9
Venting continued-
Canadian Installations
1
US Installations
2
A=
Clearance above grade,
veranda, porch, deck or
balcony
12 inches
(30 cm)
12 inches
(30 cm)
B=
Clearance to window or
door that may be
opened
6 in. (15 cm) for appliances
≤ 10,000 Btuh (3 kW), 12 in.
(30
cm) for appliances > 10,000
Btuh (3 kW) and
≤100,000 Btuh
(30 kW), 36 in. (91 cm) for
appliances >100,000 Btuh
(30 kW))
4 ft (1.2 m) below or to
side of opening; 1 ft (300
mm) above opening
C=
Clearance to
permanently closed
window
*b
*b
D=
Vertical clearance to
ventilated soffit located
above the terminal
within a horizontal
distance of 2 feet
(.6 m)
from the center line of
the terminal
*b
*b
E=
Clearance to
unventilated soffit
*b
*b
F=
Clearance to outside
corner
*b
*b
G=
Clearance to inside
corner
*b
*b
H=
Clearance to each side
of center line extended
above meter/regulator
assembly
3 feet
(.9 m)
within a height
15 feet (
4.6 m
) above the
meter/regulator assembly
*b
I=
Clearance to service
regulator vent outlet or
oil tank vent
3 feet
(.9 m
)
*b
J=
Clearance to non-
mechanical air supply
inlet to building or the
combustion air inlet to
any other appliance
12 inches
(
30 cm
)
4 feet (
1.2m
) below or to
side of opening;
12 inches (
30 cm
) above
opening.
K=
Clearance to a
mechanical air supply
inlet
6 feet
(
1.83 m
)
3 feet (
91 cm
) above if
within 10 feet horizontally
L=
Clearance above paved
sidewalk or paved
driveway located on
public property
7 feet
(
2.13 m
)†
7 feet
(
2.13 m
)†
M=
Clearance under a
veranda, porch, deck, or
balcony
12 inches
(
30 cm
) ‡
*b
1
In accordance with the current CAN/CGA-B149
Installation Codes
.
2
In accordance with the current ANSI Z223.1-(Latest edition)/NFPA 54
National Fuel Gas Code
.
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single-family
dwellings and serves both dwellings.
‡ Permitted only if a veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.
*a) A minimum clearance value determined by testing in accordance with section 2.20.
*b) “Clearance in accordance with local installation codes and the requirements of the gas supplier”.
This water heater has a certified category III, per latest ANSI Z 21.10.3-
2015.CSA 4.3-2015 revision. Refer to the latest edition of the National Fuel
Gas Code (ANSI Z223.1-latest edition), or in Canada, the Natural Gas and
Propane installation Code (B149.1-00 latest edition).