Bradley S19-220DCRPT Installation Download Page 3

3

Installation

S19-220DCRPT

Bradley Corporation • 215-1256 Rev. E; EN 06-532G

4/30/07

Installation Instructions

NOTE:  Flush the water supply line before
beginning installation.

Supplies Required:

• (3) 3/8" wall fasteners and bolts
• Pipe sealant
• Piping to 1/2" IPS water supply inlet on unit

•  Sign-mounting hardware

Step 1: Install inlet drain fittings

NOTE:  Top of eyewash heads should be 33"-45"
(838mm-1142mm) from floor.

1. Position the inlet drain fitting over the 1-1/4"

drain outlet pipe from wall. 

2. Using the inlet drain fitting as a template,

mark the bolt hole locations on wall OR install
three suitable fasteners (supplied by installer)
for 3/8" bolts in the wall at the marked hole
locations (see Figure 1).

3. Bolt the inlet drain fitting to the wall or wall

fasteners using 3/8" bolts (supplied by
installer).

Step 2: Assemble eyewash

1. Assemble eyewash components as shown in

Figure 2 on page 4.

• Apply pipe sealant (supplied by installer) to

all male-threaded pipe joints.

• Use a strap wrench around pipes when

tightening to prevent marring.

Step 3: Connect water supply

1. Connect the water supply piping (supplied by

installer) to the 1/2" IPS inlet on the eyewash. 

2. Connect the P-trap and tailpiece to the 1-1/4"

IPS drain outlet on the eyewash.

3. Mount the safety sign to a wall or pipe using

sign-mounting hardware (supplied by
installer).

4. Open the water supply lines. Test for leaks and adequate water flow.

17-1/4"

(4

38

mm)

8

-

3

/4"

(222mm)

21-1/2"

(546mm)

14"

(

3

56mm)

8

-

3

/4"

(22

3

mm)

8

-1/4"

(210mm)

4-5/

8

"

(119mm)

1

3

-5/

8

"

(

3

46mm)

Ø10-

3

/4"

(27

3

mm)

2-1/4"

(57mm)

Ø5/16"

(

8

mm)

MTG.

HOLE

4"

(102mm)

5-1/4"

(1

33

mm)

3

6" (914mm)

S

u

gg

e

s

ted 

Hei

g

ht

To Floor

3

0-1/2" (775mm)

S

u

gg

e

s

ted 

Hei

g

ht

To Floor

Figure 1

Reviews: