Bradley S19-220FWPT Installation Instructions Download Page 3

3

Installation

S19-220FWPT, S19-220TPT

Bradley Corporation • 215-1253 Rev. C; EN 06-532G

4/30/07

Installation
Instructions

NOTE:  Flush the water
supply line before
beginning installation.

Supplies Required:

• (3) 3/8" wall fasteners
and bolts
• Pipe sealant
• Piping to 1/2" IPS water
supply inlet on unit
• Piping to 1-1/4" IPS
drain outlet

•  Sign-mounting hardware

Step 1: Install inlet
drain fittings

NOTE: Top of eyewash
heads should be 33"-45"
(838mm-1142mm) from
floor.

1. Position the inlet drain

fitting over the 1-1/4"
drain outlet pipe from
wall. 

2. Using the inlet drain

fitting as a template,
mark the bolt hole
locations on wall OR
install three suitable
fasteners (supplied by
installer) for 3/8" bolts
in the wall at the
marked hole locations
(see Figure 1).

3. Bolt the inlet drain fitting to the wall or wall fasteners using 3/8" bolts (supplied by installer).

Step 2: Assemble eyewash 

1. Assemble eyewash components as shown in Figure 2 on page 4.

• Apply pipe sealant (supplied by installer) to all male-threaded pipe joints.

• Use a strap wrench around pipes when tightening to prevent marring.

Step 3: Connect water supply

1. Connect the water supply piping (supplied by installer) to the 1/2" IPS inlet on the eyewash. 

2. Connect the P-trap and the tailpiece to the 1-1/4 IPS drain outlet on the eyewash.

3. Mount the safety sign to a wall or pipe using sign-mounting hardware (supplied by installer).

4. Open the water supply lines. Test for leaks and adequate water flow.

Figure 1