System Checkout
5
After the wiring and configuration is complete, built in automatic zone panel tests may be used to verify
equipment, damper, and panel operation.
To start the panel Test Mode:
1.
Ensure all wiring is complete and power has been applied to the main and expansion panels
2.
Press
TEST
for 3 seconds and release
3.
Press
SELECT
to turn the test on and off
4.
Press
NEXT
to move on to the next test
5.
Press
HOLD FOR EXIT
for 3 seconds to exit test mode
The following tests are available in Test Mode:
Heating Stage Test ON or OFF
This test turns on the heating stage, the system fan, and also
commands all dampers to open. Press
SELECT
to Test
or
NEXT
to advance to the next test.
Cooling Stage Test ON or OFF
This test turns on the cooling stage, the system fan, and also
commands all dampers to open. Press
SELECT
to Test or
NEXT
to advance to the next test.