Installation Instructions
for the DS950 Series
TriTech
®
PIR/Microwave Intrusion Detectors
1.0
Specifications
•
Dimensions (HxWxD):
5 in. x 2.8 in. x 2.2 in.
(12.7 cm x 7.1 cm x 5.6 cm)
•
Input Power:
9 VDC to 15 VDC, 22 mA DC nominal
(up to 52 mA DC during walk testing,
stored alarms, or trouble conditions).
Use only an Approved Limited Power
Source.
•
Standby Power:
No internal standby battery.
Standby power
must
be provided by
an Approved Limited Power Source.
For each hour of standby time
needed, 22 mAh is required.
A
minimum of 4 hrs. (88 mAh) is
required for UL Listed requirements.
•
Alarm Relay:
Silent operating Form "C" reed relay.
Contacts rated 3 W, 125 mA,
28 VDC maximum for DC resistive
loads; and protected by a 4.7
Ω
,
0.5 W resistor in the common "C"
leg of the relay. To be connected to a
SELV (Safety Extra-Low Voltage) circuit
only. Do
not
use with capacitive or
inductive loads.
•
Tamper:
Normally Closed (with cover on).
Contacts rated at 28 VDC, 125 mA
max. To be connected to a Safety
Extra-Low Voltage (SELV) circuit only.
Connect tamper circuit to 24-hour
protection circuit.
•
Temperature Range:
-40°F to +120°F (-40°C to +49°C).
For UL Listed requirements, the
temperature range is +32°F to +120°F
(0°C to +49°C), indoor use.
•
Microwave Frequency:
DS950:
10.525 GHz (UL Listed)
DS950A:
10.687 GHz (Export only,
not
UL
Listed)
DS950B:
9.9 GHz (Export only,
not
UL Listed))
•
Coverage:
Broad (standard):
50 ft. by 50 ft. (15 m by 15 m)
Long Range (optional):
100 ft. by 10 ft. (30 m by 3 m)
•
Internal Pointability:
+2° to –10° Vertical, ±10° Horizontal.
•
Options:
B328 Gimbal Mount Bracket, B335
Low Profile Swivel Mount Bracket,
B338 Ceiling Mount Bracket, OLR92
Long Range Barrier Lens, TC6000
Test Cord
NOTE:
Use of a bracket may reduce range and increase dead zone
areas.
•
Reading Bosch Security Systems, Inc. Product Date Codes
For Product Date Code information, refer to the Bosch Security
Systems, Inc. Web site at:
http://www.boschsecurity.com/
datecodes/
.
•
Compliance:
This device complies with Part 15 of the FCC Rules
and with RSS-210 of Industry and Science Canada. Operation is
subject to the following two conditions:
(1) this device may not cause harmful interference, and
(2) this device must accept any interference received,
including interference that may cause undesirable
operation.
Changes or modifications not expressly approved by Bosch
Security Systems can void the user’s authority to operate the
equipment.
2.0
Installation Considerations
NOTE:
The DS950 is
not
recommended for installations containing
pets or small animals. Use the DS820 or DS835 for such
installations.
•
Never install the detector in an environment that causes an alarm
condition in one technology. Good installations start with the LED
OFF
when there is no target motion. It should never be left to
operate with the tri-color LED in a constant or intermittent green,
yellow, or red condition.
•
Point the unit away from outside traffic (roads/alleys).
NOTE:
Microwave energy will pass through glass and most
common non-metallic construction walls.
•
Avoid installations where rotating machines (e.g. ceiling fans)
are normally in operation within the coverage pattern. Point the
unit away from glass exposed to the outdoors and objects that
may change temperature rapidly.
NOTE:
The PIR detector will react to objects rapidly changing
temperature within its field-of-view.
•
Eliminate interference from nearby outside sources.
3.0
Mounting
•
Select a location likely to intercept an intruder moving
across
the
coverage pattern. The surface should be solid and vibration-
free. Mounting height range is 6 to 8 feet (1.8 to 2.4 m).
Recommended mounting height is 7.5 feet (2.3 m).
•
Remove the cover. Insert a flathead screwdriver into the locking
tab hole at the bottom front of the detector. Pull the cover up and
forward.
Tri-color
LED
Vertical
Adjust
Screw
Terminal
Strip
MW
0°
- 4°
- 8°
Vertical Adjust
Scale
LED
On/Off
Pins
On
Off
Memory
Jumper
Microwave
Range Adjust
_ +
NO C NC T
T M TR
Motion Monitor
and Anti-Mask
Selection Pins
PIR
Sensitivity
Selection Pins
Trouble
Memory
Microwave Noise Voltage Pins
30
1
INT
STD
Off
*
PIR Noise
Voltage Pins
Look Down
Lens
Look Down
Mask
*= Cut only if using the Memory
or 1 Day Motion Monitor features.
Walk test before cutting.
Corner Mount
Knockout (4)
Surface Mount
Knockout (2)
Wire
Entrances
Bracket Mount
Knockout
Vertical Adjust
Screw Mount
Cover Tab and
Locking Screw Hole
Wire
Entrances
•
Remove the circuit board from the base. Loosen the Vertical
Adjust Screw and slide the circuit board down, then out.
•
Break away the appropriate thin-wall wire entrance and mounting
hole coverings in the base.