![Bosch SST150-40 Installation And Operating Manual Download Page 21](http://html.mh-extra.com/html/bosch/sst150-40/sst150-40_installation-and-operating-manual_52855021.webp)
|
21
Indirect Fired Water Heaters Installation and Operating Manual
Installation & Operating Manual
8 Performance Data
Indirect Water Heater I=B=R Rating Table 8A
Model
Potable
Water
Volume
Gal.
Heat
Source
Water
Volume
Gal.
Standby
Heat Loss
F/hr
Continuous
Draw
Rating
Gal/hr
First
Hour
Rating
Gal/hr
Minimum
Heat Output
Rate from
Heat Source
Btu/hr
Minimum
Heat
Source
Flow Rate
GPM
Tank Heat
Source
Friction
Loss Feet
W.C
SST150-40
40.0
1.6
0.7
181
208
115,000
14.0
4.5
SST250-65
67.0
1.9
0.5
263
327
154,000
14.0
5.7
SST300-80
81.5
2.1
0.5
285
358
171,000
14.0
6.1
SST450-119
113.4
3.2
0.4
349
459
216,000
14.0
6.5
• These ratings were obtained with a heat source output and
heat source flow rate as listed in the chart using the
parameters of the Domestic Cold Water Inlet at 58°F,
Domestic Temperature Rise of 77°F, and a Boiler
Temperature Output of 180°F. Other results will be
obtained under different conditions.