Breezaire WKS-2200 Series Installation Instructions Manual Download Page 5

In some cases, improper placement or installation may cause the unit's performance to be degraded. 

The condensing unit

must have a constant supply of fresh air, less than 90o F.

 If the condensing unit is located in a confined area with poor

ventilation, the unit will not be able to reject the heat it is removing from the enclosure and a malfunctioning unit will be
suspected. Similar symptoms may be caused by an obstruction to the free flow of air into or out of the condensing unit.  In
severe cases of reduced air flow, this unit may over heat and discharge exhaust heat into the fan/coil unit and then into the
enclosure.

Proper sealing of the enclosure through the use of a plastic vapor barrier and weather stripping cannot be over
emphasized. The cooling system will not be able to maintain the proper conditions if fresh, moisture laden air is
constantly being introduced into an improperly sealed enclosure. Symptoms of this condition are; unit runs all
the time with only a slight reduction in enclosure temperature and/or water overflows from the unit.

 One way of

discovering gross air leaks is to stand inside the enclosure with the lights off, allow  your eyes to adapt to the dark and look
for light showing through cracks in the walls or around the door. Because of the temperature difference between the inside
and outside, very small cracks can allow large amounts of outside air into the enclosure.  Please be aware that moisture can
pass through solid concrete, paint and wood.

Often a newly constructed room contains fresh wood, paint, concrete and other building materials.  These materials contain
large amounts of moisture. When placed into operation in this type of environment, the system will work harder to remove
this extra moisture resulting in increased "on time".

In areas where the ambient relative humidity is very low, the desired enclosure relative humidity may not be achieved
without adding moisture. To add moisture to the enclosure use only slow, natural evaporation from a small water container.
Do not use a humidifier.

WKS2200 2/04  PG5

3/8" OD DRAIN TUBE

3/8  SUCTION LINE

1/4" LIQUID LINE

110V ELECTRICAL CORD

EVAPORATOR INTAKE

EVAPORATOR OUTLET

THERMOSTAT

3/8" SUCTION LINE

1/4" LIQUID LINE

ELECTRICAL WIRING

CONDENSER OUTLET

CONDENSER INTAKE

FAN/COIL UNIT

CONDENSING UNIT

Summary of Contents for WKS-2200 Series

Page 1: ...d the entire instruction booklet before beginning the installation Before removing the cooling unit from the box please inspect for damage which might have occurred during shipping If damage is found notify the shipper immediately and file a claim BREEZAIRE is not responsible for any damages during shipping MODEL___________________ SERIAL NUMBER__________________ INSTALLED BY______________________...

Page 2: ...EEZAIRE dealer for assistance in choosing the correct unit BREEZAIRE units are not warranted to cool a specific enclosure All interior walls and floor should have a vapor barrier and a minimum of R 11 insulation All exterior wall s insulation values should be a minimum of R 19 The ceiling should have vapor barrier and a minimum of R 19 insulation The vapor barrier should be installed on the warm s...

Page 3: ...ble flooding and shaded from direct sun light Remove the screws and the cover F Plumbing the system The two units are connected by a 1 4 inch liquid line copper tube and a 3 8 inch suction line copper tube The line set should have a minimum linear length not less than 35 ft and a maximum linear length no longer than 100 ft for each line Reduce the line set length by 10 feet for every hard 90 bend ...

Page 4: ...cted and vacuumed to prevent any air blockage The condenser coil in the condensing unit is located out side the enclosure Use a vacuum and brush attachment to remove the lint or dirt that may reside between the aluminum fins If the condenser coil becomes blocked preventing proper air flow the unit will over heat causing a loss in cooling efficiency and will result in failure of the unit not covere...

Page 5: ...from the unit One way of discovering gross air leaks is to stand inside the enclosure with the lights off allow your eyes to adapt to the dark and look for light showing through cracks in the walls or around the door Because of the temperature difference between the inside and outside very small cracks can allow large amounts of outside air into the enclosure Please be aware that moisture can pass...

Page 6: ...ed to BREEZAIRE in a condition that allows testing of the component and if that component is determined defective BREEZAIRE will refund the customer the cost of the component and freight What BREEZAIRE will NOT pay for 1 Installation or removal of the unit component 2 Handling or packaging of the unit component 3 Component repairs performed by anyone other than a BREEZAIRE authorized repair facili...

Reviews: