Bradley S19-690H Installation Download Page 3

3

Installation 

S19-690H, S19-690HR

Bradley Corporation • 

215-084 Rev. P; ECN 07-527 

8/25/08

Installation

Step 1: Assemble Eyewash

1.  Assemble the eyewash to the tank outlet with 

pipe sealant (by installer) (see page 5).

IMPORTANT:  When connecting the 
eyewash to the tank outlet, hold the 
adapters (items 2 and 3) with a wrench 
to prevent stripping. Failure to do 
so may damage the seal and cause 
leakage. Max. torque 150 in-lbs.

2.  Connect the pressure gauge to the adapter 

on the pressure side of the tank with pipe 
sealant (by installer) (see page 5).

Step 2: Assemble Heater Jacket

1. 

Secure the pipe insulation and jacket to the 
eyewash.

2.  Wrap the belt around the tank four inches 

from the bottom of the tank; fasten securely.

3.  Connect the heat trace cable to the junction 

box.

4.  Slide the jacket up the side of the tank and 

pull the drawstring at the top of the jacket.

5.  Place the junction box in the pocket on the 

inside of the jacket.

Step 3: Fill tank and pressurize

1. 

If the tank is pressurized, relieve the tank 
pressure by pulling up on the relief tank tab 
in the center of the cover until the pressure 
gauge reads “0.”

IMPORTANT:  DO NOT open the cover 
until the pressure gauge reads “0.”

2.  Open the tank by pulling up on the wire 

handle located on top of the Quicklock 
cover. Push down, rotate and remove. Fill 
the container with 7 gallons of potable water. 
Replace the cover.

 3. Pressurize the tank to 95 PSI by applying air 

pressure to the tank valve located beneath 
the pressure gauge.

NOTE: Relief valve is designed to automatically 
vent at 100-130 PSI to prevent the tank from 
overpressurizing.

Step 4: Flush tank

1. 

Discharge the water through the eye wash 
and hose spray to flush the system. 

2.  Refill the tank and pressurize as explained in 

Step 3 outlined above.

NOTE: Let unit stand for one hour. If there is a 
noticeable pressure drop, repressurize and let 
stand for one hour. If problems persist, consult the 
Troubleshooting guide found on page 4.

NOTE: This unit will provide at least 15 minutes 
of cleansing action. Take the injured person 
immediately to a normal emergency station for 
additional cleansing and treatment.

3.  Plug the heater jacket’s electrical cord into an 

electrical outlet.

Back View

 

BR

AD

LE

Y

R

Br

ad

le

y

14"

(356mm)

24-5/8"

(625mm)

27-3/4"

(705mm)

35-7/8"

(911mm)

6"

(152mm)

Reviews: