background image

With most installations, the only variable that can be changed is the location of the transmitter. 
In some cases, you may find that a target gas source is too close to the transmitter.  Consider 
other mounting locations for the transmitter or move the gas source farther away.

Maintenance

Testing the Response to the Target Gas

Carbon Monoxide or Nitrogen Dioxide Transmitters

Testing these transmitters requires that the target gas be applied to the sensor using one of 
two methods.  Gas can be applied from a tank of air containing a known concentration of the 
target gas or from the exhaust of an operating engine to produce a level of target gas sufficient
to activate the control system.  For the latter method, use a gasoline or petrol engine to 
produce CO and a diesel engine to produce NO

2

.

Of the two methods of obtaining test gas, the simplest is operating an engine in the vicinity of 
the transmitter under test.  The engine should be placed about 10 feet away from the 
transmitter so that exhaust gases will not contact the transmitter directly. 

The engine should be allowed to operate until a level of the target gas is sufficient to activate 
the ventilation system.  Depending upon the volume of the area where the transmitter is 
located, this may take from 10 to 30 minutes.

Using test gas applied from a tank has the advantage of speed as well as assurance that the 
transmitter is responding accurately to the target gas.  However, the gas must be applied 
directly to the sensor if the response is to be close to the value present in the tank.  The test 
gas cannot be allowed to become diluted by the air in the room before it comes in contact with 
the sensor. This reduces the concentration to a level too low to give the desired result.

IOM02
Rev 1.0 – December 22, 2020

20

CAUTION

Allowing the transmitter to come in direct contact with undiluted exhaust gases will decrease 
the expected useful lifetime of the sensor.  The high concentration of acids and other 
components in the exhaust gas will overload the activated carbon filter inside the sensor and 
will increase the effects of interfering gases on the accuracy of the sensor.

If the sensor becomes damaged, it must be replaced with a new sensor calibrated at the 
factory. 

Summary of Contents for TRNS Generation 2

Page 1: ...Brasch Environmental Technologies LLC 140 Long Road Suite 101 Chesterfield Missouri 63005 314 291 0440 www braschenvtech com TRNS Generation 2 Installation Operation Manual...

Page 2: ...Output 14 Connecting the Modbus Output 15 Applying Power For the First Time 15 Installation Diagrams 16 Operation 18 How the Transmitter Senses the Target Gas 18 Factory Default Settings 18 Using the...

Page 3: ...d in an Unsatisfactory Location 23 Limited Warranty 24 Warranty Statement 24 Service and Repair Procedures 24 Appendix 25 Model Numbers and Descriptions 25 Transmitter Model Number and Description 25...

Page 4: ...and transmits that signal to the output as either an analog or digital signal The sensor used in the transmitter operates on the electrochemical principle A current is produced when the target gas re...

Page 5: ...nance Simplified Installation Preconfigured Wiring Factory Calibration Customized Programming Versatile Communication Analog Output via User Selectable Current or Voltage Loop Digital Output via Modbu...

Page 6: ...Humidity 10 to 90 non condensing Ventilation Control Relays None Internal Alarm None Front Panel Indicators Power green LED Fault yellow LED Display None Selectable Fan Settings None Alert Levels None...

Page 7: ...h target gas for which Brasch currently produces a transmitter is listed below along with the relevant concentration specifications Carbon Monoxide Full Scale Span 200 PPM Resolution 1 PPM Minimum Acc...

Page 8: ...er The following table describes the function of each indicator Please refer to the transmitter s front panel label for the indicator s location Front Panel Indicators Indicator Color Description Powe...

Page 9: ...understand all such notices Types of Notices Three types of notices may be used in this manual to describe the severity of the situation encountered WARNING This notice indicates that conditions exis...

Page 10: ...provided The circuit must include a disconnect switch located within easy reach of the transmitter Color coded wires exiting the transmitter housing through the top conduit connector are provided for...

Page 11: ...eference conductor connects to the green wire When using the digital output the positive conductor connects to the brown wire and the negative conductor connects to the blue wire See figures 1 and 2 o...

Page 12: ...entative of the average gas value in that area These include but are not limited to locations near doorways fans ventilation inlets and outlets and areas with air velocities in excess of 3 3 ft s 1 m...

Page 13: ...ing cover to gain access to the mounting holes A mounting hole is located at the top and bottom of each housing end wall Find a flat area at least 6 inches high by 6 inches long and place the back of...

Page 14: ...for connecting the operating voltage to the transmitter Therefore it should not be necessary to remove the front cover from the transmitter when connecting the voltage supply Connect the hot power con...

Page 15: ...ociated with the transmitter Color coded wires exit the transmitter housing through the top conduit fitting so removal of the front cover should not be necessary At each transmitter the positive condu...

Page 16: ...Installation Diagrams IOM02 Rev 1 0 December 22 2020 16 Figure 1 Wiring Analog Output Configuration Figure 2 Wiring Digital Output Configuration...

Page 17: ...IOM02 Rev 1 0 December 22 2020 17 Figure 3 Wiring Remote Sensor Configuration...

Page 18: ...specified on the order form the following settings will be used to configure the analog proportional output of the transmitter Setting Default Analog Proportional Output Units mA Analog Proportional...

Page 19: ...he 4 20 mA output mode 0 PPM CO would equal 4 mA while 200 PPM CO would equal 20 mA Follow the instructions supplied with your controller to adjust the controller s input for the proper scaling of the...

Page 20: ...t contact the transmitter directly The engine should be allowed to operate until a level of the target gas is sufficient to activate the ventilation system Depending upon the volume of the area where...

Page 21: ...l Technologies recommends testing the detector once every six months to ensure proper response and accuracy Replacing the Sensor The sensor s useful lifetime depends greatly upon its operating conditi...

Page 22: ...l be approximately 10 years from the original manufacturing date for both Carbon Monoxide and Nitrogen Dioxide sensors The signal is triggered by a clock in the sensor board In the event that the unit...

Page 23: ...er must be greater than 100 k If these requirements are not adhered to the proportional output will not accurately reflect the concentration of gas measured by the sensor Transmitter Mounted in an Uns...

Page 24: ...nd would like to discuss it with a factory service technician you may call the number listed on the product label You will be transferred to a technician specially trained to service that product This...

Page 25: ...ly identify a transmitter once you know the model number Transmitter Model Number and Description Output Type Target Gas CO NO2 CO NO2 Analog TRNS2 CM Analog TRNS2 ND Analog TRNS2 NCM Analog Digital T...

Page 26: ...v 1 0 December 22 2020 26 UNREG COM UNREG COMM COMM Black White Black Figure 5 Input Power Connections JP2 JP3 4 20 mA 2 10 VDC 1 5 VDC 0 2 1 VDC JP2 JP3 JP2 JP3 JP2 JP3 Figure 6 Proportional Output S...

Page 27: ...roportional Output Graphs 4 6 8 10 12 14 16 18 20 0 50 100 150 200 Carbon Monoxide Output mA Concentration ppm CO 4 6 8 10 12 14 16 18 20 0 2 5 5 7 5 10 Nitrogen Dioxide Output mA Concentration ppm NO...

Page 28: ...0 ppm NO 0 5 Sensitivity measured 10 ppm Cl2 100 Sensitivity measured 20 ppm SO2 2 Sensitivity measured 400 ppm CO 0 1 Sensitivity measured 400 ppm H2 0 1 Sensitivity measured 400 ppm C2H4 0 1 Sensiti...

Page 29: ...merservice braschenvtech com Website www braschenvtech com Revision 1 0 Issue Date December 22 2020 Document Number IOM02 Brasch Environmental Technologies LLC All Rights Reserved Technical Support Co...

Reviews: