Brute Magnum
Page 41
shutoff valve. Remove the front and right-side panels
from the unit. Disconnect the union between the valve
body and the blower.
Label the four pressure tubes
that are connected to the valve actuator, to ensure
that they will be replaced correctly.
Remove the
valve actuator, per the instructions above. Unscrew
the valve body from the gas train. After the valve has
been removed, replace with a new valve in the reverse
order. Turn on gas shutoff valve and 120 volt power
and check appliance operation and tightness of gas
valve connections.
7.2.4 Safety Gas Valve
The safety gas valve is a 24-volt diaphragm
valve. It is designed to operate with supply pressures
of 4-13 inches w.c. (1.0 to 3.2 kPa). To remove the gas
valve, shut off 120-volt power. Shut off the main gas
supply to the unit. Disconnect the gas supply piping
from the back of the unit. Disconnect the electrical
wires from the valve, and unscrew the gas valve from
the gas train. Re-assemble in reverse order. A bleed
line from the diaphragm type automatic valve shall be
vented per local code requirements.
7.2.5 Manual Reset High Limit Control
The high limit switch is manual reset switch with
an adjustable set point, up to 240°F (116°C) on boiler
models and 200°F (93°C) water heater models. To
replace the switch, shut off the 120-volt power to the
appliance. Remove the cover from the switch to access
the mounting screws. Remove the screws, and pull the
switch off the control panel. Replace in reverse order.
7.2.6 Temperature
Control
The temperature control consists of an adjustable
electronic control and digital display module. To
replace the control or the display, shut off the 120-
volt power to the appliance. Remove the cover from
the control panel, and remove the screws from the
DIN rail clip, to which the controls are mounted. Pull
the electrical connector from the controller. Slide the
controllers from the DIN rail clip. Replace in reverse
order.
7.2.7 Auto Reset Temperature Limit
The auto reset temperature limit has a 200°F
(93°C) setting. The is mounted directly onto the Brute
Magnum header, on the inlet to the copper coil. It
senses the inlet water temperature to copper coil, and
guards against a malfunctioning mixing system. To
replace the switch, shut off the 120-volt power to the
appliance. Remove the cover from the switch to access
the mounting screws. Remove the screws, and pull the
switch off the control panel. Replace in reverse order.
7.2.8 Mixing
Control
The FX05 mixing control is the device that
controls the position of the mixing valve system. This
control is factory set, and must not be adjusted, except
for the °F or °C choice. To remove the control, unplug
the wires from the back, push on the tabs to slide the
clasping mechanism off, and pull the controller out
through the front of the panel. Replace in reverse order.
7.2.9 Mixing
Valves
There are two 2-way mixing valves that are
linked and connected to a valve actuator to create the
3-way mixing system. To remove the upper right
valve, remove the actuator and then remove the 2 bolts
that connect the sheet metal to the valve. Remove the
linkage from the arm that is welded to the actuator.
Remove the four bolts on the valve, and slide the
valve out. To remove the lower left valve, remove
the 2 bolts that connect the sheet metal to the valve.
Remove the linkage from the arm that is welded to the
actuator. Remove the four bolts on the valve, and slide
the valve out. Reassemble in reverse order.
Figure 29. Control Panel.
Summary of Contents for BRHHH
Page 2: ...BRADFORD WHITE CORP Page 2...
Page 20: ...BRADFORD WHITE CORP Page 20 Figure 8 Water Heater Piping One Heater One Tank...
Page 21: ...Brute Magnum Page 21 Figure 9 Water Heater Piping Multiple Heaters One Tank...
Page 22: ...BRADFORD WHITE CORP Page 22 Figure 10 Water Heater Piping One Heater Multiple Tanks...
Page 23: ...Brute Magnum Page 23 Figure 11 Water Heater Piping Multiple Heaters Multiple Tanks...
Page 30: ...BRADFORD WHITE CORP Page 30 Figure 17 Wiring Diagram Size 1200 Standard and Codes A and F...
Page 32: ...BRADFORD WHITE CORP Page 32 Figure 19 Wiring Diagram Size 1200 Code B...
Page 33: ...Brute Magnum Page 33 Figure 20 Wiring Diagram Sizes 1600 2000 and 2400 Code B...
Page 39: ...Brute Magnum Page 39 Figure 27 Gas Trains...
Page 49: ...Brute Magnum Page 49 Figure 30 Combustion Components...
Page 50: ...BRADFORD WHITE CORP Page 50 Figure 31 Gas Train Combustion Air Components...
Page 51: ...Brute Magnum Page 51 Figure 32 Gas Train Components...
Page 52: ...BRADFORD WHITE CORP Page 52 Figure 33 Electrical Components...
Page 53: ...Brute Magnum Page 53 Figure 34 Heat Exchanger Water Path Components...
Page 54: ...BRADFORD WHITE CORP Page 54 Figure 35 Heat Exchanger Water Path Components...
Page 55: ...Brute Magnum Page 55 Figure 36 Jacket Components...