The Brute Elite 125

  

INSTALLATION STANDARDS

 

MATERIAL 

UNITED STATES 

CANADA

 

Stainless Steel 

UL 1738 

Venting must be ULC-S636 certified for use as

 

PVC, sch 40 

ANSI/ASTM D178 

venting material. The venting material must be chosen

 

CPVC, sch 40 

ANSI/ASTM F441 

based upon the intended application of the boiler.

Table 5. Required Exhaust Vent Material.

shall also be supplied for ventilation, including air 

required for comfort and proper working conditions for 

personnel.

3.2  Venting (Exhaust)

 WARNING

Failure to use the appropriate vent material, installation 

techniques, glues/sealants could lead to vent failure 

causing property damage, personal injury or death.

 WARNING

All venting must be installed according to this manual 

and any other applicable local codes, including but 

not limited to, ANSI Z223.1/NFPA 54, CSA B149.1, 

CSAB149.2 and ULC-S636. Failure to follow this manual 

and applicable codes may lead to property damage, 

severe injury, or death.

The flue temperature of the Brute Elite changes 

dramatically with changes in operating water 

temperature. Therefore, it is necessary to assess the 

application of the boiler to determine the required 

certified vent class. If the Brute Elite is installed in 

an application where the ambient temperature is 

elevated, and/or installed in a closet/alcove, CPVC 

or stainless steel material is required. If the system 

temperatures are unknown at the time of installation, 

stainless or CPVC material is recommended.

The Brute Elite is a Category IV appliance and 

may be installed with PVC and CPVC that complies 

with ANSI/ASTM D1785 F441, or a stainless steel 

venting system that complies with UL 1738 Standard 

(see 

Table 5

). 

INSTALLATIONS IN CANADA

 require the use 

of venting material certified to ULCS636. All Gas 

vents connected to the Brute Elite, plastic, stainless 

steel or otherwise must be certified to this ULC 

standard. Appropriate selection of vent material is 

very important for  proper performance and safe 

operation of the Brute Elite.

The flue temperature of the Brute Elite changes 

dramatically with changes in operating water 

temperature. Therefore, it is necessary to assess the 

application of the boiler to determine the required 

certified vent class. If the Brute Elite is installed in 

an application where the outlet water temperature 

exceeds 145°F, and/or installed in a closet, class IIB 

or higher vent material is required. If the system 

temperatures are unknown at the time of installation, 

class IIB or higher venting material is recommended.

IN CANADA

 all venting used must meet the 

following requirements:

1.  ULC-S636 certified and marked

2.   The first 3 feet of venting must be accessible for 

visual inspection.

3.  All components used in the vent system must be 

from a certified manufacturer.

4 .  Vent system components must not be mixed 

with alternate manufacturers certified 

components and/or unlisted components.

5 .  The venting must be installed according to the 

vent manufacturers installation instructions. 

 

The unit’s vent can terminate through the roof, or 

through an outside wall.

See 

Table 2

 to select the appropriate vent pipe 

diameter. Vent pipe must pitch upward, toward the vent 

terminal, not less than 1/4" per foot, so that condensate 

will run back to the Brute Elite to drain. Route vent 

pipe to the heater as directly as possible. Seal all 

joints and provide adequate hangers as required in the 

venting system manufacturer’s Installation Instructions. 

Horizontal portions of the venting system must be 

supported to prevent sagging and may not have any low 

sections that could trap condensate. The unit must not 

support the weight of the vent pipe. Please see 

Table 2

 

for proper diameter vs. length allowed.

Figure 7. Combustion Air and Vent Through Roof.

Summary of Contents for brute elite 125 BLMH

Page 1: ...gases which could cause serious injury property damage or death Improper installation and or operation will void the warranty AVERTISSEMENT Assurez vous de bien suivres les instructions donn es dans c...

Page 2: ...Pump Capacity 15 SECTION 6 Water Connections 6 1 Central Heat System Piping 15 6 2 Cold Water Make Up 15 6 3 Freeze Protection 16 6 4 Suggested Piping Schematics 17 6 5 Recognized Chemicals 17 6 6 Dom...

Page 3: ...t Up 30 10 2 1 Burner Operation 30 10 2 2 Boiler Setup and Adjustment 31 10 2 3 Manifold Pressure Check 31 10 3 Shutting Down Brute Elite 31 10 4 To Restart Brute Elite 31 SECTION 11 Maintenance 11 1...

Page 4: ...cal codes Where required by the authority having jurisdiction the installation of Brute Elite boilers must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers ANSI...

Page 5: ...es are covered by a limited warranty The owner should complete the warranty registration at www BradfordWhite com All warranty claims must be made to an authorized Bradford White Corp representative C...

Page 6: ...g Package 1 PRV 30 PSI 5 Exhaust terminal assy 2 PRV Pipe w washer 6 Air intake terminal assy 3 Wall attach bracket 7 Ball valve 4 Outdoor sensor 8 System sensor not shown 9 Flow restrictor not shown...

Page 7: ...e 125 Figure 3 Dimensional Drawing Cond Hydronic DHW 2nd Gas Hydronic DHW 2nd Outlet Return Inlet Return Supply Supply Outlet Supply 3 4 3 4 1 2 3 4 1 2 3 4 1 2 3 4 PVC copper NPT copper NPT NPT NPT c...

Page 8: ...choosing the locations for the appliance 2 2 Locating Appliance for Correct Vent Distance from Outside Wall or Roof Termination The forced draft combustion air blower in the appliance has sufficient...

Page 9: ...ons require minimum air ventilation see Section 3 Note Brute Elite bracket and wall bracket are purposely offset Brute Elite NOTE Brute Elite models include 16 on center mounting holes on upper rear o...

Page 10: ...de adequate hangers The unit must not support the weight of the combustion air intake pipe Maximum linear pipe length allowed is shown in Table 2 Subtract 5 allowable linear ft 1 5m for every elbow us...

Page 11: ...connected to the Brute Elite plastic stainless steel or otherwise must be certified to this ULC standard Appropriate selection of vent material is very important for proper performance and safe operat...

Page 12: ...tee the same diameter as the vent pipe may be used The tee d vent termination offers greater protection from wind related operating issues 3 3 2 Side Wall Combustion Air Terminal The Bradford White si...

Page 13: ...91 cm J Clearance to nonmechanical air supply Direct vent only 12 30cm 80 285 36 91cm inlet to building or the combustion air inlet 399 850 Other than Direct vent 4 ft 1 2m below 36 inches 91 cm to a...

Page 14: ...xterior of the building at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for horizontally vented gas fueled heating appliance or equipment The sign shall...

Page 15: ...ting system properly vents when tested as outlined above return doors windows exhaust fans fireplace dampers and any other gas burning appliance to their previous conditions of use 7 Any improper oper...

Page 16: ...g plate Brute Elite will function properly without the use of high altitude modification at elevations up to 10 000 feet 3050 m 2 The maximum inlet gas pressure must not exceed 13 W C 3 2kPa The minim...

Page 17: ...ic separator The pump is sized for a maximum of 30 feet 9 1m of piping and the headloss of the boiler only For custom configurations the available pump head is provided in Figure 11 The system designe...

Page 18: ...ands which may result in bursting of pipes or damage to the boiler which could result in leaking or flooding conditions Do not use automotive antifreeze or ethylene glycol To help prevent freezing Bra...

Page 19: ...nt is made via aquastat located on the indirect water heater or can be controlled at the boiler via a remote sensor 6 7 Condensate Drain A condensate drain trap is built into the Brute Elite Connect a...

Page 20: ...33 31 28 Table 8 DHW and Pump Performance Data Caution Scalding Risk Bradford White recommends the use of a thermostatic mixing valve at domestic hot water outlet boiler location to reduce potential f...

Page 21: ...Page 19 The Brute Elite 125 Figure 16 Hydronic Piping Multi boilers for large homes with long multiple baseboard zones Installer to provide DHW anti scald thermostatic mixing valve...

Page 22: ...Page 20 Bradford White Corp Figure 17 Hydronic Piping Multi boilers for large homes with long multiple radiant zones Installer to provide DHW anti scald thermostatic mixing valve...

Page 23: ...Page 21 The Brute Elite 125 Figure 18 Hydronic Piping Heating zones piped with zone pumps Installer to provide DHW anti scald thermostatic mixing valve...

Page 24: ...Page 22 Bradford White Corp Figure 19 Hydronic Piping Heating zones piped with zone valves Installer to provide DHW anti scald thermostatic mixing valve...

Page 25: ...am s 7 1 Main Power Plug power cord into a non switched 115V electrical outlet with 15A circuit protection FLA is 2A There is an internal 10A breaker to protect internal system components 7 2 Pump Con...

Page 26: ...ons are wired d Repeat the above steps for Modbus port 1 terminal B and C connections to complete the wiring e Connect the drain wire from the twisted pair wire to ground on one end of the wire only 7...

Page 27: ...4 5 4 5 6 6 1 2 3 Y J8B 1 TERM STRIP R G BK 1 3 1 4 2 5 6 BK BK BR BL 1 6 5 4 3 2 J4B Y DRY CONTACT 7A GR R C OPTIONAL R20729 O BLOCKED VENT SWITCH COM NC POWER PLUG 115V BLOWER 3 1 5 1 G POWER SWITC...

Page 28: ...r reset HOD High outdoor temperature setpoint LOD Low outdoor temperature setpoint RMT Add Used for Lead Lag follow menus LL Lead Lag enable disable enables menu items HS Hysteresis temp range between...

Page 29: ...ack temperature is a dual thermistor sensor and is limit rated The control compares each of the temperature readings to determine accuracy The stack sensor is used as a limiting feature to avoid exces...

Page 30: ...door air temperature reaches the low outdoor temperature setpoint LOD the control setpoint is adjusted to the CH Outlet water setpoint temperature HOD LOD and LBT can be adjusted by accessing SETUP mo...

Page 31: ...ly drop their firing rate If when reaching the point where both boilers drop toward their minimum firing rate 20 then the first slave will drop out Slave1 will remain unavailable until its ASC timer h...

Page 32: ...art Up Shut Down Instruction Decal located on the back of the Top Front Cover and turn on gas and electrical power to appliance SECTION 10 Set Up Instructions 10 1 Filling the Boiler System 1 Ensure t...

Page 33: ...forced rate menu CO2 readings should be between the range shown in Table 13 If the CO2 is not within the range shown adjustments may be made To adjust the low fire CO2 locate the low fire adjuster scr...

Page 34: ...Propane 9 8 __ 10 8 3 5 __ 4 5 Table 13 CO2 Range and Pressure Settings Figure 25 Adjustment Screws and Settings for CO2 Manifold Pressure Screw under cap High fire setting Propane Gas Orifice O Ring...

Page 35: ...e blower arm assembly to access the burner Remove the 4 bolts connecting the blower to the arm see Figure 32 Remove the 5 bolts which hold the burner arm in place Pull burner up and out Clean burner i...

Page 36: ...xchanger 1 Shut off the 120 Volt power supply to the boiler 2 Turn off all manual gas valves connecting the boiler to the main gas supply line 3 Remove the four bolts connecting the blower flange to t...

Page 37: ...15 Start boiler per lighting procedure shown on inside front cover or side of appliance 16 Check for Gas Leaks at gas valve pipe 17 With a combustion analyzer check CO2 and CO levels at both maximum...

Page 38: ...DHW sensor fault Faulty sensor or wiring Check wiring replace sensor condition can be 95 Stack sensor fault caused by short 96 OAT temperature sensor fault Faulty outdoor air Check wiring and sensor...

Page 39: ...ence greater than 22 F 12 C 255 CH setpoint minus ODR Increase Outdoor water min water temperature was temperature min and max too small min 12 C 22 F values to a difference greater Increase setpoint...

Page 40: ...ement parts 13 1 General Information To order or purchase parts for the Bradford White Brute Elite contact your nearest Bradford White dealer or distributor If they cannot supply you with what you nee...

Page 41: ...E2337500 8O Exchanger heat plate 8P Tie cable 14 3 4 long x 0 31 wide heat stabilized F2029100 8Q Flow switch water E2337400 8R Pipe tailpiece 1 npt M x 3 4 tube cu 12H4023 8S O ring 120 1 ID x 1 3 16...

Page 42: ...Page 40 Bradford White Corp Figure 28 Panel Assembly Door Top...

Page 43: ...Page 41 The Brute Elite 125 Figure 29 Panel Assembly Door Middle...

Page 44: ...Page 42 Bradford White Corp Figure 30 Panel Assembly Door Bottom...

Page 45: ...Page 43 The Brute Elite 125 Figure 31 Base Jacket Assembly...

Page 46: ...Page 44 Bradford White Corp Figure 32 Heat Exchanger Cabinet Fan...

Page 47: ...Page 45 The Brute Elite 125 Figure 33 Heat Exchanger Burner Components...

Page 48: ...Page 46 Bradford White Corp Figure 34 Pump Assembly Components...

Page 49: ...Page 47 The Brute Elite 125 Figure 35 Plumbing Components...

Page 50: ...Page 48 Bradford White Corp...

Page 51: ...Page 49 The Brute Elite 125...

Page 52: ...nge without notice in accordance with our policy of continuous product improvement Ambler PA 19002 Tech Service 800 334 3393 Service Parts 800 538 2020 www BradfordWhite com Warranty Service 800 531 2...

Reviews: