SERIES 70 ELECTRIC ACTUATOR
Installation, Operation, and Maintenance Manual
26 of 48
© 2022 BRAY INTERNATIONAL, INC. ALL RIGHTS RESERVED. BRAY.COM
The Information contained herein shall not be copied, transferred, conveyed, or displayed in any manner
that would violate its proprietary nature without the express written permission of Bray International, Inc.
4 . Lock the travel stop bolt in position with the locknut .
5 . Manually drive the actuator to the ‘open’ position .
6 . Once the actuator is in the ‘open’ position, rotate the handwheel
counterclockwise
> ½ turn for Actuator Size E03, E06, E08.
> 1 turn for Actuator Size E12, E20, E30.
> ½ turn for Actuator Size 050, 065.
> 2 turns for Actuator Size 130, 180.
7 . Adjust the ‘open’ travel stop bolt until the travel stop spacer is fully engaged or
the travel stop bolt contacts the output segment gear .
8 . Lock the travel stop bolt in position with the locknut .