Subject to change without prior notice Revised 03-11
6 720 220 046
24 TA Series
operating Pressures & Temperatures
oPerATInG PreSSureS & TeMPerATureS
environmentally Safe r-410A refrigerant
22
TA071
Full
Load
30°
40°
50°
60°
70°
80°
90°
100°
9.0
71-87
259-316
5-7
19-23
18.0
76-92
264-322
4-5
20-25
9.0
120-146
185-225
15-19
21-26
84-102
280-342
7-8
22-26
18.0
117-142
173-211
11-14
22-27
89-108
286-349
5-6
23-28
9.0
123-150
218-266
15-18
20-25
96-117
302-368
8-9
24-29
18.0
120-146
204-249
11-14
21-26
102-124
308-376
6-7
25-31
9.0
126-153
251-307
14-17
20-24
109-132
324-395
9-11
26-32
18.0
122-149
235-287
11-13
21-25
116-141
330-403
7-8
28-34
9.0
129-157
285-347
14-17
19-24
121-148
345-421
10-12
29-35
18.0
125-152
266-325
10-13
20-25
129-157
352-430
8-9
30-37
9.0
132-160
318-388
13-16
19-23
134-163
367-447
11-14
31-38
18.0
128-156
297-363
10-12
19-24
142-173
374-457
8-10
33-40
9.0
135-164
351-429
13-16
18-22
146-178
388-474
12-15
33-41
18.0
131-159
329-401
10-12
19-23
155-189
396-483
9-11
35-43
9.0
137-167
385-469
12-15
17-21
18.0
134-163
360-439
9-11
18-22
Suction
Pressure
PSIG
Water
Temp
Drop °F
COOLING
HEATING
Entering
Water
Temp. ˚F
Water
Flow
GPM
Water
Temp
Rise°F
Air
Temp
Drop °F
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Air
Temp
Rise °F
Model
Discharge
Pressure
PSIG
This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and
should not be used to estimate system charge. This chart assumes rated air flow and 80º d.b./67º w.b. entering air temperature in
cooling, 70º d.b. entering air temperature in heating. Heating data at entering fluid temperatures below 50º assumes the use of
antifreeze. As a result of continuing research and development, specifications are subject to change without notice.
Table 1 continued: operating data