02
Interfaces
7.2.1.1
Pin Assignment
Fig. 7-16:
9-pin D-SUB male and female connector strip
Connector in the small operator terminal: 9-pin D-SUB male and
female connector strip (assignment for male and female connector strip
is the same).
All signal lines are looped through from X2.1 to X2.2. The connecting
cables should be connected to every pin, including the reserved pins.
In this way, the cables can still be used in case of future bus specifica-
tion extensions.
7.2.1.2
Cable
Pin
Designation
Function
1
nc
Not Connected
2
CAN_L
CAN_L Bus Line (Dominant LOW)
3
CAN_GND
CAN Ground
4
nc
Not Connected
5
nc
Not Connected
6
CAN_GND
CAN Ground
7
CAN_H
CAN_H Bus Line (Dominant HIGH)
8
nc
Not Connected
9
nc
Not Connected
Fig. 7-17:
Pin assignment DeviceNet
The D-SUB connector strips must be shielded sufficiently. See chapter
“Shielding D-SUB Connectors“ on page 7-22.
A DeviceNet-certified cable must be used.
Cable
type
Loop resistance
Surge
impedance
Capacitance per
unit length
2 x 1.1 mm < 22.6 Ohm/km
120 Ohm
< 39.4 pf/m
2 x 0.6 mm < 91.8 Ohm/km
120 Ohm
< 39.4 pf/m
Fig. 7-18:
Data line DeviceNet