Maintenance (must be carried out only by qualified technicians)
|
19
6 720 648 592 (2011/06)
B
Undo magnetic unit connector.
B
Remove thermocouple.
B
Replace damaged component with new one and refit
using the reverse of the procedure set out in the table
above.
Function check
Flue gas safety device function check:
B
Disconnect flue pipe;
B
Replace with pipe (about 50 cm long) with sealed
end;
B
Fit pipe vertically;
B
Start up appliance at rated output and set
temperature control to maximum temperature;
Under those conditions, the appliance should shut
down after two minutes. Remove temporary pipe and
reconnect flue pipe.