Installation
MF2933/AST4
11
Bradley Corporation • 215-1178 Rev. N; EN 06-915C
10-28-2005
LOWER
BRACKET
FRONT
PANEL
SCREW
UPPER
BRACKET
Figure 10
Figure 9
TEMPERATURE
ADJUSTMENT
STEM
TEMPERATURE
LOCKING
NUT
Figure 8
7
Check operation
8
Install top cover
and front panel
CHECK TO MAKE SURE BOTH STOP/CHECK VALVES ARE FULLY
OPEN (SEE FIGURE 3 ON PAGE 8).
A
TURN ON THE MAIN WATER SUPPLY TO THE TRI-FOUNT™ AND
CHECK FOR LEAKING.
B
INSIDE THE PEDESTAL ASSEMBLY OF THE WASHFOUNTAIN (USE
FRONT ACCESS), SLIDE THE ANCHOR PLATE ONTO THE
THREADED RODS AND SECURE ANCHOR PLATE AGAINST BOWL
USING THE WING NUTS PROVIDED.
B
TO INSTALL FRONT PANEL, SLIP SLOT IN BOTTOM OF FRONT
PEDESTAL PANEL OVER THE LIP ON THE LOWER BRACKET
(SEE FIGURE 10).
C
PUSH OPERATING PUSH BUTTONS UNTIL AIR IS PURGED FROM
LINES.
C
CAREFULLY PLACE THE TOP COVER WITH THREADED RODS ON
TOP OF WASHFOUNTAIN SPRAYHEAD (SEE FIGURE 9)
A
SECURE PANEL TO UPPER BRACKET WITH ATTACHED SCREW.
D
CHECK THE TEMPERATURE WHEN APPROXIMATELY 1.0 GPM
WATER FLOW IS REACHED AND ADJUST IF NECESSARY (THE
RANGE OF THE VALVE IS 95°F–115°F (35°C–43°C). TO ADJUST
THE TEMPERATURE, FOLLOW THE PROCEDURE BELOW:
• LOOSEN TEMPERATURE LOCKING NUT WITH WRENCH.
• USING A BLADE SCREWDRIVER, TURN THE ADJUSTMENT
STEM COUNTERCLOCKWISE TO INCREASE THE
TEMPERATURE OR CLOCKWISE TO DECREASE THE
TEMPERATURE (FIGURE 8).
• ONCE DESIRED TEMPERATURE IS REACHED, TIGHTEN NUT TO
PREVENT TEMPERATURE CHANGE.
D
IMPORTANT:
The Vernatherm™ valve is NOT factory-preset. Upon
installation, the valve temperature must be checked and
adjusted to ensure delivery of safe water temperature. Water
in excess of 110°F (43ºC) may cause scalding.