Bosch Worcester Danesmoor 12/14 Installation And Servicing Instructions Download Page 5

4.1 

The appliance is not suitable for external installation unless

a suitable enclosure is provided.

4.2 

The  appliance  should  be  positioned  on  a  non-combustible

solid  base  as  near  to  the  flue  location  point  as  possible.    Care
should  be  taken  to  ensure  that  the  appliance  is  level;  use
packing at the corners where necessary.

4.3 

When  fitting  a  LLD  or  RS  model,  the  rear  of  the  appliance

must  be  positioned  against  an  external  wall  such  that  the  flue
terminal  can  safely  discharge  the  flue  gases  as  described  in
Section 7.

4.4 

The  following  clearances  must  be  left  to  allow  access  for

installation and servicing:

(a) Above - 300mm  
(b) In front - 600mm 
(c) Right and left hand side – sufficient for panel 

removal and access to pipe connections where 
required.

See Figs. 2 and 3.
For installation and servicing of the appliance the cabinet should
be removed as follows:

5.1 

Remove the cabinet top panel by lifting squarely upwards to

release the four ball stud connections.

5.2 

Remove the front  panel  by pulling the bottom of the panel

forwards to release the ball studs and lifting the panel upwards
and forwards to release from its supporting ledge.

5.3 

The side panels are removed by firstly following procedures

5.1  to  5.2  as  described  above,  then  remove  screw  (A)  from  the
side panel base and the three screws located in the upper flange
of each side panel.  Ease the panel clear of the electrical control
box and slide  forwards to release from the locating lugs on the
base plate.

5.4 

The control box can be removed by undoing the four screws

in the top access cover and then removing the wing nut on the
underside  of  the  control  box.  The  thermostat  phials  should  be
carefully  removed  from  the  phial  pocket  and  the  control  box
placed  in  a  safe  place  taking  care  not  to  kink  the  thermostat
capillary tubes.

5.5 

On  the  RS  balanced  flue  model,  remove  the  burner  box

cover by pulling forwards to release the ball studs. This will be
found easier by pulling on one side of the handle first to release
two of the ball studs and then repeating on the other side. Take
care not to pivot the remaining two ball studs too far around as
this will cause damage to the spring clips.

OPEN FLUE MODEL ( CF/LLD )

This includes conventional flue and standard low level and high
level horizontal discharge kits.

6.1

In  order  to  ensure  clean  and  efficient  combustion  an

adequate  supply  of  air  must  be  delivered  to  the  combustion
chamber.  To  provide  sufficient  air  a  suitable  inlet  should  be
provided into the room or space in which the boiler is situated,
the sizes of which are given in Table 5. An air brick or other form
of  continuous  air  supply  may  have  to  be  built  into  the
installation in order to ensure an adequate supply of air.

6.2

If the appliance is to be installed in a confined space or com-

partment two air vents are required, one at high level and one at
low level. The minimum free area of each vent is given in Table 6
and  depends  whether  the  air  is  taken  from  another  room  or
from  outside  the  building.  Where  the  air  is  taken  from  another
room that room must contain an air inlet as described in 6.1.

6.3

There must be sufficient clearance around the appliance to

allow  proper  circulation  of  ventilation  air.  The  clearances
required for installation and servicing will normally be adequate
for ventilation. See Section 4.4.

ROOM SEALED BALANCED FLUE MODEL ( RS )

6.4 

The  appliance  does  not  require  a  separate  vent  for

combustion air.

6.5 

Installation  in  cupboards  or  compartments  require

permanent vents for cooling purposes, one at high level and one
at low level, either direct to outside air or to a room. Both vents
must  pass  to  the  same  room  or  be  on  the  same  wall  to  the
outside air. The minimum air vent free area is given in Table 7.

6.6 

There must be sufficient clearance around the appliance to

allow  proper  circulation  of  ventilation  air.  The  clearances
required for Installation and Servicing will normally be adequate
for ventilation. See Section 4.4. 

6. Air Supply

5. Removal of the Cabinet

4. Siting the Appliance

5

Table 6. Minimum Air Vent Free Area for Open Flue
appliances installed in a compartment.

Appliance

Ventilation to room or

Ventilation to outside

model

internal space

High Level

Low Level

High Level

Low Level

12/14

154cm

2

231cm

2

77cm

2

154cm

2

15/19

209cm

2

314cm

2

105cm

2

209cm

2

20/25

275cm

2

413cm

2

138cm

2

275cm

2

Table 7. Minimum Air Vent Free Area for Room Sealed
appliances installed in a compartment.

Appliance

Ventilation to room or

Ventilation to outside

model

internal space

High Level

Low Level

High Level

Low Level

12/14

154cm

2

154cm

2

77cm

2

77cm

2

15/19

209cm

2

209cm

2

105cm

2

105cm

2

20/25

275cm

2

275cm

2

138cm

2

138cm

2

APPLIANCE

AREA OF AIR INLET

cm

2

in.

2

12/14

77

12

15/19

105

16.5

20/25

138

21.5

Table 5. Minimum Combustion Air Inlet Free Area for
Open Flue appliances

All manuals and user guides at all-guides.com

Summary of Contents for Worcester Danesmoor 12/14

Page 1: ...ater and Central Heating 12 14 MINIMUM 12 kW 41 000 Btu h MAXIMUM 14 kW 48 000 Btu h 15 19 MINIMUM 15 kW 51 000 Btu h MAXIMUM 19 kW 65 000 Btu h 20 25 MINIMUM 20 kW 68 000 Btu h MAXIMUM 25 kW 85 000 Btu h THESE INSTRUCTIONS APPLY TO UK MODELS ONLY THESE INSTRUCTIONS ARE TO BE LEFT WITH THE APPLIANCE All manuals and user guides at all guides com a l l g u i d e s c o m ...

Page 2: ...as not fulfilled his obligations to record the information required by the initiative It is important that The services and the system are properly flushed as specified The User is clearly instructed on the correct operation of the appliance The benefits of regular servicing are explained to maintain the efficiency and extend the life of the appliance 2 1 These instructions cover both conventional...

Page 3: ...r circumstances Central Heating and Hot Water Mode The appliance will supply heat to the central heating system as required The water supplied to the central heating circuit can be set to the desired temperature by adjusting the heating control thermostat located on the facia panel SPECIFICATIONS Model 12 14 15 19 20 25 POWER SUPPLY 230V 50 Hz 230V 50 Hz 230V 50 Hz IP RATING IP 20 IP20 IP 20 HEATI...

Page 4: ... kW Btu hr kW Btu hr Output Kg h l h 28 Sec Kerosene 0 50 60 ES 110 1 40 1 77 215 10 5 8 5 17 58 000 15 51 000 28 Sec Kerosene 0 55 80 EH 115 1 59 2 01 225 10 5 8 75 19 65 000 17 58 000 28 Sec Kerosene 0 60 60 ES 105 1 78 2 25 235 11 5 9 0 21 5 73 000 19 65 000 35 Sec Gas Oil 0 50 80 S 155 1 80 2 12 235 11 5 9 0 21 5 73 000 19 65 000 NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE 15 19 Tabl...

Page 5: ...efficient combustion an adequate supply of air must be delivered to the combustion chamber To provide sufficient air a suitable inlet should be provided into the room or space in which the boiler is situated the sizes of which are given in Table 5 An air brick or other form of continuous air supply may have to be built into the installation in order to ensure an adequate supply of air 6 2 If the a...

Page 6: ...screw Pressure relief valve Central heating flow Pump Burner Front panel Expansion vessel Electrical panel User operating switch Optional programmer position Top panel Thermostat knob Fire valve clip Manual reset over heat thermostat phial Automatic reset high limit thermostat phial Control thermostat phial Split pin Control Box Assembly All manuals and user guides at all guides com a l l g u i d ...

Page 7: ...e relief valve Central heating flow Pump Burner Front panel Expansion vessel Electrical panel User operating switch Optional programmer position Top panel Thermostat knob Fire valve clip Burner cover Rear air duct Rear air duct access cover Manual reset over heat thermostat phial Automatic reset high limit thermostat phial Control thermostat phial Split pin Control Box Assembly All manuals and use...

Page 8: ...terminal arrangement 7 3 Room Sealed Balanced Flue Model RS The appliance is supplied ready for installation as a low level discharge balanced flue system by the simple addition of one of the flue terminal kit options shown in Fig 6 Details of the installation procedure are included in the Flue Terminal Installation instructions supplied with the terminal kit Alternatively a range of room sealed b...

Page 9: ...Discharge 4 to 7 Single Skin Wall For use with non standard single skin walls up to 182 mm thick Where noise emission from the flue terminal is likely to be of concern it is recommended that the standard 12 in terminal is used and the appliance stood away from the wall to take up the extra terminal body length c Rear Discharge Extension Kit 12 to 36 Wall X For use where the wall thickness exceeds ...

Page 10: ...nal facing the terminal Not allowed 1200 K Vertically from a terminal on the same wall Not allowed 1500 L Horizontally from a terminal on the same wall Not allowed 750 M Above an intersection with the roof 600 Not applicable 732 N From a vertical structure on the side of the terminal 750 Not applicable 750 O Above a vertical structure less than 750mm from the side of the terminal 600 Not applicabl...

Page 11: ...b The oil supply pipe should be laid as level as possible to avoid air pockets and unnecessary friction losses c The following components should be fitted in the fuel line between the storage tank and burner 1 A manual isolating valve installed as close to the tank as possible 2 A fire valve in accordance with BS5410 as shown in Fig 10 The fire valve should be fitted externally with a fire detecti...

Page 12: ...um Fire valve to BS 5410 Fire valve to BS 5410 Isolating valve Isolating valve Fire detection element Filter Burner Burner Wall Wall b Double pipe system Isolating valve Non return valve Non return valve Fire detection element Isolating valve Oil tank c Single pipe lift system with de aerator Fire valve to BS 5410 H 3 5 m 11 5 ft maximum Burner Wall Fire detection element De aerator H 3 5 m 11 5 f...

Page 13: ...tems when all of the radiators are fitted with thermostatic radiator valves 9 5 The pressure jet burner fitted to the appliance has full auto matic control and hence there is no requirement for heat leak radiators 9 6 Any unused boiler tappings should be plugged prior to filling 9 7 The primary system should be flushed and treated in accordance with the recommendations of BS 7593 before the system...

Page 14: ...The filling point must be at low level and must never be a permanent direct fixing to the mains water supply 9 16 Water loss must be replaced See Fig 13 The connection should be made to the central heating return as close to the appliance as possible 9 17 The make up vessel where fitted must be fitted with a non return valve 9 18 Repeated venting loses water from the system It is essential that th...

Page 15: ...16a A plug in colour co ordinated 2 channel electronic programmer is available from Worcester Heat Systems Limited Full instructions covering installation and operation of the programmer are included with the kit The programmer will give fully independent central heating CH and hot water HW programmes when the switch on the rear of the unit is set to P If an external programmer is to be fitted to ...

Page 16: ...ations having pumped circulation to both the domestic hot water and radiator circuits The domestic hot water and radiator circuits are independently controlled by two motorised valves via a cylinder thermostat and a room thermostat Both thermostats switch the water circulator and the boiler on and off 10 9 Honeywell Y Plan See Fig 19 The Y Plan provides complete control on installations having pum...

Page 17: ... 1 to 3 and link 2 to 4 and make link 3 to 4 10 WAY JUNCTION BOX NOTE If a frost thermostat is required it can be wired to the remote junction box NOTE The 10 way junction box must be a terminal block type and current rated to at least 5 amps Remote Pre wired Junction Box OUTSIDE BOILER INSIDE BOILER 7 8 910 X External Pump disconnect and remove Pump supplied in boiler NOTE Optional Worcester Prog...

Page 18: ...ve link 1 to 3 and link 2 to 4 and make link 3 to 4 Grey White Blue Brown Room thermostat Pump supplied in boiler N E NL HEAT SYSTEMS HEATING ADVANCE OFF TWICE ONCE ON OFF TWICE ONCE ON SELECT LOCK SET YES SELECT PM TUE HOT WATER ADVANCE Burner Socket Optional Worcester Programmer Cylinder Thermostat C 1 2 Mid Position Valve Honeywell V4073A E N L N E E N 1 2 3 4 5 6 7 8 9 1112131415 10 Blue Brown...

Page 19: ...ith the open grommet supplied in the plastic bag 4 Slacken the pipe retaining clip screw located directly below the grommet hole When using 12mm copper pipe replace the clip with the larger one supplied 5 Bend a piece of 10mm or 12mm copper tube as selected to the correct profile to allow the pipe to be fed down the side of the appli ance Make a slight chamfer on the end of the pipe to be fed thro...

Page 20: ... using a 5mm Allen key Note It is important that a good seal is made between the burner and the boiler to prevent re circulation of the flue gases from the combustion chamber to the burner inlet or the room in the case of a CF LLD appliance 3 On the RS balanced flue model feed the electrical lead back through the hole in the burner surround housing and fit the grom met into the hole ensuring a sea...

Page 21: ...e correctly located If the baffles are correctly located then reduce the pump pressure since nozzle variations of up to or 15 may occur 12 15 Remove the oil pressure gauge and manifold and check all oil system joints for any signs of leakage 12 16 On the RS balanced flue model fit the burner cover box supplied in the flue terminal kit by lining up the four ball studs and the polarising pin in the ...

Page 22: ... nozzle line and rotate the adjusting disc one turn anti clockwise to move forward by 1 mm Output Dimension kW Head Type A 15 PL 6 7 21 5 10 3 mm 17 PL 6 7 21 5 10 5 mm 19 PL 6 7 21 5 10 5 mm Fig 22 Electro Oil Inter B11 Burner 20 25 model Combustion Head Air control indicator Photocell Air adjustment screw 4 mm hexagonal head Transformer Control box Oil pump Pressure adjustment screw Draught tube...

Page 23: ... 2 Pre Service Check 1 Remove the cabinet front and top panels as described in Section 5 2 On the RS balanced flue model remove the burner cover box as described in Section 5 5 3 Operate the appliance and system noting any faults which may need to be corrected during the service 14 3 Cleaning the Burner IMPORTANT Disconnect the electrical supply at the mains before commencing any servicing Turn of...

Page 24: ...e of a CF LLD appliance 14 4 Remove the paper element from the external oil filter and replace If the filter contains a washable element then thoroughly clean in Kerosene or white spirit and re assemble into the filter 14 5 Clean the air ducts RS balanced flue model only 1 Remove the rear duct top cover 2 Shine a light down the rear duct and inspect both the rear and under duct for any sign of deb...

Page 25: ...ogrammer open circuit Check by linking 8 and 9 on the connector Faulty control box Replace if necessary Flue draught incorrect Check flue draught Combustion settings incorrect Set up as in installation instructions Faulty nozzle Replace nozzle HIGH SMOKE NUMBER Faulty nozzle Replace nozzle Incorrect combustion settings Readjust as in installation instructions Oil pressure incorrect Adjust to recom...

Page 26: ...ox Base Satronic S01 S701 1 8 716 142 782 0 Ignition Electrode 1 8 716 142 752 0 Motor B9 AEG or Simel 70 W 1 8 716 156 597 0 Motor B11 AEG FHP 90W 1 8 716 142 732 0 Oil Pump B9 Danfoss BFP41L3 1 8 716 142 743 0 Oil Pump B11 Danfoss BFP11L3 1 8 716 142 736 0 Transformer Danfoss EBI 052F0030 excludes cable 1 8 716 156 696 0 Mechanical Shut Off Valve 1 8 716 156 658 0 Flexible Oil Line Kit WHS 1 8 7...

Page 27: ...27 All manuals and user guides at all guides com ...

Page 28: ...inued improvement All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application 8 716 114 733a 11 07 Worcester Heat Systems Limited Bosch Group Cotswold Way Warndon Worcester WR4 9SW Telephone 01905 754624 Fax 01905 754619 Technical Helpline 08705 266241 www worcester bosch co uk All manuals and user guides at all guides com ...

Reviews: