![Brant Radiant Heaters DES3 Series Manual Download Page 30](http://html1.mh-extra.com/html/brant-radiant-heaters/des3-series/des3-series_manual_2802224030.webp)
30
DES3
Series
*Consult the NFPA ANSI Z223.1 Gas Vent Termination criteria if roof pitch exceeds 9:12
24 in.
Min.*
Duravent Type PVP
Venting
Roof*
Heater
Fire Stop Spacer
#8 Sheet Metal Screws (field supplied)
Adjustable Roof Flashing
Storm Collar
Vent Adapter
Clean Out Tee Fitting
Vent Cap
Clean Out Cap
3.0
Installation
•
General Venting Requirements
1 in. Minimum Clearance -
Use Attic Insulation Shield
(Field Supplied)
Figure 3.21
•
General Venting Requirements
When possible, avoid venting through an unconditioned space. Venting through an unconditioned space
promotes condensation. When venting through an unconditioned space is unavoidable, or if the unit is
installed in an area that is prone to condensation, insulate venting runs greater than 5 feet to minimize the
production of condensation. Inspect for leakage prior to insulating the venting and only use insulation that
is non-combustible with a temperature rating of not less than 480°F. Install a tee fitting at the low point of
the vent system and provide a drip leg with a clean out cap as shown in figure 3.21.
When venting pipe passes through a combustible interior wall or floor, a metal thimble with a diameter 4
inches greater than the vent pipe diameter must be used. If there is 6 feet or more of vent pipe prior to
passing through the combustible wall or floor, then the metal thimble need only be 2 inches greater than
the vent pipe diameter. If a metal thimble is not used, all clearance to combustibles from the vent pipe
must be 6 inches. Any material used to close or insulate the opening must be non-combustible.