Commissioning
7.1
General information
Open connections!
NOTICE
If connections have not been closed with protective covers, liquid or dirt can
penetrate the IndraControl S67 components and destroy them. Protect all
non-required connections with protective caps to be ordered separately (see
chapter 12.9 "Protective caps" on page 131
) to comply with protection class
IP 67.
Before commissioning the IndraControl 767 station, check the following:
●
the field bus coupler is mounted properly (see
●
all necessary supply and sensor lines, as well as the S-BUS and
Ethernet cable, are securely fastened onto the appropriate connections
chapter 6 "Connecting Data and Supply Cables" on page 35
●
the S-BUS terminator is fastened (see
chapter 6.4 "Connecting S-BUS"
●
an appropriate potential equalization was executed at the system
●
the shielding was executed correctly
●
the power supply of the higher-level controller is switched on (see asso‐
ciated manual)
7.2
Compatibility Requirements
Field bus coupler requirements for the I/O
modules.
NOTICE
To use all the Sercos field bus coupler functions, such as jitter and synchroni‐
zation of the system bus and field bus, the Sercos field bus coupler places
requirements on the input and output modules. To comply with these require‐
ments, only input and output modules with the following technical index are to
be operated (see the following table for this). The technical index of the used
input and output modules are at least correspond to the index listed in the ta‐
ble. If an input or output module is not listed in the table below, it can be used
with a technical index of "AA1" or higher.
Parts number
Type code
Technical index
R911171787
S67-DI8-M8
min. AB1
R911171788
S67-DI8-M12
min. AB1
R911171789
S67-DO8-M8
min. AB1
R911171790
S67-DO8-M12
min. AC1
R911171791
S67-DO8-M8-2A
min. AB1
R911171792
S67-DO8-M12-2A
min. AB1
R911172409
S67-DIO8-M8
min. AA1
DOK-CONTRL-S67S3BKDI8*-AP03-EN-P
Rexroth IndraControl S67 Sercos Coupler 8 Digital Inputs (M8)
Bosch Rexroth AG
43/139