POWER SUPPLIER 
XA/300LR

Power supply and control unit, with
ECHELON bus, enables standard and
residential system 300 installations to
be created.
Enables conversations between entry
panels, receivers and porter switch-
board.
It manages service controls (entry panel
self-connection/selection, door-lock
release, stair light, auxiliary control/por-
ter call) as well as the engaged status.
For data lines to the block’s entry
panels and/or main entrance panels,
the unit communicates by means of
the LON TALK protocol, whilst it uses a
BPT X2 TECHNOLOGY protocol
towards the receivers. 
The bus connection towards the entry
panels consists of 3 twisted pairs plus
the power supply, whilst it uses a sin-
gle twisted pair plus power supply
towards the receivers.
The unit features a 

CNV

connector for

connection to the XAV/300 video
modulator and a 

CNS

connector for

connection to the ICB/300 selector.
The system 300 can be programmed
in either of two ways:

Standard mode

(installation with a

single XA/300LR power supplier) by
means of the actual XA/300LR sup-
plier;

Extended mode

(installation with a

number of XA/300LR power suppliers,
or if the standard configuration is to be
extended) by means of a PCS/300 or
MPP/300LR unit.

SYSTEM SETUP 
WITH STANDARD MODE 
PROGRAMMING 
AND DEFAULT SETTINGS

System setup

1 -

Maximum number of XA/300LR: 1.

2 -

Maximum number of X2 blocks: 64.

3 -

Maximum number of entry panels

per X2 block: 4.

4 -

Maximum number of system 300

entry panels (19 with IPD/300LR).

5 -

Maximum number of IPD/300LR

porter switchboards: 1.

6 -

Maximum number of users con-

nected directly on XA/300LR: 100 (0 if
X2 blocks are present).

7 -

Maximum number of users for X2

block: 100 (99 with IPD/300LR porter
switchboard).

8 -

Maximum number of IOD/303LR

relay actuators: 1.

Default settings

1 -

System activation time: call 30 s,

conversation max 60 s.

2 -

Door-lock release activation time: 

- for the system 300 entry panel (with
ICP/LR) with pushbuttons, time
options are: 1 s, 4 s, 8 s and 16 s;
- for the HAC/300LR entry panel: adju-
stable from 1 s to 255 s;
- for the X2 entry panel: adjustable
from 1 s to 15 s;

3 -

Aux. 1 control and door-lock relea-

se only enabled when receiver is cal-
led.

4 -

Self-connection and switching

between entry panels for X2 block
panels only.

5 -

First key on all system 300 and X2

entry panels allocated automatically as
porter call key.

SYSTEM FEATURES 
WITH EXTENDED MODE 
PROGRAMMING

In this mode, system features can be
extended to enable more complex,
flexible and customizable solutions.
Below are just some of the options:
- extending the number of entry panels
and receivers per block;
- personalizzazione tempo di attivazio-
ne impianto e durata chiamata;
- programming all receivers using a
programmer (in this case, you will need
to collect the ID codes and enter them
in the tables that come with the pro-
gramming devices);
- texts can be customized for naming
entry panels and users.

STANDARD 
PROGRAMMING

Programming structures the system by
allocating a unique identification code
to all LON units (for example, ICP/LR,
HAC/300LR, IPD/300LR) and X2 units
(for example, receivers and X2 block
entry panels such as HEV/301,
HEC/301, etc.).
Programming is divided into two parts:
- receivers programming
- entry panels and accessories pro-
gramming.

ENTERING AND EXITING 
STANDARD PROGRAMMING

To gain access to programming, it is
necessary to press the SERVICE but-
ton.
You can access programming by pro-
ceeding as follows.

1 - Programming receivers.

Press the SERVICE button for at least 3
s;

the yellow LED flashes at regular inter-
vals.

2 - Programming entry panels.

Press the SERVICE button again for
another 3 s; 

the yellow LED stays on.

3 - Exiting programming and auto-
matic programming of IPD/300LR
and IOD/300LR units, where applica-
ble.

Lastly, press the SERVICE button for
approx. 1 s;

the yellow LED goes off.

PROGRAMMING

Power up the XA/300LR unit and pro-
ceed as follows.

WARNING. If the installation featu-
res more than one system 300
entry panel (ICP/LR o HAC/300LR),
or if you are dealing with an X2

1

XA/300LR US

R4

03.2009/2407-2101

1

2

3

C

A

LED SERVICE

CNV

B

CNS

L

A

B

+

+

SW2

RJ45

L

N

43,5

4

5

7,5

57

210

1

0

6

A

B

64,5

210

1

4

5

BPT S.p.A.
Via Cornia, 1
33079 Sesto al Reghena-PN-Italy
[email protected]  –  www.bpt.it

NOTE:

This equipment has been tested and found to com-

ply with the limits for a Class B digital device, pursuant to Part
15 of the FCC Rules. These limits are designed to provide

reasonable protection against harmful interference in a residential instal-
lation.
This equipment generates, uses and can radiate radio frequency energy
and, if not installed and used in accordance with the instructions, may
cause harmful interference to radio communications. However, there is
no guarantee that interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or
more of the following measures:
- Reorient or relocate the receiving antenna. 
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.

EN

INSTALLATION 
INSTRUCTIONS

DIMENSIONS IN MILLIMETRES

DIMENSIONES EN MILIMETROS

 

Summary of Contents for XA/300LR

Page 1: ...s per block personalizzazione tempo di attivazio ne impianto e durata chiamata programming all receivers using a programmer in this case you will need to collect the ID codes and enter them in the tab...

Page 2: ...erations in point 2 2 or 2 3 using call buttons n 2 3 and 4 respectively 2 3 Repeat the procedure in 2 2 for the remaining entry panels in the order in which the entry panels are to be scanned Once th...

Page 3: ...audio video panel Wait for audible confirmation 2 Then press call button n 10 posi tion 2E to set the total number of user calls used 10 Wait for audible confirmation WARNING If there is a porter swit...

Page 4: ...a tecla de todas las placas exteriores 300 y X2 como llamada conserje CARACTER STICAS DE LAS INSTALACI N CON PROGRAMACI N EN MODO AMPLIADO En esta modalidad es posible ampliar las caracter sticas de l...

Page 5: ...a programaci n Placas exteriores de bloque X2 HEV 301 HEC 301 AZV 304 etc fig 3 ATENCI N La programaci n de las placas exteriores de bloque X2 ser posible s lo con los aparatos versi n 3 0 o sucesivas...

Page 6: ...ster la conectada con el unidad de control XA 300LR del blo que X2 4 3 Esperar la confirmaci n ac stica El n mero de notas ac sticas es igual que el n mero total de placas exterio res X2 conectadas co...

Page 7: ...os conectables sobre la l nea X2 B 100 videointercomunicacions 200 telefonos Derivados internos activables con la misma llamada 3 8 con por lo menos 6 derivados con nota atenua da Temperatura de funci...

Page 8: ...DIOINTERCOMUNICACION pag 11 15 VIDEOINTERCOMUNICACION pag 16 31 0 28 1 2 5 30 30 100 100 250 Cross section of the supply line wires Secci n de los conductores de la l nea de alimentaci n Distance Dist...

Page 9: ...nductores correspondientes a los cableados CN2 CN3 para las conexiones de la interfaz HIA 300 a las unidades insta ladas en la placa exterior HPV 1 y HPC 1 ATENCI N El conductor de conexi n var a en f...

Page 10: ...AE ICP LR MC 304 L CBO CBO MC 304 CBI CBO CBI 12 Fig 12 13 Connection diagram of auxiliary door lock release button AE Fig 12 13 Esquema de conexi n del pulsador auxiliar abrepuerta AE AE ICP LR L CBO...

Page 11: ...5 21 8 11 12 14 1 CBI CN1 HEP 306 HEP 312D CN3 CN2 HIA 300 A V OUT V IN 3 4 CB CBO CBO 0 1 2 3 4 SW3 4 2 3 G V S B A N M R C G 5 21 SW1 NC 321 CP B M1 3 120 120 L N CP Personal door bell button Pulsad...

Page 12: ...W1 B M1 SW1 YC 300 YC 300A YC 300 YC 300A SW1 NC 321 CP B M1 5 SE 300C02 2 UL MULTI FLAT AUDIO ENTRY INSTAL LATION WITH 2 ENTRANCES EQUIPO DE AUDIOINTERCOMUNI CACION MULTIFAMILIAR CON 2 ENTRADAS SE 30...

Page 13: ...CBO CBO MC 304 CBI CBO ICP LR L 12V 2 1 C XA 300LR B A A L CNV B CNS HPC 1 HA 200 HIA 300 ICP LR KHPS KHPD HTS KHSO HEP 306 HEP 312D HA 200 5 21 8 11 12 14 1 CBI CN1 HEP 306 HEP 312D CN3 CN2 CBI CBO 2...

Page 14: ...W1 B M1 SW1 YC 300 YC 300A YC 300 YC 300A SW1 NC 321 CP B M1 5 SE 300C03 2 UL MULTI FLAT AUDIO ENTRY INSTAL LATION WITH 3 ENTRANCES EQUIPO DE AUDIOINTERCOMUNI CACION MULTIFAMILIAR CON 3 ENTRADAS SE 30...

Page 15: ...HEP 306 HEP 312D HA 200 5 21 8 11 12 14 1 CBI CN1 HEP 306 HEP 312D CN3 CN2 2 KHSO HIA 300 A V OUT V IN 3 4 CB CBO 0 1 2 3 4 SW3 ICP LR TMP TTS ICP LR MVA 300 MC 304 MVA 300 A MC 304 L CBI CBO CBI CBO...

Page 16: ...3 SW1 B M1 SE 300V04 1 A UL SE 300V04 1 UL MULTI FLAT VIDEO ENTRY INSTAL LATION USING A CAMERA SEPARA TED FROM THE ENTRY PANEL CEN TRALIZED VIDEO HANDSETS POWER SUPPLY EQUIPO DE VIDEOINTERCOMUNI CACIO...

Page 17: ...3 SW2 XC XT SW1 B M1 B B SE 300V04 1 A UL CP 1 2 OUT B M1 M2 SW0 SW2 SW4 SW3 1 SW1 XDV 304 YVM 300 SW3 SW1 B M1 SW3 SW1 B YKP 300 YV M1 CP CN1 CN1 M1 B M1 NVM 300 NC 321 3 4 IN SW1 SW1 SE 300V04 1 B U...

Page 18: ...L 12V HPC 1 HA 200 HIA 300 ICP LR KHPS KHPD HTS HEP 306 HEP 312D HA 200 5 21 8 11 12 14 2 CBI CN1 HEP 306 HEP 312D CN3 CN2 HIA 300 A V OUT V IN 3 4 CB CBO CBO B VLS 101 B V V A 1 2 3 1 2 3 4 5 0 1 2 3...

Page 19: ...M1 NVM 300 NC 321 SW1 SW1 YVM 300 SW3 SW1 B M1 SE 300V05 1 A UL SE 300V05 1 UL MULTI FLAT VIDEO ENTRY INSTAL LATION WITH 1 ENTRANCE CEN TRALIZED VIDEO HANDSETS POWER SUPPLY EQUIPO DE VIDEOINTERCOMUNI...

Page 20: ...3 SW2 XC XT SW1 B M1 B B SE 300V05 1 A UL CP 1 2 OUT B M1 M2 SW0 SW2 SW4 SW3 1 SW1 XDV 304 YVM 300 SW3 SW1 B M1 SW3 SW1 B YKP 300 YV M1 CP CN1 CN1 M1 B M1 NVM 300 NC 321 3 4 IN SW1 SW1 SE 300V05 1 B U...

Reviews: