8.2
Mechanical Installation of Rexroth Inline Terminals
8.2.1
General Information
Rexroth Inline terminals can be added in series to the right of the IndraCon‐
trol L45/L65/L85 depending on your requirements. No tool is required. On
connecting these modules in series, the potential and bus signal connection
(voltage and data routing) between the individual components of the station is
established automatically.
The terminals are mounted perpendicularly to the top-hat rail.
Once the station has been set up, individual terminals can be replaced subse‐
quently by being pulled out or plugged in without any additional tools.
Top-hat rail
The Rexroth Inline terminals are mounted to the right of the IndraControl L45/
L65/L85 on the 35 mm standard top-hat rail.
8.2.2
Mounting the Inline Terminals
Proceed as follows to latch on a terminal, see
fig. 8-2 "Latching a terminal" on
:
●
First latch on the terminal that is required to set up the station, perpen‐
dicularly to the top-hat rail (see figure A).
Ensure that all feather keys and keyways of neighboring terminals
are interlocked (see figure B).
The keyway/feather key connection connects neighboring terminals to each
other and ensures that the voltage jumpering is set up securely.
●
Then fit the connectors onto the respective terminal.
First fit the front connector shaft latch in the front release mechanism (figure
C).
Then press the connector towards the terminal until it clicks into place in the
rear release mechanism (figure D).
The keyways provided in the terminal are not continued in the con‐
nector. A terminal can only be latched on, if there is no connector
to the left of it. It must be removed at BVe.
DOK-CONTRL-ICL45L65L85-PR01-EN-P
Rexroth IndraControl L45/L65/L85 Control
Bosch Rexroth AG
51/81
Installation and Maintenance