Status
code
Name
Description
0x1800
Timing configura‐
tion order error
Configuration order for the timing parameter is in‐
correct (e.g., timing configuration of the control is
incomplete)
0x8100
Communication
Critical errors with synchronous data exchange
0x8210
System deviation
high
Synchronization error of the S-BUS with the field
bus
0xB020
Local bus commu‐
nication error
Communication error on the S-BUS (e.g., inter‐
ruption of the S-BUS)
0xB030
Local bus configu‐
ration error
Configuration error on the S-BUS (e.g., configura‐
tion of the I/O modules was changed on the S-
BUS)
Tab. 9-30:
Supported Sercos status codes for I/O errors (C1D)
Example for diagnostic class warning (C2D)
In case of a wire break at channel 5 of module S67-DO8-M8 (slot 3), the fol‐
lowing diagnostic information is provided:
IDN/S-0-0095 "Diagnosis message"
ASCII text
= "Open load"
IDN/S-0-0390 "Diagnostic number"
Hexadecimal value (32-bit)
= 0xC10E2350
Bit 31:30 "Interpretation of the bits 29:0"
= 0b11 (standard diagnostics)
Bit 29:24 "Device profile"
= 0x01 (FSP_IO)
Bit 19:16 "Diagnostic class"
= 0x0E (warning (C2D))
Bit 15:0 "Status code"
= 0x2350 (interruption)
IDN/S-0-1500.00.32
Hexadecimal value (64-bit)
= 0x0E235005DE030005
Bit 63 "Interpretation of the status code"
= 0 (status code of the FSP_IO)
Bit 59:56 "Diagnostic class"
= 0x0E (warning (C2D))
Bit 55:40 "Status code"
= 0x2350 (interruption)
Bit 39:24 "I/O function group"
= 0x05DE (S-0-1502)
Bit 23:16 "slot number"
= 3
Bit 15:8 "slave index"
= 0
Bit 7:0 "channel number"
= 5
9.5
IP Communication
The Sercos field bus coupler S67-S3-BK-DI8-M8 provides various services
via the NRT channel using IP-based protocols:
●
Web-based management (TCP/IP, HTTP, WBM)
●
Automatic IP address assignment (BootP, DHCP)
The web-based management (WBM) allows the user to carry out the basic
configuration of the coupler. In addition, the current status of the coupler is
Bosch Rexroth AG
DOK-CONTRL-S67S3BKDI8*-AP03-EN-P
Rexroth IndraControl S67 Sercos Coupler 8 Digital Inputs (M8)
98/139
Sercos