background image

8

9

TROUBLESHOOTING

6

1.

   Locate the battery compartment door.

2.

   Gently remove the two "AA" alkaline batteries located in the battery compartment.  

3.

   Install two new "AA" alkaline batteries into battery compartment.  Be sure to  

 

 

match the positive (+) ends of the batteries with the positive (+) terminals located   

 

in the battery compartment.

4.

   Close battery compartment and verify that the low battery indicator does not  

 

 

appear in the display.

In order to maximize comfort and energy efficiency, this thermostat is equipped with an 

Adaptive Recovery Mode (ARM™). This feature minimizes the amount of time required by 

heating or cooling system to reach the new setpoint, after a setback period is completed, and 

assures your desired temperature is achieved at your set program times.
This feature activates when recovering room temperature from setback programs to comfort 

programs, so it will only take place when the current (heating) program setpoint temperature is 

lower than the upcoming program set point temperature, or the current (cooling) program 

setpoint temperature is higher than the upcoming program setpoint temperature.
During ARM™, room temperature is recovered gradually by turning on the heating or cooling 

before the end of the setback period. The set point temperature is changed to that of the 

upcoming comfort program temperature. The start time of recovery is based on the difference 

between the current room temperature and the upcoming comfort program setpoint 

temperature. The recovery to the upcoming setpoint starts 10 minutes before the upcoming 

setpoint time for each degree of temperature change required, up to a maximum of 2 hours.
ARM™ does not operate when the unit is in the 

HOLD

 mode, or if the program is temporarily 

overridden.

SYMPTOM

POTENTIAL SOLUTION

Thermostat does not 

turn on heating or 

cooling system.

Check to see if 

OFF

 is shown in display. This indicates that the 

system is turned off at the thermostat. Move the system selector 

switch to the 

HEAT

 or 

COOL

 position. After the compressor short 

cycle protection 5-minute period expires the system should start 

within a minute’s time.
Compressor protection features may be in effect due to 

compressor short cycle conditions, power outages or rolling 

blackouts. See 

Compressor Protection

, section 5.4 for full 

explanation of this feature.
Heating or cooling system may be malfunctioning. Call a 

professional service technician immediately to verify  

system operation.

Thermostat turns on 

heating instead of 

cooling or cooling 

instead of heating.

Check thermostat wiring to make sure that the heating and 

cooling stages are connected to the correct terminals on the 

wiring terminal block. For heat pump systems, check that the 

O/B switch is set to the correct position. See 

Installation and 

Wiring Diagrams

 sections of this manual.

Verify your program time and temperature entries. The heating 

and cooling programs utilize separate times and temperatures 

for the 

MORN

DAY

EVE

 and 

NIGHT

 setpoints. See 

Setting Your 

Energy Saving Programs

, section 4.4 of this manual.

Thermostat program has been temporarily overridden and 

program indicator is flashing in the display. Press 

RETURN

 

button to return the thermostat to normal program operation or 

wait until next setpoint and the temporary override will expire.
Thermostat program is in Extended Hold (Vacation) Mode and 

HOLD

 and 

TEMP

 is showing in display. Press 

HOLD

 or 

RETURN

 

button to release permanent hold and return the thermostat to 

normal program operation.

Thermostat turns 

heating or cooling 

system on too often or 

not often enough.

Increase or decrease first stage temperature differential setting 

as appropriate to provide the desired performance level. See 

Setting Temperature Differential,

 section 4.3.1 of this manual.

Thermostat will not 

follow program 

setpoints.

 

Check current time of day, day of week program settings. Be 

sure to verify 

AM/PM

 indicator is accurately displaying desired 

time settings. See 

Setting Current Time of Day and Day of Week,

 

section 4.2 of this manual.
Check to see if 

OFF

 is shown in display. This indicates that the 

system is turned off at the thermostat. Move the system selector 

switch to the 

HEAT

 or 

COOL

 position. After the compressor short 

cycle protection 5-minute period expires the system should start 

within several seconds.

ADDITIONAL 

OPERATION FEATURES

5

cont.

5.6

Adaptive Recovery Mode (ARM™)

The Reset feature allows the user to completely reset the thermostat to register new 

manual switch settings. To erase all entered programs, current time of day, day of week 

and other user settings, gently press the 

RESET

 button using a paper clip or a small 

pencil tip.

5.8

Resetting the Thermostat

5.7

Filter Check Monitor (see section 4.3.3 for setting)

The Filter Check Monitor displays a reminder for required filter replacement or cleaning, by 

flashing the 

FILT

 segment in the display. See instructions on your filter or heating/cooling 

unit for recommendations for interval setting.

When the selected interval has been reached, and required cleaning or replacement has 

been performed, press the 

RETURN

 button in any normal mode to reset the timer and turn 

off the warning.

5.5

Low Battery Detection and Replacement 

cont.

Summary of Contents for 2000NC

Page 1: ...ermostat can also be used on 250mv to 750mv millivolt heating only systems Do not use this thermostat on applications with voltages above 30 Volts AC 2 2 Installing Your New Thermostat NOTE If you are...

Page 2: ...Press the button on the keypad until the setpoint temperature is a minimum of 3 degrees lower than the current room temperature 6 The cooling system should start within several seconds Place the syste...

Page 3: ...ended hold time 1 In normal operating mode press and hold the RETURN button for 4 seconds The LCD display will show d1 x where x equals the F C differential setting This is the current temperature dif...

Page 4: ...ay Program Group will be displayed The display will show M TU W TH F to indicate the Weekday group is being programmed The hour portion of the setpoint time and the AM PM indicator will be flashing AD...

Page 5: ...oling instead of heating Check thermostat wiring to make sure that the heating and cooling stages are connected to the correct terminals on the wiring terminal block For heat pump systems check that t...

Page 6: ...or too cold See Review Set Temperature section 5 1 of this manual to verify the current set point and make any modifications that are necessary LO is shown in the thermostat display where the room te...

Page 7: ...option any Braeburn thermostat under warranty provided it is returned postage prepaid to our warranty facility in a padded carton within the warranty period with proof of the original date of purchase...

Reviews: