![Bradley S19-220TSS Installation Download Page 3](http://html1.mh-extra.com/html/bradley/s19-220tss/s19-220tss_installation_2800268003.webp)
3
Installation
S19-220TSS
Bradley Corporation • 215-158TSS Rev. F; EN 06-532E
4/24/07
Installation Instructions
NOTE: Flush the water supply line before
beginning installation.
Supplies Required:
• (2) 1/4" wall fasteners and bolts
• Pipe sealant
• Piping to 1/2" IPS water supply inlet on
unit
• Piping to 1-1/4" IPS drain outlet
• Sign-mounting hardware
Step 1: Install inlet drain fittings
NOTE: Top of eyewash heads should be
33"-45" (838mm-1142mm) from floor.
1. Position the inlet drain fitting over the
1-1/4" drain outlet pipe from wall.
2. Using the inlet drain fitting as a
template, mark the bolt hole locations
on wall OR install three suitable
fasteners (supplied by installer) for
1/4" bolts in the wall at the marked
hole locations (see Figure 1).
3. Bolt the inlet drain fitting to the wall
or wall fasteners using 1/4" bolts
(supplied by installer).
Step 2: Assemble eyewash
1. Assemble eyewash components as
shown in Figure 2 on page 4.
• Apply pipe sealant (supplied by installer) to all male-threaded pipe joints.
• Use a strap wrench around pipes when tightening to prevent marring.
Step 3: Connect water supply
1. Connect the water supply piping (supplied by installer) to the 1/2" IPS inlet on the eyewash.
2. Connect the tailpiece to the 1-1/4 IPS drain outlet on the eyewash (see Figure 2 on page 4).
3. Mount the safety sign to a wall or pipe using sign-mounting hardware (supplied by installer).
4. Open the water supply lines. Test for leaks and adequate water flow.
8
-1/
8
"
(206mm)
1
3
-1/2"
(
3
4
3
mm)
Ø 10-
3
/4" (27
3
mm)
15-
3
/
8
" (
3
91mm)
4"
(102mm)
8
-
3
/
8
"
(21
3
mm)
7-1/2"
(191mm)
5-1/4"
(1
33
mm)
Wall
4-1/2"
(114mm)
3
6"
(914mm)
S
u
gg
e
s
ted
Hei
g
ht
To Floor
29-1/4"
(74
3
mm)
S
u
gg
e
s
ted
Hei
g
ht
To Floor
Figure 1