6
Mounting and installation
6.1
Mounting HCS01 Devices in the Control Cabinet
1
Mounting surface in control cabinet
2
Left-hand mounting
3
Back-side mounting (standard mounting)
4
Right-hand mounting
Fig. 6-1:
Options for Mounting
Notes on Mounting
●
Observe the minimum distances to be complied with for mounting (see
technical data or dimensional drawings).
The specified horizontal minimum distance refers to the distance to
neighboring devices or equipment installed in the control cabinet (such
as cable ducts) and not to the distance to the control cabinet wall.
●
The back-side mounting (back of device directly mounted to mounting
surface in control cabinet) is the standard and should be used, if possi‐
ble.
●
The left-hand or right-hand mounting (left or right side of device directly
mounted to mounting surface in control cabinet) can be used, if the
mounting clearance between control cabinet wall and control cabinet
front is not sufficient for back-side mounting.
NOTICE! Risk of damage by high temperatures! At the back of the
HCS01 devices, there are braking resistors which can become very hot
during operation. When arranging the devices in the control cabinet,
make sure there aren't any heat-sensitive materials close to the braking
resistors.
In the case of left-hand or right-hand mounting, you must not pile the de‐
vices. Each device must have immediate contact to the control cabinet
wall.
●
Tightening torque of the mounting screws: 6 Nm
●
On the sides of the devices, there are adhesive labels with notes on
safety. The supplied accessory
additionally contains these adhe‐
sive labels. If the adhesive labels at the devices are no longer visible af‐
ter mounting, place the adhesive labels from the
clearly visibly at the device or in the immediate vicinity of the device.
DOK-INDRV*-HCS01******-PR05-EN-P
Bosch Rexroth AG
121/341
Rexroth IndraDrive CsDrive Systems with HCS01
Mounting and installation