background image

Installation Instructions

Bradley Drench Shower   Horizontal Supply

Model No. 

Installation Instructions

Supplies Required:

Pipe sealant

Piping to 1” BSP water supply inlet on unit

Adequate supply pipe supports

Minimum 102 mm (4”) drain to accommodate 115 liters per minute discharge for drench

shower waste

Step 1: Assemble drench shower

NOTE: Flush the water supply line before beginning

installation.

1. Assemble drench shower components as shown

in Figure 2 on page 4.

2. Apply pipe sealant or tape (supplied by installer)

to all male-threaded pipe joints.

NOTE: Use a strap wrench around the pipes when

tightening to prevent mm-ring.

3. The 

bottom edge of the showerhead should be

2134 mm 

 from the floor.

Step 2: Connect water supply

IMPORTANT: Do not rely on Bradley’s

Drench Shower to support

Figure 1

supply piping.

1. Connect water supply piping to 

 BSP inlet on unit (piping supplied by installer).

Provide adequate supports (supplied by installer) for supply pipe using pipe hangers or
other means.

2. Mount safety sign to wall or pipe using sign mounting hardware supplied.

3. Open water supply lines. Test for leaks and adequate water flow.

Installation Instructions 

continued.. 

Bradley Corporation 

 

 G; EN 98-579

3

Summary of Contents for E19-120A

Page 1: ...ANT This equipment should be inspected tested and recorded weekly to maintain proper operation Main water supply to the eye wash should be ON at all times This installation manual and parts list should be filed by the building owner s maintenance department 215 148AE Ref G EN 98 579 Page 1 of 4 PO Box 309 Menomonee Falls WI USA 53052 0309 PHONE 414 251 6000 FAX 414 251 5617 http lwww bradleycorp c...

Page 2: ...o be defective within one year from the date of our invoice at our option F O B Menomonee Falls Wisconsin 2 This warranty does not cover installation or any other labor charge and does not apply to fixtures which have been damaged by accident abuse or improper maintenance 3 The repair or replacement of the defective fixtures as stated in this warranty shall constitute the sole remedy of the purcha...

Page 3: ... by installer to all male threaded pipe joints NOTE Use a strap wrench around the pipes when tightening to prevent mm ring 3 The bottom edge of the showerhead should be 2134 mm 7 O from the floor J Step 2 Connect water supply IMPORTANT Do not rely on Bradley s Drench Shower to support Figure 1 supply piping 1 Connect water supply piping to l 1 4 BSP inlet on unit piping supplied by installer Provi...

Page 4: ...235 1 ADAPTER 1c S27 278 1 1 BALL VALVE 4E 125 OOlDP 1 WASHER 1D 128 129 1 HANDLE 4F 157 005 4 DIFFUSER PADS 1E 140 720 1 STOP BRAcKEl 5 S45 314 1 SIGN MOUNTING HARDWARE 2 113 005LKE 1 PIPE 1 IPS 8 12 158A 1 PULL ROD 809mm LONG 3 189 723 1 90 STREET ELBOW 1 IPS r 204 421 1 EMERGENCY TAG 4 S24 084E 1 STN STL SHOWERHEAD ASSY 8 114 05OE 1 SAFETY SIGN 4A 187 053 1 SHOWERHEAD SHELL 9 153 298 1 BSP ADAP...