In operation
Transport
Storage
Mechanical strength
Maximum vibration
Frequency range:
10 Hz to 150 Hz
Excursion:
0.75 mm at 10 Hz to
57 Hz
Acceleration:
1 g at 57 Hz to 150 Hz
Test duration per axis:
10 frequency cycles
Frequency throughput
speed:
1 octave/min
Acc. to EN 60068-2-6,
test Fc
Max. shock:
15 g acc. to EN 60
068-2-27, no disturb-
ance of the function
Max. shock:
15 g acc. to EN 60
068-2-27, no disturb-
ance of the function
Contamination level
2
2
2
Tab. 6-1: Ambient conditions
Defective product due to gases jeopardizing
functions
NOTICE
Due to the risk of corrosion, avoid sulphurous gases (e.g. sulphur dioxide (SO
2
)
and hydrogen suphide (H
2
S)). The product is not resistant against these gases.
Failure of the product due to contaminated air
NOTICE
●
The ambient air must not contain acids, alkaline solutions, corrosive agents,
salts, metal vapors and other electrically conductive contaminants in high
concentrations
●
The devices to be installed into the housing and installation compartments
must at least comply with the degree of protection IP 54 according to DIN EN
60529.
●
The device shall be provided in a suitable fire enclosure in the end-use appli-
cation.
8/33
Ambient conditions
IndraControl VAC 08.1 CDI+ Splitter
Bosch Rexroth AG R911400465_Edition 01
Summary of Contents for rexroth IndraControl VAC 08.1
Page 1: ...IndraControl VAC 08 1 CDI Splitter Operating Instructions R911400465 Edition 01 ...
Page 6: ...IV IndraControl VAC 08 1 CDI Splitter Bosch Rexroth AG R911400465_Edition 01 ...
Page 36: ...30 33 IndraControl VAC 08 1 CDI Splitter Bosch Rexroth AG R911400465_Edition 01 ...
Page 39: ...Notes IndraControl VAC 08 1 CDI Splitter 33 33 ...