30
Service menu
Sense II – 6 720 818 367 (2015/10)
7.1.1 System data menu
Settings for the entire heating system can be made in this
menu. For example, the value for the minimum outside
temperature or the thermal storage capacity of the heated
building. Additional settings for heating circuit 1 and DHW
system 1 are available in this menu (if directly installed at the
heat source).
Settings in
bold
represent factory default settings
Minimum outside temperature
The minimum outside temperature is the average value of each
of the coldest outside temperatures or recent years, and it has
an influence on the heating curve. The value for the region can
be taken from the required heat load calculation that should be
done for every building or from the climate zone chart or from
Tab. 17.
▶ Set the minimum outside design temperature for the
heating system (UK default is -3 °C).
Menu item
Adjustment range
description
Low loss hdr.
sensr. instll.
No low-loss header
No low loss header is installed
At the boiler
Low loss header installed, temperature sensor connected to heat source (boiler)
At the module
Low loss header installed, temperature sensor connected to module (i.e. MM 100/
MM 200)
Header w/o sensor
Low loss header installed, no temperature sensor is connected. If a heat requirement is
present, the heating pump is in permanent operation.
Config. DHW at
boiler
No DHW
Hydraulic connection of DHW system I to heat source (boiler)
3-way valve
Primary pump
Config. of HC1
at boiler
(only with heat
source with
EMS 2)
Information:
Configure hydraulic and electrical connection of heating circuit 1 made at
the heat source (boiler)
No heating circuit
Heating circuit 1 not directly connected to heat source (boiler)
No own heating
circuit pump
Internal boiler pump serves also as pump in heating circuit 1
Own pump
Heating circuit 1 is supplied by a dedicated heating pump (connected to heating
appliance or module (MM 100/MM 200))
Boiler circuit
pump
None
The heat source pump serves as a heating circuit pump.
System pump
The pump in the heat source must be running for every heat requirement. If a low loss
header is present, the internal pump is always a system pump.
Min. outdoor
temperature
– 35 ...
– 3 (UK)
... 10 °C
With weather-compensated control the minimum outside temperature affects the
heating curve (
Minimum outside temperature, page 30 and Menu for setting of the
Damping
Yes
The set building type affects the measurement of the outside temperature. The outside
temperature influence is delayed (dampened) depending on insulation levels of the
building.
No
The measured outside temperature influence is not delayed and its impact on meeting
the target room temperature is immediate in weather compensation mode.
Type of building
Measure of the thermal storage capacity (insulation) of the heated building (
Heavy
High storage capacity
Medium
Medium storage capacity
Light
Low storage capacity
Table 16 Settings in the system data menu
Minimum outside temperature in °C
Amsterdam
– 10
Marseilles
– 6
Athens
– 2
Moscow
– 30
Berlin
– 15
Naples
– 2
Brussels
– 10
Nice
0
Budapest
– 12
Paris
– 10
Bucharest
– 20
Prague
– 16
Table 17 Minimum outside temperatures for Europe