7.10.5 Pressure and Flow Command Limit
Code
Name
Setting range
Default
Min.
Attri.
F4.00 Protection function configura-
tion word
0...15
Bit0: Pressure sensor failure (PSF)
Bit1: Actual pressure monitoring
Bit2: p/Q max. command limit
Bit3: Oil changing detection
0
-
Run
F4.21 Minimum pressure command
limit
0.0...[F4.22] bar
5.0
0.1
Stop
F4.22 Maximum pressure command
limit
[F4.21]...1,000.0 bar
250.0
0.1
Stop
F4.23 Minimum flow command limit 0...[F4.24] rpm
200
1
Stop
F4.24 Maximum flow command limit [F4.23]...5,000 rpm
3,000
1
Stop
Tab. 7-23: Parameter list of pressure and flow command limit
The minimum pressure and flow command limitation (F4.21 and F4.23) works all
the time, independently to any control bit. That means if the setting pressure or
flow command is lower than [F4.21] or [F4.23], it will be limited to [F4.21] or
[F4.23] without any error / warning message.
The maximum pressure and flow command limitation can be activated via bit2 of
F4.00. This function will check whether the pressure or flow command given by
customer exceeds the limitation set in [F4.22] and [F4.24]. If a given command
exceeds its limitation, the effective command value will be limited to the maxi-
mum limit, and a warning signal will be raised.
Bosch Rexroth AG
Block Diagram of Main Functions
FcP 5020
50/83
DOK-RCON03-FCP5020****-QU04-EN-P