Appliance information
6720814332 (2018/04)
9
2.14
Specifications
2.15
Product data on energy consumption
The product data on energy consumption can be found in the operating
instructions for the user.
50-V2
65-V2
85-V2
100-V2
General Information
Unit
Rated output G20 (50/30 °C) [P
n
cond]
kW
14.3 – 49.9
14.3 – 69.5
20.8 – 84.5
20.8 – 99.5
Rated output G20 (80/60 °C) [P
n
]
kW
13.0 – 46.5
13.0 – 62.6
18.9 – 80.0
19.0 – 94.5
Rated input G20 [Q
n
(Hi)]
kW
13.3 – 47.5
13.3 – 64.3
19.3 – 82.0 19.3 – 96.5
Efficiency G20 (37/30 °C) partial load 30% in accordance with EN 15502
%
108.2
107.8
107.9
107.9
Efficiency G20 (80/60 °C) full load
%
97.7
97.4
96.7
97.0
Standby loss in accordance with EN 15502
%
0.18
0.14
0.11
0.09
Seasonal efficiency, heating curve (75/60 °C)
%
106.1
106.8
107.1
106.7
Seasonal efficiency, heating curve (40/30 °C)
%
109.2
109.4
109.7
109.5
Pump over-run time
min
5
Residual head of fan (p
max
)
Pa
85
130
195
220
IP classification [IP rating]
IP X4D (B
23
, B
33
: X0D)
Flue categorisation (according to EN 15502)
B
23
, B
33
, C
13
, C
33
, C
43
, C
53
, C
63
,C
83
, C
93
Temperature classification in accordance with EN 14471
T120
Appliance fuse
230 V, 5AF
Mains voltage, frequency [U]
230 V, 50 Hz
Electrical power consumption (without a pump group),
standby / partial load / full load
W
6 / 18 / 41
6 / 18 / 82
6 / 25 / 102
6 / 25 / 155
Permissible ambient temperature
°C
0 – 40
Maximum flow temperature [Tmax]
°C
90
Maximum operating pressure [PMS]
bar
4
Maximum condensate accumulation rate
l/h
6.0
7.6
9.3
11.0
Connections
Flue gas connection/concentric air supply
mm
80/125
100/150
Heating flow/return pipe (boiler)
inch
G 1½
Gas connection (boiler)
inch
R 1
Condensate drain (flexible hose external diameter)
mm
24
Emission levels in accordance with EN 13384
CO
2
content with natural gas G20, partial load/full load
%
8.9 / 9.3
8.9 / 9.3
8.9 / 9.3
8.9 / 9.3
CO output G20 at full load
ppm
33
57
83
100
NO
x
emission G20 at full load in accordance with EN 15502 (average)
mg/kWh
15
24
21
35
NO
x
class
5
Flue gas mass flow rate at max. rated output
g/s
22.2
29.8
37.7
43.8
Flue gas temperature at 80/60 °C, partial load/full load
°C
57 / 60
57 / 62
57 / 66
57 / 68
Flue gas temperature at 50/30 °C, partial load/full load
°C
34 / 39
34 / 39
34 / 49
34 / 53
Differential pressure gas/air (with partial load)
Pa
-5
Dimensions and weight
Height × width × depth
mm
980 x 520 x 465
Height × width × depth including pump group
mm
1329 x 520 x 465
Weight (dry)
kg
70
Pump group
Heating flow pipe
inch
G 1½
Heating return pipe, male thread with flat gasket
inch
G 1½
Gas
inch
G 1
Electrical power consumption WILO Stratos PARA 25/1-8, min./max.
W
8 / 140
Maximum current drawn WILO Stratos PARA 25/1-8
A
0.95
Table 4 Specifications
The information in brackets corresponds to the
information on the data plate.