Care and cleaning.

If the water heater is to remain idle for an extended period of 

time, the power and water to the appliance should be turned 

off and the water heater drained to conserve energy and 

prevent a buildup of dangerous hydrogen gas. This unit has 

no power button, power can only be shut off at the circuit 

breaker or disconnect switch.
If the water heater has an anode depletion sensing feature 

(some models) and the water heater cannot be drained, it is 

recommended to leave the power turned on with the water 

heater in vacation mode to ensure that the feature will 

continue to operate properly while still conserving energy.

The water heater and piping should be drained if they might 

be subjected to freezing temperatures.
After a long shutdown period, the water heater’s operation 

and controls should be checked by qualified service 

personnel. Make certain the water heater is completely filled 

again before placing it in operation.

NOTE: Refer to the Hydrogen Gas Caution in the Operating 

Instructions (see page 3).

DRAINING THE WATER HEATER

CAUTION:

 Risk of Shock - 

Shut off power to 

the water heater before draining water.

DANGER:

 Risk of Scald - 

Before manually 

operating the relief valve, make certain no one will be exposed 

to the hot water released by the valve. The water drained from 

the tank may be hot enough to present a scald hazard and 

should be directed to a suitable drain to prevent injury or 

damage.

To drain the water heater, follow these steps:

1. Attach a garden hose to the drain valve located at the 

bottom of the unit and direct that hose to a drain. 

2. Turn off the cold water supply.

3. Admit air to the tank by opening a hot water faucet or 

lifting the handle on the relief valve

4. Open the drain valve with a flat screwdriver.
Note: See page 15 for product schematic.

EXTENDED SHUTDOWN PERIODS OR VACATIONS EXCEEDING VACATION MODE OPTIONS

Use a flat slot 

screwdriver to 

turn valve.

CLEARING THE CONDENSATION DRAIN TUBE

CLEANING THE FILTER

In the Hybrid, Heat Pump and High Demand/Boost modes, the heater 

moves air through the system and out the back of the unit. The filter 

is in place to protect the evaporator from dirt and dust. 
A clean air filter is important to get the highest efficiency. Occasion-

ally this filter will need to be cleaned (minimum once per year). When 

the filter requires cleaning, the Red light above the Filter button will be 

illuminated and an audible beep will sound. 

NOTE:

 If the filter gets too dirty, the unit will automatically switch to 

Electric/Standard mode and energy savings will be lost.
Leave the power on.  Remove the filter from  

the top of the unit. Squeeze two tabs and lift to remove the air filter. 

Once it has been removed, the filter can be vacuumed or wiped clean 

with a damp cloth or rinsed with warm water.
Once the filter has been cleaned and dried, it can be replaced by 

aligning it into the slots in the top of the unit and pushing it down into 

place. 

After the clean filter has been reinstalled, press and hold the 

FILTER

 

button.  If a heating cycle is on when the filter fault is reset, it will con-

tinue in electric mode to finish the cycle.  After that, it will automati-

cally revert to the mode it was in prior to being switched.

IMPORTANT:

 Filter must be cleaned when the alarm is displayed. A 

dirty filter will make the system work harder and result in a reduction 

of efficiency and possible damage to the system. In order to get the 

best energy efficiency available, make sure your filter is clean.

The main drain is intended to carry all condensate away.  If it is 

clogged, the heat pump will stop operating, the display will show 

F20, and an alarm will sound.  Press any button to silence the 

alarm, then clear the condensate drain by removing any drain 

lines and connections, and clearing debris. Reattach drain lines 

and connections, then allow the water heater to run.
Periodically inspect the drain lines and clear any debris that may 

have collected in the lines.

See Installation 

Instructions for 

more information.

Main drain line

Direct the 

main drain 

tube into a 

drain

Overflow

Filter

Tabs

Slots

Summary of Contents for RE2H50S*-1NCWT Series

Page 1: ...mmended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance connected to the hot water system If hydrogen is present there will be an unus...

Page 2: ...igated by a qualified service technician and corrective action must be taken before placing the water heater in service again To reset the temperature limiting control 1 Turn off the power to the wate...

Page 3: ...ybrid mode operation at a temperature setting of 135 F 57 C Electric Only Mode This mode uses only the upper and lower heating resistance elements to heat the water stopping the cool air discharge dur...

Page 4: ...ION DRAIN TUBE CLEANING THE FILTER In the Hybrid Heat Pump and High Demand Boost modes the heater moves air through the system and out the back of the unit The filter is in place to protect the evapor...

Page 5: ...a device that periodically cuts power to the water heater the accuracy of the anode rod depletion sensing feature may become compromised and anode rod inspection every 2 3 years is recommended If the...

Page 6: ...interfere with the removal of the filter If a separate ducting kit is purchased additional space is required above and to the rear of the water heater for installation Consult the ducting kit manual f...

Page 7: ...ief valves The BTUH rating of the relief valve must not be less than the input rating of the water heater as indicated on the rating label located on the front of the heater 1 watt 3 412 BTUH Connect...

Page 8: ...lting from the use of such unauthorized devices If local codes require external application of insulation blanket kits the manufacturer s instructions included with the kit must be carefully followed...

Page 9: ...lean the heating elements This should only be done by a qualified service personnel The heater is beeping and the display says F11 The water heater has not been filled with water before power ing up P...

Page 10: ...10 Notes...

Page 11: ...chauffe un incendie une inondation ou des dommages physiques B Ne rallumez pas le chauffe eau s il n est pas rempli pas d eau C Ne rallumez pas le chauffe eau si le robinet d alimentation d eau froide...

Page 12: ...avant la remise en service du chauffe eau Pour r initialiser la commande de limitation de temp rature 1 Coupez l alimentation lectrique du chauffe eau 2 Retirez le s panneau x d acc s et l isolation...

Page 13: ...d pourvues de portes persiennes tel qu indiqu dans les instructions d installation REMARQUE Le rendement de l appareil la consommation et les conomies d nergie selon le Guide de l nergie valent pour...

Page 14: ...e eau d place l air dans le syst me et le fait ressortir l arri re de l appareil Le filtre est en place pour prot ger l vapora teur de la salet et la poussi re Un filtre air propre est n cessaire pour...

Page 15: ...e tige d anode peut tre compromise et nous recommandons d inspecter la tige d anode chaque 2 ou 3 ans Si le chauffe eau est inactif pendant une longue p riode de temps et qu il ne peut pas tre vidang...

Page 16: ...et l arri re du chauffe eau a in de pouvoir installer La trousse de r partition d air sera achet e et un espace additionnel est requis au dessus et l arri re du chauffe eau a in de pouvoir l installer...

Page 17: ...a valeur nominale d entr e du chauffe eau comme ceci est inscrit sur l tiquette l avant du chauffe eau 1 watt 3 412 Btu h Branchez la sortie de la soupape de s curit une bonde ouverte de telle fa on q...

Page 18: ...et le chauffe eau ne fournit pas une conduction suffisante pour une masse ad quate La tuyauterie non m tallique les raccords di lectriques ou flexibles etc peuvent isoler lectriquement le chauffe eau...

Page 19: ...eau tableau N E C 310 16 167 F 75 C 208V 240V 277V 480V 3 000 12 12 14 14 4 000 10 10 12 14 4 500 10 10 10 14 5 000 10 10 10 14 5 500 8 10 10 14 6 000 8 8 10 12 8 000 8 8 8 10 9 000 8 8 10 10 000 8 10...

Page 20: ...vec de l eau Appuyer sur ENTER pour teindre l alarme puis alimenter le cycle lorsque le r servoir a t rempli Si le r servoir plein d eau a t confirm et que le code F11 appara t il est possible que le...

Page 21: ...Remarques 21...

Page 22: ...ado en su totalidad por personal calificado del servicio t cnico Precauciones de Seguridad A Apague el suministro de energ a del calentador de agua si ste sufri un sobrecalentamiento incendio inundaci...

Page 23: ...ratura alta deber ser investigada por un t cnico calificado del servicio o se deber realizar una acci n correctiva antes de volver a poner en uso el calentador de agua Para reiniciar el control de l m...

Page 24: ...n puertas de celos a como se especifica en las instrucciones de instalaci n NOTA Tanto el rendimiento de Energy Guide Gu a de Uso de Energ a como el consumo y el ahorro de energ a est n basados en ins...

Page 25: ...brido Heat Pump only Bomba de Calentami ento solamente y High Demand Boost Alta Demanda Incrementar el calentador mueve aire a trav s del sistema y hacia afuera por la parte trasera de la unidad El fi...

Page 26: ...varilla del nodo cada 2 o 3 a os Si el calentador de agua estar inactivo por un per odo de tiempo prolongado y el calentador de agua no puede ser drenado se recomienda dejar activado el encendido con...

Page 27: ...compra un kit de tuber as de aparte se requerir espacio adicional en la parte superior y trasera del calentador de agua para la instalaci n Para acceder a instrucciones espec ficas consulte el manual...

Page 28: ...do purgado del sistema V LVULA DE ALIVIO ADVERTENCIA Riesgo de da o sobre la unidad El ndice de presi n de la v lvula de alivio no debe superar los 150 PSI 1 03 kPa la m xima presi n de funcionamiento...

Page 29: ...dos para uso como conductor de conexi n a tierra incluir n un conductor separado para la conexi n a tierra Deber a estar adjunto a las terminales de conexi n a tierra del calentador de agua y la caja...

Page 30: ...ressor turns on The water heater is operat ing in Hybrid mode Quick ly provides initial amount of hot water then switches to efficient heat pump for majority of heating 30 Soluci n de Problemas Antes...

Page 31: ...Encendido por Ciclos cuando el tanque haya sido llenado Si la unidad fue confirmada para su llenado con agua y se experimenta un c digo F11 es posible que el c digo sea una falsa indicaci n debido a c...

Page 32: ...Notas 32...

Reviews: