consists of keeping the unit clean and dry Operate and store the unit in a clean dry environment where it will not be exposed to excessive dust dirt moisture or any corrosiv...

Page 19: ...Checking Oil Level Oil level should be checked prior to each use or at least every 5 hours of operation Keep oil level maintained 1 Make sure generator is on a level surface 2 Clean area around oil f...

Page 20: ...yearly whichever comes first Clean or replace more often if operating under dusty or dirty conditions To service the air cleaner follow these steps 1 Loosen screws A and remove air cleaner cover B 2 C...

Page 21: ...nt will improve performance and extend engine life This procedure cannot be done without partial engine disassembly and the use of special tools For this reason we recommend that you have an authorize...

Page 22: ...th recommended grade See Changing Engine Oil Oil Cylinder Bore Remove spark plug and pour about 1 2 ounce 15 ml of clean engine oil into the cylinder Install spark plug and pull starter handle slowly...

Page 23: ...fuel 8 Spark plug wire not connected to spark plug 9 Bad spark plug 10 Water in fuel 11 Flooded 12 Excessively rich fuel mixture 13 Intake valve stuck open or closed 14 Engine has lost compression 1 S...

Page 24: ...isted in your Operating and Maintenance Instructions B S recommends that you retain all your receipts covering maintenance on your small off road engine but B S cannot deny warranty solely for the lac...

Page 25: ...or repairs The owner is responsible for the performance of all required maintenance as defined in the B S Operator s Manual 6 Consequential Coverage Coverage hereunder shall extend to the failure of...

Page 26: ...ty repair and apologize to you for being inconvenienced Any Authorized Service Dealer may perform warranty repairs Most warranty repairs are handled routinely but sometimes requests for warranty servi...

Page 27: ...27...

Page 28: ...ce of power equipment actual on site or net power This difference is due to a variety of factors including but not limited to accessories air cleaner exhaust charging cooling carburetor fuel pump etc...

Page 29: ...Generador Port til de 8000 Vatios Manual del Operario BRIGGS STRATTON POWER PRODUCTS GROUP LLC JEFFERSON WISCONSIN U S A...

Page 30: ...s de ser usado Consulte la secci n Montaje de este manual donde encontrar instrucciones para el montaje final Siga las instrucciones al pie de la letra D nde encontrarnos Usted no tendr que ir muy lej...

Page 31: ...s 12 Cargador de flotaci n de la bater a 13 Operando 14 Encienda el motor 14 Conexi n de cargas el ctricas 15 Parada por falta de presi n de aceite 15 Parada del motor 15 Operaci n durante un clima fr...

Page 32: ...el s mbolo de alerta AVISO indica una situaci n que podr a producir da os en el equipo Siga en todo momento los mensajes de seguridad para evitar o reducir el riesgo de lesiones y de muerte El fabrica...

Page 33: ...sirvan al generador ADVERTENCIA La combustible y sus vapores son extremadamente inflamables y explosivos El fuego o una explosi n pueden causar quemaduras severas e inclusive la muerte CUANDO ANADA CO...

Page 34: ...sconecte el alambre de la buj a y col quelo donde no pueda entrar en contacto con la buj a CUANDO PRUEBE LA BUJ A DEL MOTOR Utilice un comprobador de buj as homologado NO comprueba la chispa sin la bu...

Page 35: ...dad Instale el juego de ruedas conforme a las instrucciones siguientes 1 Dele la vuelta al generador de forma que el motor quede arriba 2 Introduzca el eje A a trav s de los dos soportes de montaje 3...

Page 36: ...para evaporar Gran altitud En altitudes superiores a 1 524 metros 5 000 pies se deber utilizar gasolina con un m nimo de 85 octanos 85 AKI 89 RON Para seguir cumpliendo la normativa sobre emisiones es...

Page 37: ...electricista cualificado un inspector el ctrico o el organismo competente En algunas zonas es obligatorio registrar los generadores en las compa as el ctricas locales Si el generador se utiliza en una...

Page 38: ...cape no puedan entrar por ventanas puertas tomas de aire de ventilaci n u otras aberturas en un espacio cerrado en el que puedan acumularse Tenga en cuenta los vientos y las corriente de aire preponde...

Page 39: ...or de Aire Filtra el aire de entrada a medida que penetra en el motor J Palanca Estranguladora Usada cuando se est dando arranque a un motor fr o K Tanque del Combustible El tanque tiene una capacidad...

Page 40: ...os AC de 60 Hz fase sencilla que requieren hasta 7 200 vatios de energ a a 30 Amperios para 240 Voltios o dos independientes 120 voltio cargas El enchufe est protegido por un disyuntor basculante Toma...

Page 41: ...nidad que se encuentra en el interruptor de arranque Enchufe el cargador de la bater a a una toma de pared de 120 V CA 2 Desconecte el cargador de la unidad y del enchufe de la pared durante el arranq...

Page 42: ...sos desde 5 hasta 7 7 Coloque la palanca de retroceso en la posici n de Run marcha Si el motor vacila mueva la palanca de retroceso hasta la posici n media Half hasta que el motor marche suavemente y...

Page 43: ...dor autorizado de servicio Briggs Stratton NO utilice el motor hasta que la presi n de aceite sea correcta Parada del motor 1 Desconecte todas las cargas el ctricas de los tomacorrientes del panel del...

Page 44: ...ndose de que el lado del silenciador quede expuesto NOTA La estructura debe mantener una cantidad suficiente del calor disipado por el generador para evitar problemas de congelaci n 2 NO cierre el ge...

Page 45: ...nte 4 Conecte y encienda la pr xima carga 5 De nuevo permita que el generador se estabilice 6 Repita los pasos 4 y 5 para cada carga adicional que usted tenga NUNCA a ada cargas que sobrepasen la capa...

Page 46: ...l quidos en el generador a trav s de las ranuras del aire de refrigeraci n parte del l quido puede permanecer en los huecos y rendijas del aislamiento del devanado del rotor y del estator El l quido y...

Page 47: ...probaci n del Nivel de Aceite Compruebe el nivel de aceite antes de cada uso o cada 5 horas de funcionamiento como m nimo Rellene si es necesario 1 Coloque el generador sobre una superficie nivelada 2...

Page 48: ...polvo Para dar servicio al filtro de aire siga los pasos que se detallan a continuaci n 1 Afloje los tornillos A y quite aire la cubierta m s limpia B 2 Quite filtro de espuma C y papel el filtro D 3...

Page 49: ...mejorar y tendr una mayor vida til Este procedimiento no puede llevarse a cabo sin desmontar parcialmente el motor y sin usar herramientas especiales Por esta raz n le recomendamos que un distribuidor...

Page 50: ...ecomendado Aceite el di metro interior del cilindro Quite la buj a y vierta aproximadamente 15 ml 1 2 onza de aceite de motor limpio en el interior del cilindro Coloque la buj a y arranque lentamente...

Page 51: ...sa 10 Agua en la gasolina 11 Sobrecebado 12 Mezcla de combustible excesivamente rica 13 La v lvula de entrada est atascada est cerrada 14 El motor ha perdido compresi n 1 Gire la v lvula del combustib...

Page 52: ...rrecta realizaci n de las operaciones de mantenimiento que se enumeran en las Instrucciones de uso y mantenimiento B S recomienda conservar todas las facturas relativas al mantenimiento del motor pero...

Page 53: ...rabilidad equivalentes El propietario es responsable del cumplimiento de todas las operaciones de mantenimiento obligatorio que se definen en el manual del operario de B S 6 Cobertura de da os derivad...

Page 54: ...equipos sanitarios destinados al mantenimiento de las constantes vitales Esta garant a excluye los fallos debidos a hechos fortuitos y a otros acontecimientos de fuerza mayor que escapan al control d...

Page 55: ...27...

Page 56: ...equipos potencia en la aplicaci n o neta real Esta diferencia se debe entre otros a los siguientes factores accesorios filtro de aire escape carga refrigeraci n carburador bomba de combustible etc li...

Reviews: