17 / 36
IndraControl XFE 01.1
Installation notes
Bosch Rexroth AG
R911345570, Edition 06
10.2 Installation notes
NOTICE
Destruction of the device due to electrostatic discharge
The device contains components that can be damaged or destroyed by
electrostatic discharge. Comply with the required safety measures against
electrostatic discharge (ESD) acc. to EN 61340-5-1 when operating the
control.
•
Shielding connection for the extension module
To ensure EMC safety, connect all shieldings directly at the control cabinet entrance to a common
FE ground line.
Note:
The shielding connection set for the S20 modules may not be set for the extension modules.
•
Mounting location
The extension modules have the degree of protection IP 20 and are thus intended for use in a
closed control cabinet or control box (terminal box) of the degree of protection IP 54 or higher.
•
Mounting rail
Mount the extension modules on a 35 mm standard mounting rail. The preferred overall height of
the mounting rail is 7.5 mm (corresponds to TH 35-7.5 acc. to EN 60715).
Mount the extension modules and the extension bus base modules as described in this chapter.
Install the extension modules on a horizontally mounted mounting rail.
The fastening distance of the mounting rails may not exceed 200 mm. This distance is required to
ensure stability while mounting and dismounting the control or the extension modules.
< 200
_
Fig. 6: Mounting rail fastening (in mm)
NOTICE
Electronic damage due to fastening elements of the mounting rail
If screws and rivets are too high on the mounting rail, the bus base modules
do not really engage on the mounting rail. Use only screws and rivets with a
structural height of up to 3 mm to fasten the mounting rail.
•
End clamps
–
Fasten end clamps on both sides of the IndraControl XM station. End clamps guarantee the
correct fastening of the control and the modules connected to them on the mounting rail and
they are used as lateral end elements.
–
Always fasten the left end clamp of the station before mounting the control. This ensures the
following:
●
It impedes the shifting of the control.
●
The installation place for the end clamps is secured.
●
If the control has to be replaced, there is sufficient space to separate the control from the bus
base modules.
Mounting, dismounting and electr
ic inst
allation