
14
15
8.2 Summary
The Summary page displays the Control Unit and a separate box for each of the Function Units. Click the Settings
button on the respective unit to open the confi guration page for this unit.
8.3 View & Change Settings - Control Unit
To change system settings, select the ‘Settings’ button in the Control Unit section of the SUMMARY page. Settings can be
changed in the following sections:
Date/Time
General
Set number of antennas: 1 (only change this if further antennas are added).
Alarm
Set Volume: Low, Medium or HighAlarm Time: Number of seconds the alarm continues after tag leaves detection
zoneAlarm Acknowledge: Disabled, Mute One or Mute All (Mute One is recommended). This is to allow the driver to silence
the alarm once a detected tag has been acknowledged.Alarm Tone = Default or Alternative.
Driver
Driver Tag Alarm = Enable (Unit alarms if tag is left in the controller when the ignition is off )
ALL other settings should remain as pre-set.
To change antenna settings, select the ‘Settings’ button in the Antenna section of the SUMMARY page.
Antenna Power
This determines the Antenna power/detection range. Enter: No.1=Min to 15=Max
Note: SW1 on Control Unit must be set to 0 (see ‘Antenna switch settings’ overleaf)
Important! The system has two range levels which must be set depending on the required detection distance. This setting
can be located by following:ADMIN \ GENERAL \ RFID
Relay
Confi gure how the Control Unit relay will operate. Relay can be activated from a number of sources and released by mute
or acknowledge push button press under selected conditions
Input
The Antenna Unit can be enabled /disabled via the input 1 signal (either high or low) and the events recorded (see optional
wiring table on page 12).
All other settings should only be changed under instruction.
8. Wi-Fi Confi guration & Settings
8.1 Control Unit Connection
The Control Unit broadcasts a SSID of ZoneSafe_XXXXXX
where XXXXXX is the device’s serial number, as printed on
the product label on the back of the unit.
From your device, view available Wi-Fi connections and
select this network and click Connect. Enter the default
security key “ZONESAFE” and click OK.
Example serial number located on back of Control Unit.
When the connection has been established, open a web
browser and enter URL http://192.168.0.1/ This is the
address of the Control Unit.
When prompted, enter the default user name as “admin”
and the password “PASSWORD”.
Usernames and passwords are case-sensitive.
Antenna Unit Power
Adjust the output power from 1-15, 1 being lowest power.
8.4 Settings & Information - Antenna Unit