F2026 Undervoltage in power section
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
Supported by Supply Unit:
HMV01
The DC bus voltage value is monitored by the drive controller and the
supply unit.
If the DC bus voltage falls below the minimum value determined for the
drive (see value of
P-0-0114, Undervoltage threshold
) or it reacts to
"DC bus not ok" of the module bus, the device generates the error
message F2026 if "non-fatal warning" has been set with regard to the
reaction to undervoltage in
P-0-0118, Power supply, configuration
.
If the DC bus voltage falls below 75% of the mains voltage crest value
that was detected when the mains contactor had been switched on, the
error F2026 is displayed at the device. Power is switched off!
Cause
Remedy
Power is switched off without previous drive
deactivation by means of drive enable ("AF")
Check logic for activating drive in connected control unit
Failure in power supply or overload of power supply
Check power supply
Mains failure
Check cause of mains failure, switch mains voltage on
again
See also Functional Description "Power Supply"
F2026 - Attributes
Display:
F2026
Mess. no.:
F2026 (hex)
Drive Controllers HMS, HMD,
HCS
Supply Unit HMV01.1