116
RUDOLF - Ref. : CDR 27 028_gb
R-DPA96 A/AN - R-Module 3 (
RS485 - JBUS/MODBUS
®
)
COMMUNICATION
Decimal
Hexa.
Number
Text
Unit
address
address
of words
3454
D7E
1
Query! : phase-to-phase residual value :
0 : no
5: U12
6: U23
7: U31
3455
D7F
2
Value
3457
D81
1
Query! : phase-to-neutral residual value :
0 : no
22 : V1
23 : V2
24 : V3
3458
D82
2
Value
3460
D84
2
Duration
ms
3462
D86
1
Day
3463
D87
1
Month
3464
D88
1
Year
3465
D89
1
Hour
3466
D8A
1
Minute
3467
D8B
1
Second
Decimal
Hexa.
Number
Text
Unit
address
address
of words
3584
E00
1
Query! : maximum phase-to-phase value
:
0 : no
5: U12
6: U23
7: U31
3585
E01
2
Value
3587
E03
1
Query! : maximum phase-to-neutral value
:
0 : no
22 : V1
23 : V2
24 : V3
3588
E04
2
Value
3590
E06
2
Duration
ms
3592
E08
1
Day
3593
E09
1
Month
3594
E0A
1
Year
3595
E0B
1
Hour
3596
E0C
1
Minute
3597
E0D
1
Second
LAST 10 VOLTAGE DIPS EVENT LOG / SAG (FUNCTION 3)
Voltage dip n-10
LAST 10 VOLTAGE SURGE EVENT LOG / SWELL (FUNCTION 3)
Voltage surge n-1
Zone size: 140 words (decimal) or 8C (hexadecimal).
Summary of Contents for Rudolf R-DPA96 A
Page 25: ...25 R DPA96 A AN RUDOLF Ref 876 583 A DPA96A DPA96A DPA96A DPA96A x 1 x 2 x 3 x 4 OPERATION...
Page 27: ...27 R DPA96 A AN RUDOLF Ref 876 583 A DPA96A DPA96A DPA96A x 9 x 10 x 11 DPA96A x 12 OPERATION...
Page 28: ...28 RUDOLF Ref 876 583 A R DPA96 A AN DPA96A DPA96A DPA96A x 3 x 1 x 2 OPERATION...
Page 43: ...43 RUDOLF Ref 876 584 A...
Page 44: ...44 RUDOLF Ref 876 584 A...
Page 53: ...53 SOCOMEC R f 876 585 A...
Page 54: ...54 SOCOMEC R f 876 585 A...
Page 129: ...129 RUDOLF Ref 876 341 A...
Page 130: ...130 RUDOLF Ref 876 341 A...
Page 139: ...139 RUDOLF Ref 876 586 A...
Page 140: ...140 RUDOLF Ref 876 586 A...
Page 152: ...152 RUDOLF Ref 876 587 A...
Page 168: ...OPERATION DPA96A DPA96A RUDOLF Ref 876 588 A R DPA96 A AN R Module 7 Memory 168...