![Bosch SM Split CS Series Installation, Operation And Maintenance Manual Download Page 30](http://html.mh-extra.com/html/bosch/sm-split-cs-series/sm-split-cs-series_installation-operation-and-maintenance-manual_44212030.webp)
SM Split CS Series Heat Pump
SM Split CS Series Heat Pump
8733825873 (2020/05)
30
|
Troubleshooting
Subject to change without prior notice
SmartStart Assist Troubleshooting
Table 14 SmartStart Assist Troubleshooting
SmartStart Assist Flashing Sequence
Fig. 14 SmartStart Assist Flashing Sequence
Red Led
Relay
Contact*
Condition
Action
FULLY ON +
11/12
Min. recovery time between starts
and/or recovery time between stop to
start
Auto reset when minimum recovery
time elapses
2 FLASHES
11/14
Undervoltage (Ue<190VAC)
Auto reset with 5 mins. recovery **
3 FLASHES
11/14
Overcurrent (>80A for >1 sec.)
Auto reset with 5 mins. recovery
4 FLASHES
11/14
relay protection
Auto reset with 5 mins. recovery***
5 FLASHES
11/14
incomplete ramp
Auto reset with 5 mins. recovery
N/A
11/12
Supply phase loss
Physical check
N/A
11/12
Idle state
N/A
11/12
Ramping state
N/A
11/12
Bypass mode
Green Led
Relay
Contact*
Condition
Action
FLASHING
11/12
Power supply alarm
Replace SmartStart device
FULLY ON
11/12
Idle State
RSBS waiting for control signal to
start
+ APPLICABLE TO RSBS2332A2V.2C24HP. FOR MODELS,NO INDICATION ON THE RED LED IS PROVIDED
*APPLIES ONLY TO RSB23XXA2V22C24..MODELS
**MONITORED DURING IDLE AND BYPASS
***REFER TO NOTE 6 IN MODE OF OPERATION SECTION OF THE SSA IOM
****REFER TO VOLTAGE DIPS AND INTERRUPTIONS SECTION FOR MODE OF OPERATION OF THE SSA IOM
During recovery from an alarm condition, the red LED will flash at twice the normal flashing frequency
between successive flashing cycles as shown above to indicate that the SmartStart Assist is in recovery
mode, which lasts for five minutes.