Max. inrush current
(cold start 25 °C)
40 A for nominal voltage AC 230 V
20 A for nominal voltage AC 115 V
Output voltages
+5 V
+12 V
-12 V
+20 V
ISO 6 V
Current (max.)
20 A
3 A
500 mA
2 A
200 mA
Tolerance (incl. residual ripple)
±5 %
±5 %
±5 %
±5 %
±5 %
Maximum output power
160 W
Efficiency
0.8
Fig.4-2:
Technical data of the power supply unit 115 V / 230 V
The control cabinet PC VPB 40.1 can be dam‐
aged if the power supply unit is switched off if
the total output power exceeds 160 W.
NOTICE
When maximum output currents are specified, please observe that the currents
are the maximum possible currents for the respective output voltage. However,
it is not possible to produce the maximum current from all output voltages, as
the maximum total output power of 160 W must not be exceeded.
4.3
24 V Voltage Supply
Nominal input voltage
DC 24 V
Input voltage range
DC 24 V +20 %, -15 %
Emitted interference and surge
immunity
U
max
= 35 V (for t < 100 ms)
Max. input current
6 A for nominal voltage 24 V
Max. inrush current
25 A for nominal voltage 24 V
Output voltages
+5 V
+12 V
+24 V
-12 V
ISO 6 V
Current (max.)
13 A
3 A
2 A
500 mA
200 mA
Tolerance (incl. residual ripple)
±5 %
±5 %
±5 %
±5 %
±5 %
Max. output power
110 W
Efficiency
0.8
Fig.4-3:
Technical data of the 24 V power supply unit
Bosch Rexroth AG
DOK-SUPPL*-VPB*40.1***-PR02-EN-P
Rexroth IndraControl VPB 40.1 Control Cabinet PC
20/81
Technical Data