9.4
KCU02
9.4.1
Mounting depths
Adjusting Mounting Depths
HMV01 and HCS03 devices have greater mounting depths than the drive
connection box KCU. For connecting the drive connection box KCU to an
HMV01 or HCS03 device, you must therefore use the control cabinet adapter
which compensates the different mounting depths.
9.4.2
Touch Guard
Lethal electric shock by live parts with more
than 50 V!
WARNING
●
The appropriate touch guard must be mounted for each device following
connection work.
Never operate the device without mounted touch guard.
●
Never mount a damaged touch guard.
●
Immediately replace a damaged touch guard by an undamaged touch
guard.
●
Keep the cutouts at the touch guard as small as possible. Only remove
the cutouts if necessary.
Cutouts at the Touch Guard
●
If the DC bus and the control voltage are connected by means of contact bars,
only cutout A may be removed from the touch guard.
●
If the DC bus and the control voltage are connected by means of cables (e.g. in
case of multiple-line arrangement), cutouts A, B and C may be removed from
the touch guard.
●
At the first and last device in a line of interconnected devices, cutouts may not
be removed from the outer side of the touch guard.
Tab. 9-3:
Cutouts at the Touch Guard
DOK-INDRV*-KCU02+KSM02-PR03-EN-P
Bosch Rexroth AG
255/337
Rexroth IndraDrive Mi Drive Systems with KCU02 KSM02, KMS02/03, KMV03, KNK03
Mounting and installation
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01