INSTALLATION INSTRUCTIONS 

FOR WKCE SERIES COOLING UNITS 

  The 

BREEZAIRE

 

WKCE Series cooling units are designed to, when installed in a properly constructed 

enclosure, provide a constant, selectable temperature between 48°F and 62°F while maintaining the relative 
humidity to the proper 50% to 75%.  

BREEZAIRE

 cooling units are designed to lower the temperature, while 

removing 

only 

excessive moisture.  In a properly constructed enclosure this process can raise the 

relative

 

humidity.  The unit does not add moisture to the enclosure.  The unit does not include a heating system and 
will not warm the enclosure.  The WKCE Series is not intended to cool service cabinets, which are maintained 
at lower temperatures and opened or entered frequently. 

The Digital Electronic (Sentry III) thermostat has the following features: 

 

Large, easy to read, green LED display. 

 

Accurate, easy to adjust readable set points with continuous reading of enclosure temperature or 

displaying of set point when changing enclosure temperatures. 

 

Power outage protection, which delays unit start up after power outages. 

 

Blocked airflow protection, which shuts down unit and protects wine in case of high temperatures 

caused by condenser blockage. 

 

Controls temperature by enclosure air sensors or optional bottle probe. 

Please see the Sentry III Owners manual 

  

   

 

  The 

BREEZAIRE WKCE

 series, with the cold air discharge on the bottom of the cooling units were designed 

and engineered for cabinets and credenzas.  However if you have looked at the

 BREEZAIRE WKL

 series 

cooling unit and you feel the

 WKCE

 series units will better serve your application consult your dealer for 

assistance. 

ENCLOSURE CONSTRUCTION GUIDELINES 

  To use the below SIZING GUIDE, the enclosure to be cooled must be built to the following minimum 
specifications.  If the enclosure cannot be built to these minimum specifications, consult your 

BREEZAIRE

 

dealer for assistance in choosing the correct unit.  

BREEZAIRE

 cooling units are not warranted to cool a 

specific enclosure.

 

  All walls, floors and ceilings should have a vapor barrier.  This vapor barrier should be installed on the warm 
side of the insulation.  All interior walls and floors should be lined with a minimum of R-11 insulation and 
exterior walls and ceiling insulation value should be a minimum of R-19.  There should be no glass windows or 
doors. 

 

  WKCE series are specifically designed and engineered to be installed in cabinets and credenzas.  The 
enclosures in which you install the cooling unit must be well insulated and air tight for the cooling unit to 
perform properly. 

 

  All joints, door frames, electrical outlets or switches and any pipes or vents which go through the 
enclosure should be sealed to prevent air and moisture leakage into the room.  Concrete and brick are 
not insulation or moisture barriers. 

 

  Doors into the enclosure should be of minimum size, insulated to R-11 and be tightly sealed with a high 
quality weather stripping.  Be sure to seal the bottom of the door and behind the door frame's molding. 

 

  Enclosure lighting should be of low wattage, with a timer to insure lights are not left on when the 
enclosure is unoccupied.  Recessed lighting should not be used, as they will allow outside air to enter the 
enclosure. 

 

  If the ambient temperature surrounding the enclosure exceeds the enclosure's temperature by more 
than

 

25

°

F the units cooling capacity will be reduced.  No enclosure wall should receive direct sunlight or 

strong wind. 

 

Note: 

 Glass doors and/or windows are not included in our calculations and should not be used in a wine 

enclosure. 

 