3
Installation
S19-120P
Bradley •
215-148P Rev. R; ECN 17-05-039
7/18/2017
Supplies Required
• Pipe sealant and teflon tape
• Piping to 1" NPT water supply inlet
• Adequate supply pipe supports
• Minimum 4" (102 mm) drain to accommodate
30 gallons (115 liters) per minute discharge for
shower waste
• Sign-mounting hardware
• Backflow prevention device as required by
UPC, IPC and/or local plumbing codes
• OPTIONAL: Hardware to mount bracket to wall
Assemble components
1. Assemble components as shown on page 4.
2. Apply pipe sealant or tape (by installer) to all
male-threaded pipe joints.
3. Bottom edge of showerhead should be 84"
(2134 mm) from the floor.
Connect water supply
NOTICE! Do not rely on Bradley’s Drench Shower
to support supply piping.
1. Connect water supply piping to 1" NPT inlet
on unit (piping supplied by installer). Provide
adequate supports (supplied by installer)
for supply pipe using pipe hangers or other
means.
2. Mount the safety sign to the wall using sign-
mounting hardware supplied by installer.
4½"
(114mm)
9"
(229mm)
Ø 3.1"
(78.7mm)
20"
(508mm)
84"
(2134mm)
Suggested
Height to
Floor
25½"
(648mm)
3
⁵⁄₈
"
(92mm)
6"
(152mm)